Bulletin 161
Adjustable Frequency AC Drive
Allen-Bradley
41
Description
The Bulletin 161 microdrive provides flexible control for a wide vari-
ety of applications using 230 volt, 3 phase induction motors in the
range from 1/4 to 5 HP (.2 – 3.7 kW). The flexibility of the
Bulletin 161 allows it to be operated from 115 or 230 volt single
phase as well as 230 volt three phase input power supply.
Contents
Description
Page
Conformity to Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Catalog Number Explanation. . . . . . . . . . . . . . . . . . . . . . . . . . 42
List Pricing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Conformity to Standards
The Bulletin 161 conforms to the following standards:
Standard
UL Listed
✔
CSA Certified (C-UL)
✔
CE Approved
✔
C-Tick-N223
Pending
Bulletin 161
Adjustable Frequency AC Drive
42
Allen-Bradley
Product Selection
161 Catalog Number Explanation
161S Standard Drive Pricing
➊
“K” version drives with 50 Hz default settings are not available for sale in the USA. The “U” version
drive can be set with 50Hz default settings using Parameter b85.
161D DeviceNet Drive Pricing
161S
–
A
–
A01
–
N
–
P
–
U
Bulletin Number
S = Standard
D = DeviceNet
Voltage Rating
A = 200 - 240V
D = 100 - 120V
Current Rating
Enclosure Type
N = Open (IP20)
Programmer
P = Fixed Keypad
Default Setting
K = 50 Hz default
U = 60 Hz default
Input
Voltage Rating
Drive Rating
Standard
HP
kW
Output
Current Rating
Catalog No.
❋
100-120V
1 Phase
1/4
0.2
1.4
161S-DA01NPU
1/2
0.4
2.6
161S-DA02NPU
1
0.75
4.0
161S-DA04NPU
Drive Rating
Standard
Input
Voltage Rating HP
kW
Output
Current Rating
Catalog No.
❋
200-240V
1 or 3 Phase
1/4
0.2
1.4
161S-AA01NPU
1/2
0.4
2.6
161S-AA02NPU
3/4
0.55
3.0
161S-AA03NPU
1
0.75
4.0
161S-AA04NPU
1.5
1.1
5.0
161S-AA05NPU
2
1.5
7.1
161S-AA07NPU
3
2.2
10.0
161S-AA10NPU
200-240V
3 Phase
5
3.7
15.9
161S-AA15NPU
Drive Rating
DeviceNet
Input
Voltage Rating HP
kW
Output
Current Rating
Catalog No.
❋
200-240V
1 or 3 Phase
1/4
0.2
1.4
161D-AA01NPU
1/2
0.4
2.6
161D-AA02NPU
3/4
0.55
3.0
161D-AA03NPU
1
0.75
4.0
161D-AA04NPU
1.5
1.1
5.0
161D-AA05NPU
2
1.5
7.1
161D-AA07NPU
3
2.2
10.0
161D-AA10NPU
200-240V
3 Phase
5
3.7
15.9
161D-AA15NPU
❋
Prices – Consult Sales Office or price list
Bulletin 161
Adjustable Frequency AC Drive
Allen-Bradley
43
Accessories — Field Installed
1321 Line Reactors
(For Remote User Mounting)
Iron core, 600V, Class H insulation, 115 degree C rise, copper wound,
50/60 Hz., terminal blocks, Minimum 3% impedance, UL, CSA.
Drive Ratings
Line Reactor
Input Volts
HP
kW
Output
Current Rating
Catalog
Number
❋
200-240V AC
3 phase
1/4
0.2
1.4
1321-3R2-A
1/2
0.4
2.6
1321-3R2-D
3/4
0.55
3.0
1321-3R4-A
1
0.75
4.0
1321-3R4-A
1.5
1.1
5.0
1321-3R8-A
2
1.5
7.1
1321-3R8-A
3
2.2
10.0
1321-3R12-A
5
3.7
15.9
1321-3R18-A
❋
Prices – Consult Sales Office or price list
Bulletin 161
Adjustable Frequency AC Drive
44
Allen-Bradley
Notes