Politechnika Warszawska Instytut Maszyn Elektrycznych |
---|
Laboratorium Maszyn Elektrycznych |
Nazwa ćwiczenia: Badanie generatora synchronicznego cd. |
Rok akademicki: 2012/2013 |
Dzień: wtorek 15.01.2013 |
Wartości znamionowe prądnicy:
P = 10 [kW]
$$n_{N} = 1500\ \lbrack\frac{\text{obr}}{\min}\rbrack$$
UN = 380 [V]
IN = 15, 2 [A]
cosφN = 0, 8
f = 50 [Hz]
Usr |
Isr |
P |
S |
Uf |
If |
n |
cosφ |
---|---|---|---|---|---|---|---|
[V] | [A] | [W] | [W] | [V] | [A] | [Obr/min] | [1] |
408,228 | 4,786 | 1404,777 | 3383,817 | 55,665 | 1,960 | 1499,899 | 0,422 |
412,621 | 5,908 | 1814,090 | 4222,554 | 55,634 | 1,959 | 1499,868 | 0,438 |
418,950 | 7,514 | 2369,787 | 5452,626 | 55,618 | 1,957 | 1500,081 | 0,447 |
426,428 | 9,759 | 3299,360 | 7207,606 | 55,570 | 1,955 | 1500,429 | 0,460 |
436,599 | 12,782 | 4440,657 | 9666,039 | 55,569 | 1,954 | 1500,411 | 0,465 |
442,489 | 14,556 | 5065,506 | 11155,637 | 55,518 | 1,952 | 1500,198 | 0,458 |
Tabela . Wyniki charakterystyki zewnętrznej dla współczynnika mocy pojemnościowego
Usr |
Isr |
P |
S |
Uf |
If |
n |
cosφ |
---|---|---|---|---|---|---|---|
[V] | [A] | [W] | [W] | [V] | [A] | [Obr/min] | [1] |
380,684 | 3,893 | 2503,540 | 2567,018 | 55,517 | 1,951 | 1499,909 | 0,999 |
377,182 | 4,838 | 3101,554 | 3160,695 | 55,466 | 1,953 | 1500,173 | 1,000 |
376,345 | 5,245 | 3363,344 | 3418,691 | 55,301 | 1,944 | 1500,209 | 1,000 |
375,768 | 6,069 | 3893,591 | 3950,241 | 55,465 | 1,948 | 1500,231 | 1,000 |
373,905 | 7,226 | 4618,579 | 4679,685 | 55,543 | 1,950 | 1500,176 | 0,999 |
368,568 | 8,697 | 5487,035 | 5551,933 | 55,500 | 1,949 | 1500,312 | 1,000 |
364,000 | 10,038 | 6254,228 | 6328,505 | 55,565 | 1,950 | 1500,469 | 1,000 |
360,518 | 11,437 | 7052,387 | 7141,823 | 55,436 | 1,945 | 1500,401 | 1,000 |
350,579 | 14,055 | 8406,175 | 8534,337 | 55,349 | 1,941 | 1500,437 | 0,999 |
Tabela .Wyniki charakterystyki zewnętrznej dla współczynnika mocy równego 1
Usr |
Isr |
P |
S |
Uf |
If |
n |
cosφ |
---|---|---|---|---|---|---|---|
[V] | [A] | [W] | [W] | [V] | [A] | [Obr/min] | [1] |
367,338 | 2,606 | 670,134 | 1657,814 | 55,612 | 1,969 | 1499,799 | 0,431 |
363,495 | 3,169 | 857,871 | 1995,312 | 55,651 | 1,970 | 1500,030 | 0,435 |
358,437 | 3,803 | 1036,700 | 2360,739 | 55,528 | 1,964 | 1500,037 | 0,454 |
348,600 | 5,065 | 1312,929 | 3058,356 | 55,508 | 1,964 | 1500,084 | 0,443 |
333,356 | 6,946 | 1955,732 | 4010,356 | 55,495 | 1,962 | 1500,238 | 0,499 |
314,922 | 8,966 | 2214,495 | 4890,817 | 55,583 | 1,965 | 1500,284 | 0,465 |
283,159 | 11,999 | 2727,682 | 5884,921 | 55,580 | 1,965 | 1500,376 | 0,475 |
246,899 | 14,563 | 2655,228 | 6227,687 | 55,548 | 1,961 | 1500,195 | 0,437 |
Tabela . Wyniki charakterystyki zewnętrznej współczynnika mocy indukcyjnego
Na podstawie pomiarów wyznaczyliśmy charakterystyki zewnętrzne badanego generatora synchronicznego. Charakterystyka zewnętrzna jest to zależność napięcia od prądu twornika Usr = f(Isr) przy stałych wartościach prądu wzbudzenia If = const, współczynnika mocy dla różnych obciążeń (czynnym, indukcyjnym i pojemnościowym) cosφ = const i prędkości n = const.
Rysunek 1. Charakterystyki zewnętrzne uzyskana z pomiarów
Wnioski:
Charakterystyki zewnętrzne powinny przeciąć się przy znamionowym prądzie twornika równym 15,2 [A]. Uzyskana charakterystyka nie pokrywa się z teoretyczną ponieważ pomiary zostały rozpoczęte w innym punkcie.
Usr |
Isr |
P |
S |
Uf |
If |
n |
cosφ |
---|---|---|---|---|---|---|---|
[V] | [A] | [W] | [W] | [V] | [A] | [Obr/min] | [1] |
392,784 | 4,955 | 1557,218 | 3371,017 | 70,172 | 2,563 | 1499,961 | 0,464 |
395,325 | 6,585 | 2086,736 | 4509,044 | 75,610 | 2,756 | 1499,989 | 0,460 |
397,017 | 8,436 | 2506,340 | 5800,895 | 81,554 | 2,970 | 1500,065 | 0,427 |
400,184 | 9,791 | 3013,979 | 6786,384 | 86,849 | 3,158 | 1500,230 | 0,441 |
401,187 | 11,061 | 3661,347 | 7685,845 | 90,988 | 3,305 | 1499,798 | 0,478 |
400,712 | 12,063 | 3689,354 | 8372,131 | 93,962 | 3,406 | 1500,060 | 0,442 |
401,319 | 13,577 | 4426,248 | 9437,411 | 98,496 | 3,571 | 1500,282 | 0,472 |
403,642 | 14,316 | 4403,669 | 10008,941 | 102,475 | 3,714 | 1500,397 | 0,439 |
406,365 | 15,626 | 5264,623 | 10998,154 | 108,031 | 3,904 | 1500,678 | 0,480 |
Tabela . Wyniki charakterystyki regulacyjnej dla współczynnika mocy indukcyjnego
Usr |
Isr |
P |
S |
Uf |
If |
n |
cosφ |
---|---|---|---|---|---|---|---|
[V] | [A] | [W] | [W] | [V] | [A] | [Obr/min] | [1] |
386,540 | 4,624 | 1322,402 | 3095,827 | 45,293 | 1,642 | 1499,515 | 0,431 |
383,913 | 5,933 | 1718,583 | 3945,154 | 41,637 | 1,510 | 1499,960 | 0,443 |
384,883 | 8,331 | 2428,322 | 5553,960 | 37,553 | 1,364 | 1499,838 | 0,446 |
384,833 | 11,383 | 3661,277 | 7587,003 | 33,437 | 1,216 | 1499,727 | 0,491 |
385,266 | 12,852 | 3859,589 | 8576,352 | 30,402 | 1,107 | 1499,750 | 0,457 |
385,538 | 13,889 | 4139,993 | 9274,561 | 28,845 | 1,051 | 1500,039 | 0,455 |
384,742 | 14,387 | 4299,091 | 9587,055 | 27,972 | 1,020 | 1499,735 | 0,458 |
383,831 | 14,800 | 4521,218 | 9839,031 | 27,505 | 1,003 | 1499,864 | 0,469 |
Tabela . Wyniki charakterystyki regulacyjnej dla współczynnika mocy pojemnościowego
Usr |
Isr |
P |
S |
Uf |
If |
n |
cosφ |
---|---|---|---|---|---|---|---|
[V] | [A] | [W] | [W] | [V] | [A] | [Obr/min] | [1] |
389,603 | 2,001 | 1255,203 | 1350,343 | 56,888 | 2,056 | 1499,965 | 0,999 |
389,747 | 2,201 | 1401,502 | 1486,137 | 57,232 | 2,067 | 1499,953 | 1,000 |
390,068 | 3,095 | 2023,582 | 2091,285 | 57,830 | 2,089 | 1499,693 | 0,999 |
390,836 | 3,742 | 2473,714 | 2533,122 | 59,184 | 2,136 | 1499,994 | 1,000 |
390,133 | 4,939 | 3279,817 | 3337,497 | 58,979 | 2,127 | 1500,370 | 0,999 |
392,779 | 6,035 | 4050,372 | 4105,508 | 61,175 | 2,205 | 1500,426 | 0,999 |
393,107 | 6,636 | 4464,001 | 4518,634 | 62,571 | 2,253 | 1500,615 | 1,000 |
395,235 | 8,070 | 5468,829 | 5524,378 | 64,648 | 2,329 | 1500,539 | 1,000 |
394,229 | 9,874 | 6677,401 | 6741,891 | 65,704 | 2,366 | 1500,327 | 1,000 |
397,085 | 12,080 | 8237,050 | 8308,187 | 69,955 | 2,520 | 1500,388 | 1,000 |
399,010 | 13,619 | 9337,005 | 9411,932 | 73,498 | 2,636 | 1500,298 | 1,000 |
400,692 | 15,442 | 10629,423 | 10717,068 | 76,090 | 2,732 | 1500,220 | 1,000 |
Tabela . Wyniki charakterystyki regulacyjnej dla współczynnika mocy równego 1
Na podstawie pomiarów wyznaczyliśmy charakterystyki regulacyjne badanego generatora synchronicznego. Charakterystyka regulacyjna jest to zależność prądu wzbudzenia od prądu twornika Uf = f(Isr) przy stałych wartościach napięcia Usr = const, współczynnika mocy dla różnych obciążeń (czynnym, indukcyjnym i pojemnościowym) cosφ = const i prędkości n = const.
Rysunek 3. Charakterystyki regulacyjne
Wnioski:
Charakterystyki regulacyjne dla cosφ = 1 i cosφind = 0, 5 czyli dla obciążenia czynnego i
indukcyjnego, mają przebieg rosnący ponieważ przy wzroście prądu twornika Ia, w celu
utrzymania stałej wartości napięcia na zaciskach maszyny musieliśmy zwiększyć prąd
wzbudzenia If. Spowodowane było to rozmagnesowującym oddziaływaniem twornika.
Dla cosφpoj = 0, 5 czyli dla obciążenia pojemnościowego maszyny, charakterystyka ma przebieg
malejący, co jest spowodowane domagnesowującym oddziaływaniem twornika. Wraz ze
wzrostem prądu twornika musieliśmy obniżyć wartość prądu wzbudzenia aby utrzymać stałą
wartość napięcia.
Porównując dwa stany przy takiej samej wartości prądu obciążenia, lecz różnych
współczynnikach mocy można stwierdzić że w celu uzyskania tego samego napięcia przy malejącej
wartości indukcyjnego współczynnika mocy wymagany jest coraz większy prąd wzbudzenia,
podczas gdy dla obciążenie pojemnościowego wzbudzenie prądnicy należy zmniejszać.