background image

Part 1926 Subpart F 

Fire Protection and 

Prevention

for Construction

background image

Fire Protection and 

Fire Prevention Standards

• 1926.150  -  Fire Protection
• 1929.151  -  Fire Prevention
• 1926.152  -  Flammable and Combustible        

Liquids

• 1926.153  -  Liquefied Petroleum Gas (LP-Gas)
• 1926.154  -  Temporary Heating Devices
• 1926.155  -  Definitions applicable for this 

      subpart

background image

Fire Protection and 

Fire Prevention Standards

• 1926.156  -  Fixed Extinguishing Systems 

-        General 

(Removed)

• 1926.157  -  Fixed Extinguishing Systems 

-        Gaseous Agent 

(Removed)

• 1926.158  -  Fire Detection System 

     

(Removed)

• 1926.159  -  Employer Alarm Systems 

     

(Removed)

background image

1926.150

Fire Protection

• General requirements.

The employer shall be responsible for the 
development of a fire protection program 
to be followed throughout all phases of 
the construction and demolition work, and

• He shall provide for the firefighting 

equipment as specified in this subpart. As 
fire hazards occur, there shall be no delay 
in providing the necessary equipment.

background image

1926.150

Fire Protection

• Access to all available firefighting 

equipment shall be maintained at all times.

All firefighting equipment, provided by the 
employer, shall be conspicuously located. 

• All firefighting equipment shall be 

periodically inspected and maintained in 
operating condition. Defective equipment 
shall be immediately replaced.

background image

1926.150

Fire Protection

• As warranted by the project, the 

employer shall provide a trained 
and equipped firefighting 
organization (Fire Brigade) to 
assure adequate protection to life.

background image

1926.150

Fire Protection

• Water supply

.

A temporary or permanent water supply, of 
sufficient volume, duration, and pressure, 
required to properly operate the firefighting 
equipment shall be made available as soon as 
combustible materials accumulate. 

– Where underground water mains are to be 

provided, they shall be installed, completed, 
and made available for use as soon as 
practicable.

background image

1926.150

Fire Protection

• Portable firefighting equipment-
• Fire extinguishers and small hose lines.

 

A fire extinguisher, rated not less than 2A, 
shall be provided for each 3,000 square 
feet of the protected building area, or 
major fraction thereof. Travel distance 
from any point of the protected area to the 
nearest fire extinguisher shall not exceed 
100 feet.

background image

1926.150

Fire Protection

• One 55-gallon open drum of water 

with two fire pails may be 
substituted for a fire extinguisher 
having a 2A rating.

background image

1926.150

Fire Protection

• A 1/2-inch diameter garden-type hose line, not 

to exceed 100 feet in length and equipped with 
a nozzle, may be substituted for a 2A-rated fire 
extinguisher, providing it is capable of 
discharging a minimum of 5 gallons per minute 
with a minimum hose stream range of 30 feet 
horizontally. The garden-type hose lines shall be 
mounted on conventional racks or reels. The 
number and location of hose racks or reels shall 
be such that at least one hose stream can be 
applied to all points in the area.

background image

1926.150

Fire Protection

• One or more fire extinguishers, rated 

not less than 2A, shall be provided on 
each floor. In multistory buildings, at 
least one fire extinguisher shall be 
located adjacent to stairway.

• Extinguishers and water drums, 

subject to freezing, shall be protected 
from freezing

background image

1926.150

Fire Protection

• A fire extinguisher, rated not less 

than 10B, shall be provided within 
50 feet of wherever more than 5 
gallons of flammable or combustible 
liquids or   5 pounds of flammable 

gas are being used on 

the 

jobsite. This 

requirement does 

not 

apply to the integral  fuel 

tanks of motor vehicles.

background image

1926.150

Fire Protection

• Carbon tetrachloride and other toxic 

vaporizing liquid fire extinguishers 
are prohibited.

• Portable fire extinguishers shall be 

inspected periodically and maintained 
in accordance with Maintenance and 
Use of Portable Fire Extinguishers, 
NFPA No. 10A-1970.

background image

1926.150

Fire Protection

• Fire extinguishers which have 

been listed or approved by a 
nationally recognized testing 
laboratory, shall be used to meet 
the requirements of this subpart.

background image

1926.150

Fire Protection

• Fire hose and connections

– One hundred feet, or less, of 1 1/2-

inch hose, with a nozzle capable of 
discharging water at 25 gallons or 
more per minute, may be substituted 
for a fire extinguisher rated not more 
than 2A in the designated area 
provided that the hose line can reach 
all points in the area.

background image

1926.150

Fire Protection

• If fire hose connections are not 

compatible with local firefighting 
equipment, the contractor shall provide 
adapters, or equivalent, to permit 
connections.

• During demolition involving combustible 

materials, charged hose lines, supplied by 
hydrants, water tank trucks with pumps, 
or equivalent, shall be made available.

background image

1926.150

Fire Protection

• Fixed firefighting equipment-

Sprinkler protection.

– If the facility being constructed 

includes

the installation of automatic 

sprinkler protection, the installation 
shall closely follow the construction 
and be placed in service as soon as 
applicable laws permit following 
completion of each story.

background image

1926.150

Fire Protection

• During demolition or alterations, existing 

automatic sprinkler installations shall be retained 
in service as long as reasonable. The operation of 
sprinkler control valves shall be permitted only by 
properly authorized persons. Modification of 
sprinkler systems to permit alterations or 
additional demolition should be expedited so that 
the automatic protection may be returned to 
service as quickly as possible. Sprinkler control 
valves shall be checked daily at close of work to 
ascertain that the protection is in service.

background image

1926.150

Fire Protection

Standpipes.

–  

In all structures in which standpipes are required, or 

where standpipes exist in structures being altered, 
they shall be brought up as soon as applicable laws 
permit, and shall be maintained as construction 
progresses in such a manner that they are always 
ready for fire protection use. The standpipes shall be 
provided with Siamese fire department connections 
on the outside of the structure, at the street level, 
which shall be conspicuously marked. There shall be 
at least one standard hose outlet at each floor.

background image

1926.150

Fire Protection

Fire alarm devices.

An alarm system, e.g., telephone system, 
siren, etc., shall be established by the 
employer whereby employees on the site 
and the local fire department can be 
alerted for an emergency.

The alarm code and reporting instructions 
shall be conspicuously posted at phones 
and at employee entrances.

background image

1926.150

Fire Protection

Fire cutoffs.

Fire walls and exit stairways, required for 
the completed buildings, shall be given 
construction priority. Fire doors, with 
automatic closing devices, shall be hung 
on openings as soon as practicable.

Fire cutoffs shall be retained in buildings 
undergoing alterations or demolition until 
operations necessitate their removal.

background image

1926.151

Fire Prevention

Ignition hazards.

– Electrical wiring and equipment for 

light, heat, or power purposes shall 
be installed in compliance with the 
requirements of Subpart K of this 
part.

background image

1926.151

Fire Prevention

Ignition hazards.

– Internal combustion engine powered 

equipment shall be so located that the 
exhausts are well away from combustible 
materials. When the exhausts are piped 
to outside the building under 
construction, a clearance of at least 6 
inches shall be maintained between such 
piping and combustible material.

background image

1926.151

Fire Prevention

Ignition hazards.

– Smoking shall be prohibited at or in the 

vicinity of operations which constitute a fire 
hazard, and shall be conspicuously posted: 
"No Smoking or Open Flame.”

– (Portable battery powered lighting 

equipment, used in connection with the 
storage, handling, or use of flammable gases 
or liquids, shall be of the type approved for 
the hazardous locations.

background image

1926.151

Fire Prevention

Ignition hazards.

– The nozzle of air, inert gas, and steam 

lines or hoses, when used in the cleaning 
or ventilation of tanks and vessels that 
contain hazardous concentrations of 
flammable gases or vapors, shall be 
bonded to the tank or vessel shell. 
Bonding devices shall not be attached or 
detached in hazardous concentrations of 
flammable gases or vapors.

background image

1926.151

Fire Prevention

Temporary buildings.

– No temporary building shall be erected 

where it will adversely affect any means of 
exit.

– Temporary buildings, when located within 

another building or structure, shall be of 
either noncombustible construction or of 
combustible construction having a fire 
resistance of not less than 1 hour.

background image

1926.151

Fire Prevention

– Temporary buildings, located other than 

inside another building and not used for the 
storage, handling, or use of flammable or 
combustible liquids, flammable gases, 
explosives, or blasting agents, or similar 
hazardous occupancies, shall be located at a 
distance of not less than 10 feet from 
another building or structure. Groups of 
temporary buildings, not exceeding 2,000 
square feet in aggregate, shall, for the 
purposes of this part, be considered a single 
temporary building.

background image

1926.151

Fire Prevention

Open yard storage.

– Combustible materials shall be piled with due 

regard to the stability of piles and in no case 
higher than 20 feet.

– Driveways between and around combustible 

storage piles shall be at least 15 feet wide and 
maintained free from accumulation of rubbish, 
equipment, or other articles or materials. 
Driveways shall be so spaced that a maximum grid 
system unit of 50 feet by 150 feet is produced.

background image

1926.151

Fire Prevention

Open yard storage.

– The entire storage site shall be kept free 

from accumulation of unnecessary 
combustible materials. Weeds and grass 
shall be kept down and a regular procedure 
provided for the periodic cleanup of the 
entire area.

– When there is a danger of an underground 

fire, that land shall not be used for 
combustible or flammable storage.

background image

1926.151

Fire Prevention

Open yard storage.

– Method of piling shall be solid wherever possible and 

in orderly and regular piles. No combustible material 
shall be stored outdoors within 10 feet of a building 
or structure.

– Portable fire extinguishing equipment, suitable for the 

fire hazard involved, shall be provided at convenient, 
conspicuously accessible locations in the yard area. 
Portable fire extinguishers, rated not less than 2A, 
shall be placed so that maximum travel distance to 
the nearest unit shall not exceed 100 feet.

background image

1926.151

Fire Prevention

Indoor storage.

– Storage shall not obstruct, or adversely 

affect, means of exit.

 

– All materials shall be stored, handled, and 

piled with due regard to their fire 
characteristics.

– Noncompatible materials, which may create 

a fire hazard, shall be segregated by a 
barrier having a fire resistance of at least 1 
hour.

background image

1926.151

Fire Prevention

Indoor storage.

– Material shall be piled to minimize the 

spread of fire internally and to permit 
convenient access for firefighting. 

– Stable piling shall be maintained at all 

times. 

– Aisle space shall be maintained to safely 

accommodate the widest vehicle that may be 
used within the building for firefighting 
purposes.

background image

1926.151

Fire Prevention

Indoor storage

– Clearance of at least 36 inches shall 

be maintained between the top level of 
the stored material and the sprinkler 
deflectors.

– Clearance shall be maintained around 

lights and heating units to prevent 
ignition of combustible materials.

background image

1926.151

Fire Prevention

Indoor storage

– A clearance of 24 inches shall be 

maintained around the path of travel 
of fire doors unless a barricade is 
provided, in which case no clearance 
is needed. Material shall not be 
stored within 36 inches of a fire door 
opening.

background image

1926.152

Flammable And Combustible 

Liquids

General Requirements

Indoor Storage of 
flammable and 
combustible liquids

Storage Outside 
Buildings

Fire Control for 
Flammable or 
Combustible Liquid 
Storage

• Dispensing Liquids

Handling liquids at 
point of final use

• Service and refueling 

areas

Tank Storage

• Piping, Valves and 

Fittings

Marine Service 
Stations

background image

1926.152

Flammable And Combustible 

Liquids

• What quantities of flammable and 

combustible liquid in excess of 
____ gallons shall be stored in an 
acceptable or approved cabinet?

• Give appropriate paragraph.

background image

1926.152

Flammable And Combustible 

Liquids

• What quantities of flammable and 

combustible liquid in excess of 

25

 gallons shall be stored in an 

acceptable or approved cabinet?

• Give appropriate paragraph. 

(b)

(2)

background image

1926.152

Flammable And Combustible 

Liquids

• What is the capacity of the diked 

area around fuel storage tanks?

• Give the appropriate paragraph

 

background image

1926.152

Flammable And Combustible 

Liquids

• What is the capacity of the diked area 

around fuel storage tanks? 

– For a tank or group of tanks with fixed roofs 

containing crude petroleum with boilover 
characteristics, the volumetric capacity of the 
diked area shall be not less than the capacity of 
the largest tank served by the enclosure, 
assuming a full tank. The capacity of the diked 
enclosure shall be calculated by deducting the 
volume below the height of the dike of all tanks 
within the enclosure.

 (i)(2)(vii)(C)(2)

 

background image

1926.153

 Liquefied Petroleum Gas (LP-

Gas)

• Approval of equipment 

and systems

• Welding

 on LP-Gas 

containers

• Container valves and 

container accessories

Safety Devices

• Dispensing

Requirement for 
appliances

• Equipment installed 

outside buildings

Containers used inside 
buildings

• Multiple container systems

Storage outside buildings

• Using other than DOT 

containers

Damage from vehicles

background image

1926.153

 

Liquefied Petroleum Gas (LP-

Gas)

• ____________________________shall 

be provided with one or more 
approved safety relief valves or 
devices. 

• Give appropriate paragraph.

background image

1926.153

 

Liquefied Petroleum Gas (LP-

Gas)

Every container and every 
vaporizer

 shall be provided with 

one or more approved safety relief 
valves or devices. 

• Give appropriate paragraph  

(d)(1)

background image

1926.154

Temporary Heating Devices

Ventilation.

– Fresh air shall be supplied in sufficient 

quantities to maintain the health and safety of 
workmen. Where natural means of fresh air 
supply is inadequate, mechanical ventilation 
shall be provided.  

– When heaters are used in confined spaces, 

special care shall be taken to provide sufficient 
ventilation in order to ensure proper 
combustion, maintain the health and safety of 
workmen, and limit temperature rise in the area

.

background image

1926.154

Temporary Heating Devices

Clearance and mounting.

•  

TABLE F-4 in 29 CFR 1926

background image

1926.154

Temporary Heating Devices

• Heaters not suitable for use on wood 

floors shall not be set directly upon 
them or other combustible materials. 
When such heaters are used, they 
shall rest on suitable heat insulating 
material or at least 1-inch concrete, 
or equivalent. The insulating material 
shall extend beyond the heater 2 feet 
or more in all directions.

background image

1926.154

Temporary Heating Devices

• Heaters used in the vicinity of 

combustible tarpaulins, canvas, or 
similar coverings shall be located at 
least 10 feet from the coverings. 
The coverings shall be securely 
fastened to prevent ignition or 
upsetting of the heater due to wind 
action on the covering or other 
material.

background image

1926.154

Temporary Heating Devices

Stability. 

• Heaters, when in use, shall be set 

horizontally level, unless 
otherwise permitted by the 
manufacturer's markings.

background image

1926.154

Temporary Heating Devices

Solid fuel salamanders.

• Solid fuel salamanders are 

prohibited in buildings and on 
scaffolds.

background image

1926.154

Temporary Heating Devices

Oil-fired heaters.

– Flammable liquid-fired heaters shall 

be equipped with a primary safety 
control to stop the flow of fuel in the 
event of flame failure. Barometric or 
gravity oil feed shall not be 
considered a primary safety control.

background image

1926.154

Temporary Heating Devices

• Heaters designed for barometric or 

gravity oil feed shall be used only 
with the integral tanks.

• Heaters specifically designed and 

approved for use with separate 
supply tanks may be directly 
connected for gravity feed, or an 
automatic pump, from a supply tank.

background image

1926.155

Definitions

• "Approved", for the purpose of this 

subpart, means equipment that has 
been listed or approved by a nationally 
recognized testing laboratory such as 
Factory Mutual Engineering Corp., or 
Underwriters' Laboratories, Inc., or 
Federal agencies such as Bureau of 
Mines, or U.S. Coast Guard, which 
issue approvals for such equipment.

background image

1926.155

Definitions

• "Closed container" means a container 

so sealed by means of a lid or other 
device that neither liquid nor vapor will 
escape from it at ordinary 
temperatures.

"Combustible liquids" mean any liquid 
having a flash point at or above 140 
deg. F. (60 deg. C.), and below 200 deg. 
F. (93.4 deg. C.)

background image

1926.155

Definitions

• "Combustion" means any chemical 

process that involves oxidation 
sufficient to produce light or heat.

"Fire brigade" means an organized 
group of employees that are 
knowledgeable, trained, and skilled in 
the safe evacuation of employees 
during emergency situations and in 
assisting in fire fighting operations

.

background image

1926.155

Definitions

• "Fire resistance" means so resistant to fire 

that, for specified time and under 
conditions of a standard heat intensity, it 
will not fail structurally and will not permit 
the side away from the fire to become 
hotter than a specified temperature. For 
purposes of this part, fire resistance shall 
be determined by the Standard Methods of 
Fire Tests of Building Construction and 
Materials, NFPA 251-1969.

background image

1926.155

Definitions

• "Flammable" means capable of being 

easily ignited, burning intensely, or 
having a rapid rate of flame spread.

"Flammable liquids" means any liquid 
having a flash point below 140 deg. F. 
and having a vapor pressure not 
exceeding 40 pounds per square inch 
(absolute) at 100 deg F.

background image

1926.155

Definitions

• "Flash point" of the liquid means 

the temperature at which it gives 
off vapor sufficient to form an 
ignitable mixture with the air near 
the surface of the liquid or within 
the vessel used as determined by 
appropriate test procedure 

background image

1926.155

Definitions

• "Liquefied petroleum gases," "LPG" 

and "LP Gas" mean and include 
any material which is composed 
predominantly of any of the 
following hydrocarbons, or 
mixtures of them, such as propane, 
propylene, butane (normal butane 
or iso-butane), and butylenes

background image

1926.155

Definitions

• "Portable tank" means a closed container 

having a liquid capacity more than 60 U.S. 
gallons, and not intended for fixed 
installation.

"Safety can" means an approved closed 
container, of not more than 5 gallons capacity, 
having a flash-arresting screen, spring-closing 
lid and spout cover and so designed that it 
will safely relieve internal pressure when 
subjected to fire exposure.

background image

1926.155

Definitions

• "Vapor pressure" means the 

pressure, measured in pounds per 
square inch (absolute), exerted by 
a volatile liquid as determined by 
the "Standard Method of Test for 
Vapor Pressure of Petroleum 
Products (Reid Method)." (ASTM 
D-323-58).

background image

Most Frequently Cited 

Fire Hazard Violations 

Transporting or handling 
flammable liquids in non-approved 
containers [1926.152(a)(1)]. 

background image

Most Frequently Cited 

Fire Hazard Violations 

Failure to have a class 2-A rated fire 
extinguisher within a 100 feet (30.4 m) 
of an area where class A fire hazards 
exist within a building [1926.150(c)(1)
(I)]. Another frequent violation related 
to this one is not having at least one 
class 2-A rated fire extinguisher on each 
floor of a multistory building located 
near the stairway [1926.150(c)(1)(iv)]. 

background image

Most Frequently Cited 

Fire Hazard Violations 

Failure of the employer to develop and 
implement a fire protection program for 
all phases of work involving employees 
on the job site [1926.150(a)(1)]. 

Failure to inspect and maintain portable 
fire extinguishers to keep them in 
serviceable condition [1926.150(c)(1)
(iii)]. 

background image

Most Frequently Cited 

Fire Hazard Violations 

Lack of posting of "no smoking" 
signs where refueling operations 
are conducted [1926.152(g)(9)], 
and where operations which 
constitute a fire hazard, which 
commonly will include flammable 
liquids and flammable gases 
[1926.151(a)(3)].

background image

Review

What is a fire brigade?

Who is responsible for the development of 
a fire protection program to be followed 
throughout all phases of the construction 
and demolition work?

During ___________ involving combustible 
materials, charged hose lines, supplied by 
hydrants, water tank trucks with pumps, 
or equivalent, shall be made available.

background image

Review

A fire extinguisher was be rated as 
what “A” as a minimum?

What types of fire extinguishers are 
prohibited? 

A clearance of at least ____ inches 
shall be maintained between the 
top level of the stored material and 
the sprinkler deflectors.


Document Outline