sl40e300 / 040211
1 / 2
Data
sheet
Order information
Order number
Description
SL40.300
SL40.301
SLZ01
basic version, passive load sharing
with signal/measurement outputs, signal output connector included: Order number XFB-S-W8-MSTB 06-W8)
Screw mounting set, two needed per unit
Clever Power
SL40.300/.301
• Input: 3 AC 400...500V
• Output: 24...28V / 960W (1080W)
• No switch-off at overload
• Ideal for parallel operation
• Output for measurement and
logical signals (.301)
CUL/CSA-C22.2
EMC and
Low Volt.
UL60950 E137006
UL508 LISTED
IND. CONT. EQ.
No 950-M90
18 WM, 60°C
Directive
CB
scheme
IEC60950
Input
Construction / Mechanics *
Output
(signal outputs see overleaf)
Efficiency, Reliability etc. *
Input voltage
3 AC 400...500 V, – 15 %, + 15 %
47-63 Hz,
Suitable for IT power systems
Rated Tolerances
• Continuous operat.
• Short term (1 min)
at 24 V/40 A
340-575 V AC
300-620 V AC
Input current
3.0 A
Inrush current
< 30 A
Inrush current limiting done with a fixed 23R resistor (not a thermistor)
which is bridged after the unit is running, so losses are minimized. That
means no reset time even at a warm-start.
Fuse loading
3 A
2
s
To be fused with a 3 x 10A, B-type 'circuit-breaker' switch based on the
usual thermomagnetic overload sensing principle (used anyway to fuse
the input lines; unit has no internal fuses).
Harmonic current
emissions (PFC)
acc. EN 61000-3-2
Transient
handling
Active transient filter incorporated, so tran-
sient resistance acc.to VDE 0160 / W2 (1300 V /
1.3 ms), for all load conditions.
Hold up time
min. 15 ms
at 400 V AC, 24 V / 40 A
Housing dimensions and Weight
• W x H x D
• Free space for
ventilation
• Weight
275 mm x 124 mm x 117 mm (+ DIN rail)
above/below each 70 mm recommended
left/right each 25 mm recommended
3.3kg
Connections
(input and output)
robust screw terminals, connector size range:
• solid: 1.5...6 mm
2
(Outp.: 0.5...16 mm
2
)
• flexible: 1.5...4 mm
2
(Outp.: 0.5...10 mm
2
)
Output: Minus terminal with 2 connectors,
current handling per output: 40 A (max. acc.
to UL) resp. 56 A (max. acc. to VDE)
Design advantages:
• All connection blocks mounted on front panel for ease of access.
• PVC insulated cable can be used for all connections, as the connection
blocks are mounted in the cooler area on the underside of the unit.
• Power density: 230 W per litre housing volume.
Output voltage
24...28 V DC, adjustable by (covered) front
panel potentiometer. Adj. range guaranteed
Output noise
suppression
Radiated EMI values below EN 61000-6-3, even
when using long, unscreened output cables.
Ambient temperature
range T
amb
Operation: 0°C...+70°C (>60°C: Derating)
Storage: -25°C...+85°C
Rated continuous loading with convection cooling
• T
amb
=0°C - 60°C
• T
amb
=0°C - 45°C
24 V / 40 A (960 W) resp. 28 V / 35 A (980 W)
24 V / 45 A (1080 W) resp. 28 V / 38 A (1064 W)
short-term (< 1 min.) also at 60°C admissible
Derating
typ. 24 W/K (at T
amb
=+60°C...+70°C)
Voltage regulation
better than 2% over all
Ripple (incl. spikes)
< 50 mV
PP
(20 MHz bandw., 50
Ω measurem.)
Over-voltage protection At 32 V ± 10%: switch to hiccup mode
Front panel indicators: • Green LED on, when V
out
> U
T
, where U
T
is
ca. 2 V below Vout adjusted (24V...28V)
• Red LED on, when V
out
< U
T
Parallel operation
SL40.300: yes, no active current sharing
SL40.301: yes, active current sharing, please re-
fer to “Output Signaling” - “Current Balance”
Current sharing by balancing line (active sharing principle, SL40.301) or
’soft’ output characteristic (passive sharing principle, SL40.300; charac-
teristic switch-over by jumper as in SL20/SL30 without opening the unit)
Power Back Immunity
< 35 V
Efficiency
typ. 92.5%
(400 VAC, 24 V / 40 A)
Losses
typ 78 W
(400 VAC, 24 V / 40 A)
MTBF
SL40.300: 305,000 h
SL40.301: 268,000 h
acc. to Siemensnorm SN 29500
(24 V/40 A, 400 VAC, T
amb
= +40 °C)
Life cycle (electrolytics)
The unit exclusively uses longlife electrolytics,
specified for +105°C (cf. ’The SilverLine’, p.2).
High reliability and lifetime, as
• only 6 aluminum electrolytics and
• no small aluminum electrolytics are used.
Your partner in power supply:
European
Power Supply
Manufacturers
Association
PULS GmbH
Arabellastraße 15
D-81925 München
Tel.: +49 89 9278-0
www.puls-power.com
Fax: +49 89 9278-199
Data sheet
2 / 2
sl40e300 / 040211
Bayerns Best 50
Czech 100 Best
EuropeÕs 500
Specifications valid for 3 x AC 400V input voltage, +25°C ambient temperature, and 5 min run-in time, unless otherwise stated. They are subject to change without prior notice.
Start / Overload Behaviour
Output for measurements and signalling
(SL40.301 only)
Further Information
Startup delay
< 0.5 s
Rise time
< 0.1 s (40 A, 20,000
µF)
Overload behaviour
PULS Overload Design (see diagram at the right), thus neither
switch-off nor hiccup at overload
Advantages:
• High short-circuit current, giving large ’start-up window’: unit starts reliably even with
awkward loads (DC-DC converters, motors). No ’sticking’ as can occur with fold-back
characteristics.
• Even longer overload possible as unit does not switch off.
’Shut-Down’: Shut-down input: units switches off, if
• Input is connected to ’Signal GND’ (
∆U < 1V) or
• +20...28 V Voltage are applied to this input and ’Signal GND’ (max. 20 mA).
’Power Good’: Power-Fail / -Good
• Signal: High (24 V) at correct operation (no overload, over-temp., short-circuit). At
’low’ signal and nominal load, output remains at nominal voltage for at least 5 ms.
• Corresponding ground is ’Signal GND’ output (current source)
• Permissable load resistance:
≥ 300 Ω, e.g. 24V relais, control lamp (no dropping resistor
needed for LED), scoring logic. To get 5V level: connect this output and ’Signal GND’
via 5V zener diode (0.5W) + 1k
Ω resistor switched in parallel
’Thermal Alarm’: warning signal at over-temperature
• Signal: High (24 V) at correct operation (no over-temperature). If signal switches to
’low’ and temperature increases further, output current is lowered,
• Ground and permissable load resistance: see ’Power Good’ output
’Current Monitor’: Current measurement output, usable with
• Voltmeter
• Ammeter
1 V per 10 A output current (to ’Signal GND’ output, R
in
(volt-
meter) > 100 k
Ω)
1 mA per 10 A output current (to ’Signal GND’ output, R
in
(am-
meter) < 100
Ω)
’Current Balance’: balancing output for current sharing
• For active current sharing at parallel operation interconnect the "Current Balan-
ce" output terminals of all paralleled units. The corresponding ground is the
pole. Do not interconnect the "Signal GND" outputs. Exact output voltage re-
gulation is effective when the output current is greater than 0.4A. Current sharing
also works reliable with decoupling diodes and modules for redundancy applica-
tions.
’Signal GND’: Ground terminal for all signal outputs of this unit (not ’Current Balance’)
• Do not connect this terminal to the
terminal
of this unit (not even across a load: risk
of overload)
• Do not connect this terminal to any output of another unit (not even with ’Signal
GND’ of another unit)
• max. load current: 0.3 A
Signal ground is internally fused by a self-curing fuse (polyswitch)
For further information, especially about EMC, Connections, Safety, Approvals,
Mechanics und Mounting see page 2 of the „The SilverLine“ data sheet. For detailed di-
mensions please see the SilverLine mechanics data sheet SL40.
0
20
40
60
80
340
380
420
460
500
Input voltage Vin [V]
Hold-up time [ms
]
Iout = 16 A
Iout = 24 A
Iout = 32 A
Iout = 40 A
Iout = 45 A
82%
84%
86%
88%
90%
92%
94%
5
10
15
20
25
30
35
40
45
Output current Iout [A]
Efficiency [%
]
3 x 340 VACin
3 x 400 VACin
3 x 480 VACin
0
4
8
12
16
20
24
28
32
0
10
20
30
40
50
Vout=24V, Single Mode
Vout=24V, Parallel Mode
Vout=28V, Single Mode
Vout=28V, Parallel Mode
Output current Iout [A]
Output vol
tage V
out [V
]
SL40.300:
SL40.301: no switch-over,
charact. as SL40.300, Single Mode
Efficiency (typ., at V
out
=24V)
Hold-up time (min., at V
out
=24V)
Output V/I characteristic (typ.)