Running control
File: Running Flag.doc
Last edition: 2003-03-04
Author: Mikael Krantz
History: 96-02-13/MK First released version.
96-10-02/MK Updated to Menta 1.20
97-08-29/MK Updated to Menta 3.0
98-12-29/MK New file name
2003-03-04/MK Updated to Menta 4.0
Description
The "Normal run flag" is set to true when the time schedule or the "Extended day" flag is true and the "External stop" flag is false.
Inputs
(Binary) Extended day
(Binary) External stop
Outputs
(Binary) Normal run
Parameters
(TSCH) RunningTime 06:00 17:00 MTWTF__
Public signals
(TSCH) RunningTime
(Binary) NormalRun