vmcpu1"0 upgrade inst


INSTRUCTIONS FOR UPGRADING

IC200CPU001 WITH VERSION 2.20 FIRMWARE

PER UPGRADE KIT 44A747796-G05

The VersaMax PLC CPU has operating firmware stored in FLASH memory. The firmware upgrade and WinLoader update utility for these boards are provided on the upgrade disk. The WinLoader update utility is a Windows-based program that controls downloading the new firmware from the upgrade disk to the FLASH memory on the PLC CPU. WinLoader requires Windows 95, Windows NT, Windows 98, Windows 2000 or Windows XP. The hardware required to run these operating systems should suffice to also run WinLoader.

Please refer to the following table to determine which CPU001 hardware revisions can be upgraded to this version, 2.20, of the CPU firmware.

Compatability Table

IC200CPU001-AA

IC200CPU001-AA models are not field upgradable to this version of the firmware. Upgrading an IC200CPU001-AA to this version of the firmware will render port 2 on the CPU inoperable. In addition, the programmer will be unable to store/load folder data to/from the CPU via port 1. However, the old version of the firmware may be reinstalled so the CPU will function properly. If features in this version of the firmware are needed, then new CPU001 hardware must be purchased.

IC200CPU001-BA, BB, BC, or BD

IC200CPU001-BA, BB, BC, or BD models are not field upgradable to this version of the firmware. Upgrading an IC200CPU001-BA, BB, BC, or BD to this version of the firmware firmware will render port 2 on the CPU inoperable. In addition, the programmer will be unable to store/load folder data to/from the CPU via port 1. However, the old version of the firmware may be reinstalled so the CPU will function properly. If features in this version of the firmware are needed, then new CPU001 hardware must be purchased.

IC200CPU001-CC, CD, CE, DE

Any IC200CPU001-CC, CD, CE or DE may be upgraded to this version of the firmware.

NOTE: The instructions provided outline a specific sequence of procedure that MUST be followed. If the procedure for some reason is not followed, please contact the GE FANUC hotline for help in setting up the PLC.

TO INSTALL THE NEW FIRMWARE, PERFORM THE FOLLOWING STEPS:

(Note: This firmware may be upgraded via serial download from an IBM compatible computer to CPU005 serial port 1 (RS-232). Firmware updates through serial port 2 (RS485) are not supported.)

  1. Save or backup any programs or data resident in the module before performing the update function.

  1. Place the PLC in STOP/NOIO Mode.

  1. Clear the configuration in your PLC. This will setup the serial ports for 19200 baud, 8 bits per char, odd parity, and 1 stop bit for serial communications. If they are already set to these default values then this step may not be necessary.

  1. Clear any faults in the PLC.

  1. Close any applications (including PLC programming applications) that may be using the COM ports of your PC.

  1. Connect the serial port of your computer (master) to port 1 on the PLC to be updated (slave). (See section at the end of this document for suggested cables to use.)

  1. Insert the upgrade floppy disk into your A: or B: drive.

  1. Invoke the WinLoader software package by double clicking on its icon located in drive A: or B: (depending on the drive designation for the 3.5" floppy disk) in Windows Explorer or simply execute it by going to the start menu and selecting RUN. In the RUN window type A (or B):winloader.exe

  1. Begin upgrade of firmware by single clicking the "Update" button. While update is in progress, the OK and RUN LEDs on the PLC will blink in unison, and the status bar on WinLoader will show percentage complete.

  1. Upon completion of the update a window will "pop up" indicating the status of the update. If the update was successful, power cycle the PLC and indicate that another device is NOT to be updated by clicking the "No" button. If not successful, see the "Common Causes of Failure" section below to determine how to correct the problem.

  1. Place upgrade label on unit, not covering any vents or other labels.

COMMMON CAUSES OF FAILURE

  1. PLC is not in STOP/NOIO mode. SIDE EFFECTS: A WinLoader dialog box will appear and tell the user that there is a “CPU STATE MISMATCH”. REMEDY: WinLoader will ask user if it's OK for WinLoader to clear fault tables and place PLC in STOP/NOIO mode. Click yes and proceed.

  1. Connected to wrong serial port. SIDE EFFECTS: A WinLoader dialog box will appear and tell the user that the “FIRMWARE UPDATE FAILED” and will list several possible reasons why the firmware update failed. REMEDY: Make sure serial cable is connected to serial port 1 on the PLC and the correct COM port of the PC (should match COM port indicated on WinLoader screen), power-cycle, and start process again.

  1. COM port on computer already in use. SIDE EFFECTS: A WinLoader dialog box will appear and tell the user that "FIRMWARE UPDATE FAILED" and that the selected COM port is either busy or does not exist. REMEDY: Close any other applications (including PLC programming applications), insure serial cable is connected to correct COM port on the PC and start process again.

RESTARTING AN INTERRUPTED FIRMWARE UPGRADE

A. Power cycle the PLC.

B. If a partial or erroneous download was performed, the module will power up with the OK and RUN LEDs on the power supply flashing in unison. If the OK and RUN LEDs are flashing in unison, then begin again at step 6 of the installation instructions, otherwise begin again at step 1.

CABLES REQUIRED FOR UPGRADING

The cable to attach to port 1 of the PLC is sold by GE Fanuc as catalog number IC200CBL001.

If you do not have this cable, any cable that meets the wiring diagram as shown in the CPU001 datasheet (GFK-1536) can be used to connect your PC to port 1 of the PLC. Cables that meet this wiring diagram are often sold in office supply or electronics stores as "serial mouse extension cable" or "CGA/EGA monitor extension cable".

Another option is to use the cable that comes with the RS-232/RS-422 converter kit (IC690ACC901) in conjunction with a "male-to-male" DB9 gender changer. Such an adapter can be purchased off-the-shelf from many office supply or electronics stores, and is also available from AMP under AMP P/N: 621828-1.

REV DESCRIPTION DATE APPROVED

REVISIONS

DRAWN

CHECKED

ENGRG

ISSUED

DIMENSIONS ARE IN INCHES/MM

TOLERANCES ON:

2 PL DECIMALS

3 PL DECIMALS

ANGLES=

FRACTIONS=

UNLESS OTHERWISE NOTED SIGNATURES DATES

SIZE

A

SCALE

GEGS NO

DWG NO

44A751476

SHEET OF

TITLE

INSTALLATION INSTRUCTIONS

THIRD ANGLE PROJECTION

621

VERSION LEVEL

DIST

1 2



Wyszukiwarka

Podobne podstrony:
vmcpu?5"0 upgrade inst
vmcpu2"0 upgrade inst
vmcpu5"0 upgrade inst

więcej podobnych podstron