1
Emergency switches and safety gate
control switches in accordance with
VDE 0113 part 1, 11/98 and
EN 60204-1, 12/97
Features
l Dual-channel operation which
detects shorts across the input
contacts
l Supply voltage:
24 V AC/DC, 48 ... 240 V AC/DC
l Supply voltage 48 ... 240 V AC/DC:
Galvanic isolation from the
input circuit
l Automatic or monitored manual
reset can be selected
l Plug-in connection terminals
(Either screw terminals or
cage clamp terminals)
Approvals
Emergency Stop Relays, Safety Gate Monitors
Category 4, EN 954-1
PNOZ X2P
Technical Details
PNOZ X2P
Electrical Data
Supply voltage
24 V AC/DC
48 ... 240 V AC/DC
Tolerance
85 ... 110 %
Power consumption 24 V AC/DC: Approx. 3 VA/2 W
48 ... 240 V AC/DC: Approx. 2 VA/1 W
Voltage and current at the input,
24 V DC/25 mA
reset and feedback circuits
Switching capability in accordance with
EN 60947-4-1, 01/00
AC1:
240 V/6 A/1500 VA
DC1:
24 V/4 A/100 W
EN 60947-5-1, 08/00
AC15:
230 V/5 A; DC13: 24 V/4A
(DC13: 6 cycles/min)
Output contacts
2 safety contacts (N/O)
Contact fuse protection according to
6 A quick or 4 A slow
EN 60947-5-1, 08/00
Times
Switch-on delay Automatic reset:
24 V AC/DC: max. 150 ms
48 ... 240 V AC/DC: max. 250 ms
Manual reset: max. 100 ms
Delay on de-energisation
Single-channel input circuit:
24 V AC/DC: max. 120 ms
48 ... 240 V AC/DC: max. 600 ms
Dual-channel input circuit: max. 30 ms
Recovery time
Approx. 1 s
Simultaneity channels 1/2
¥
Max. supply interruption before
Approx. 10 ms
de-energisation
48 ... 240 V AC/DC (Single-channel
input circuit): max. 600 ms
Mechanical Data: with cage clamp terminals
Terminal blocks per connection
2
Maximum cross section of ext. conductors
Flexible, without crimp connectors: 0.2 ... 1.5 mm
2
stripping length 8 mm
Dimensions (H x W x D)
101 x 22.5 x 121 mm
Weight
200 g
Mechanical Data: with screw terminals
Maximum cross section of ext. conductors
Single-core
Flexible, without crimp connectors: 0.2 ... 2.5 mm
2
Flexible with crimp connectors: 0.25 ... 2.5 mm
2
Multi-core
Flexible, with crimp connectors but
(2 conductors with same cross-section)
without plastic sheath: 0.25 ... 1 mm
2
Flexible, with TWIN-crimp connectors
and plastic sheath: 0.5 ... 1.5 mm
2
Torque setting for screw terminals
0.5 ... 0.6 Nm
Dimensions (H x W x D)
94 x 22.5 x 121 mm
Weight
200 g
NSG-D-2-143-10/03
PNOZ X2P
●
●
●
Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone +49 (7 11) 34 09-0, Telefax +49 (7 11) 34 09-1 33, E-Mail: pilz.gmbh@pilz.de
Emergency Stop Relays, Safety Gate Monitors
Category 4, EN 954-1
PNOZ X2P
NSG-D-2-143-10/03
Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone +49 (7 11) 34 09-0, Telefax +49 (7 11) 34 09-1 33, E-Mail: pilz.gmbh@pilz.de
Internal wiring diagram
- UB = 24 V AC/DC
A1 (L+)
A2 (L-)
S22
S12
S21
S11
S33
13
14
K1
K2
23
24
S34
Start
Unit
Start
Unit
Auto
Start
Y36 Y37
Reset
circuit
Input
circuit
Safety
contacts
- UB = 48 ... 240 V AC/DC
A1 (L+) A2 (L-)
S22
S12
S21
S11
S33
13
14
K1
K2
23
24
S34
Start
Unit
Start
Unit
Auto
Start
Y36 Y37
AC/DC
DC
Reset
circuit
Input
circuit
Safety
contacts
Description
l 22.5 mm P-99 housing, DIN-Rail
mounting
l Positive-guided relay outputs:
2 safety contacts (N/O)
l Connections for
– E-STOP buttons or
safety gate limit switches
– reset button
l Detects shorts across the input
contacts
l LEDs for channel 1, channel 2 and
power supply
l Increase in the number of
safety contacts available by
connecting expander modules
Operating modes
l Single-channel operation
l Dual-channel operation
l Automatic reset
l Monitored manual reset
External wiring
l Example 1
Single-channel E-STOP wiring with
monitored manual reset.
S11
S12
S34
S22
S33
S21
U
B
(L+)
A1
S1
S3
l Example 2
Dual-channel E-STOP wiring with
monitored manual reset
S11
S12
S34
S22
S33
S21
S1
S3
S34
S33
S11
S22
S12
S21
S1
S1
S2
Y37
Y36
l Example 3
Dual-channel safety gate control with
automatic reset.
l Example 4
Dual-channel safety gate control with
monitored manual reset.
S34
S33
S11
S22
S12
S21
S1
S3
S1
S2
Gate open
Switch operated
Gate closed
S1/S2: E-STOP or safety gate switch
S3:
Reset button
– Key
1
Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone +49 (7 11) 34 09-0, Telefax +49 (7 11) 34 09-1 33, E-Mail: pilz.gmbh@pilz.de
K4
S33
S34
K5
K4
K5
13
14
L1
N
l Increase in the number of
contacts
The number of output contacts can
be increased by using expander
modules or relays/contactors with
positive-guided contacts.
NSG-D-2-143-10/03
Emergency Stop Relays, Safety Gate Monitors
Category 4, EN 954-1
PNOZ X2P
Emergency Stop Relays, Safety Gate Monitors
Category 4, EN 954-1
PNOZ X2P
NSG-D-2-143-10/03
General Technical Data
Unless stated otherwise in the technical details for the specific unit
Electrical Data
Frequency Range AC
50 ... 60 Hz
Residual Ripple DC
160 %
Contact Material
AgSnO
2
Continuous Duty
100 %
Environmental Data
EMC
EN 50081-1, 08/93, EN 61000-6-2, 03/00
Vibration in accordance with
Frequency: 10 ... 55 Hz,
EN 60068-2-6, 01/00
Amplitude: 0.35 mm
Climatic Suitability
DIN IEC 60068-2-3, 12/86
Airgap Creepage
DIN VDE 0110 part 1, 04/97
Ambient Temperature
-10 ... +55 °C
Storage Temperature
-40 ... +85 °C
Mechanical Data
Torque Setting on Connection Terminals
0.6 Nm (screws)
Mounting Position
Any
Housing Material
Thermoplast Noryl SE 100
Protection
Mounting: IP 54
Housing: IP 40
Terminal Range: IP 20
The units were tested in accordance with the relevant standards current at
the time of development.
Order References
Type
U
B
Order No.
PNOZ X2P with cage clamp terminals
24 AC/DC
787 303
PNOZ X2P with screw terminals
24 AC/DC
777 303
PNOZ X2P with cage clamp terminals
48 ... 240 V AC/DC
787 307
PNOZ X2P with screw terminals
48 ... 240 V AC/DC
777 307
Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone +49 (7 11) 34 09-0, Telefax +49 (7 11) 34 09-1 33, E-Mail: pilz.gmbh@pilz.de