Economizer function
File: Economizer.doc
Last edition: 2003-03-04
Author: Mikael Krantz
History: 96-02-13/MK First released version.
96-10-03/MK Updated to Menta 1.20
97-08-28/MK Updated to Menta 3.0
98-12-29/MK New file name
2003-03-04/MK Updated to Menta 4.0
Description
Economizer function is activated during cooling mode if the "Exhaust air temperature" goes below the "Outdoor temperature" with more than "Economizer limit". The economizer function is deactivated then the "Outdoor temperature" goes below the "Return air temperature". Economizer function is blocked if the "Return air temperature" sensor is not connected. It is not possible to set a lower value on "Economizer limit" than 1 °C.
Inputs
(Real) Outdoor temperature, °C.
(Real) Exhaust air temperature, °C.
(Binary) Fan operation flag
(Binary) Heating case flag
Outputs
(Binary) Economizer flag
Parameters
(Real) EconomizerLimit 2 °C
Public signals
(Real) EconomizerLimit
(Binary) EconomizerFlag