Pressure Transmitter PC-28
[
[
[
Any range from 4 kPa
up to 40 MPa
4 ÷ 20 mA two-wire
transmission
Exi I/IICT6 spark proof
a
Electrical
connections
Pipe stubs
PD type
IP 54 rated Ingress
Protection; DIN 43650
Electrical Connector with
PG-11 Packing Gland
M type
M20×1.5 stub, internal diameter
4
∅
P type
M20×1.5 stub, internal diameter
12
∅
CM30×2 type
25 kPa
4 MPa
M30×2 pipe stub
with flush diaphragm
≤ <
p
CM20×1.5 type
M20×1.5 pipe stub with
flush diaphragm;
4 MPa
p
≥
Note: (CM30×2 spoz.) – hygi-
enic version – sealed-off thread;
optionally supplied with a weld-
in mounting ring and a seal.
RM type
16 kPa
4 MPa
≤ <
p
Radiator with M type pipe stub
Measurement of media up to
150°C with no impulse line
PZ type
IP 65 rated Ingress
Protection; Terminal box
with PG-11 Packing Gland
PK type
IP 67 rated Ingress
Protection; Electrical cable
connection, atmospheric
connection via a capillary
located in the cable, cable
length 3 m
(unless the order
states otherwise)
2 15
2 15
∅
12
Red (+)
Black (–)
max 148
Application
The PC-28 pressure transmitter is designed to meas-
ure pressure, underpressure and absolute pressure of
gases, vapours and liquids.
Design
The active sensing element is a piezoresistive silicon
sensor, separated from the medium by a diaphragm
and a selected type of manometric liquid.
A silicone-protected electrical circuit is situated in the
case (Ingress Protection rating from IP 54 to IP 67
depending on the type of electrical connection used).
Calibration
Potentiometers can be used to shift the zero position
and the range by up to ±10%, without altering the set-
tings.
Assembly
In view of its small mass, the transmitter can be
mounted directly on the installation. When measuring
the pressure of vapour or other hot media, a siphon
tube or impulse line should be used. We recommend
a manometric valve before the transmitter for easier
installation and for resetting or even replacement of
the unit without shutting down your process.
In the case of orders for transmitters with threads
other than M20×1.5 (e.g. G ½"), we perform the ap-
propriate reduction.
For measurement of levels and pressures requiring
special process connectors (e.g. in the food and
chemical industries) the transmitter is equipped with
an Aplisens diaphragm seal.
Assembly equipment and a full range of diaphragm
seals are described in detail later in this catalogue.
Measurements in hazardous areas
The PC-28 transmitter is spark-proof and has
Exi
a
I/IICT6 factor (under KDB decision no. 98.457W).
The installation of the transmitter in a hazard zone
requires the use of a spark-proof power supply and
measurement circuit certified as fulfilling the following
conditions: I
max
93 mA, U
max
28 V.
We recommend the use of the Aplisens ZS-30Ex
spark-proof power supplier/separator.
∅
6...9 Cable
∅
5...10 Cable
20
5
∅
4
∅
6
M20×1.5
SW27
∅
27
124
25
5
8
Version II/2002
APLISENS Sp. z o.o., ul. Morelowa 7
, tel. +4822 8140 777
fax +4822 8140 778, www.aplisens.com.pl, e-mail: aplisens@
.pl
, 03-192 Warszawa
aplisens.com
Technical data
Any measurement range 4 kPa ÷ 40 MPa (positive gauge pressure, vacuum pressure);
40 kPa ÷ 8 MPa (absolute pressure)
Measurement Range
10 kPa
40 kPa
0...100 kPa ÷ 40 MPa
Overpressure Limit
(repeated, without hysteresis)
50 kPa
100 kPa
2 × range
max 70 MPa
Damaging Overpressure
100 kPa
360 kPa
8 × range or 100 MPa
Accuracy
0.4%
0.25%
Thermal error of zero
Typically 0.3% / 10°C
max 0.4% / 10°C
Typically 0.2% / 10°C
max 0.3% / 10°C
Thermal error of span
Typically 0.3% / 10°C
max 0.4% / 10°C
Typically 0.2% / 10°C
max 0.3% / 10°C
Hysteresis, repeatability
0.05%
Thermal compensation range
0 ÷ 70°C
Ambient temperature limits
-25 ÷ 80°C
Process temperature limits
-25 ÷ 95°C – direct measurement
over 95°C – measurement using a diaphragm seal, radiator or impulse line
ATTENTION: never allow the liquid to freeze in the impulse line or your installation close to the transmitter.
We recommend the standard ranges: -100, -40, -10, 10, 40, 100, 250, 600 kPa; 1, 1.6, 2.5, 6, 16, 25, 40 MPa
Absolute pressure: 40, 100, 250, 600 kPa; 1, 1.6, 2.5, 6 MPa
Vacuum gauges: -100 ÷ 100, -100 ÷ 250, -100 ÷ 600 kPa
Output signal
4 ÷ 20 mA, two-wire transmission
Power supply
12 ÷ 30 V DC (Ex max 28 V)
Error due to power supply variation 0.005% / V
Construction material
of the pipe stub and diaphragm
00H17N14M2 (316Lss)
Construction material of the case 0H18N9 (304ss)
Load resistance R [
U
V] 12 V
0.02 A
sup
Ω
]
[
≤
−
Extra features, certificates:
◊
Ex – spark-proof
◊
D – version with hydraulic gland for high-pressure hydraulic systems
◊
H – hydrophore version (high overload capacity, integrated circuit offering excess voltage protection)
◊
Hastelloy – CM 30×2 stub pipe and isolating diaphragm made of Hastelloy C 276 alloy
◊
For other features phone us on: +4822 8140 777
Ordering procedure
PC-28 /___/__÷__/___/___
Extra features:
Ex, D, H, Hastelloy, others (description)
End of measurement range – in relation to 20 mA output
Note: for measurement of absolute pressure, state ABS
Type of electrical connection: PD, PZ, PK
Type of pipe stub or type of diaphragm seal
according to the diaphragm seal data sheets
Example
Note
PC-28 / 0 1 bar
: PC-28 Transmitter / Ex feature / range 0 ÷ 100 kPa ABS inverted output (20 ÷ 4 mA) / electrical cable
connection / M20×1.5 pipe stub with internal diameter 4
: The standard transmitter comes with type M pipe stub and PD type connector. This can be ordered using a simpler
format, e.g.
∅
PC-28 / Ex / 100 ÷ 0 kPa ABS / PK / M
÷
Start of measurement range – in relation to 4 mA output
PD connector
1
2
3
4 ÷ 20 mA
e.g. Aplisens
ZL-24
+
–
Electrical diagram
Power
supply