3360446721

3360446721



If in the expression (2) in order to replace the shifted copy of voltage U(t + x) with the shifted copy of

current I(l+x), we will get the mutual correlation function of voltage with the current:

*„,<«■>=«[<>(0 ■/(<+«■)] =

/((+t)-»,6*= (io) .l\v«yi(t+z)dt-- "% •/(>«)* +

Similarly, if in the expression (2) to replace the shifted copy of current I(t +x) with the shifted copy of

voltage U(l +x), we will get the mutual correlation function of current with the voltage:

ir,„(r)=Ju|</(<+r)-/( rtj. (11)

At a temporary shift change eąual to the zero, formulas (10) and (11) determine energy of voltage and current interaction, expressed by mutual correlation functions:

Kli (* = 0) = yjV(0I(t)dt-mv -m,, (12)

Klu(x = 0)=-jl(t) U(t)dt-m, mu . (23)

At the same time it is also known that according to the theoretical electrical engineering, active-power D is determined as arithmetical mean of instantaneous power p(l) = U(t) ■ I(t) for the interval [0, / ]:

P4)

Comparing expressions (12) and (13) with the formula (14) we come to the conclusion that active-power £) is determined by the mutual correlation function of voltage with a current Kai(x) or current with voltage Km (T) at a temporary shift X = 0 as

P = Kul(x = 0) + muml.    (15)

Then inactive power after Fryzę will be written as

J{kl, (t = 0) + ml, )x x(*r,(l = 0) + m,!)--[ir„(T = 0) + m„ m,Y

(A,+KUD,+»i)-    (16)

- \KU (x = 0) + mv ■ m, ]2

3. Results of numeral calculations and their ana-lysis

With the use of the above-mentioncd correlations productive and non-productive losses of electric power were estimated in the wires of traction network of feeder zones in the areas of one of Ukrainian railways electrified on a direct current (+3.0 kB). With this purpose we have got time dependences of the rectified feeder voltage and currents, performed their cross-correlation-spectral treatment and determined electric indexes and losses of electric power A Wb and A daily dependences of which (in one of areas) are presented in fig.2 but absolute and relative values in three areas are given in Table.

Fig. 1 - Daily average (for one month) values of basie A Wb aiłd additional AfKld losses of electric power in a traction network of one of feeder areas

Fig. 2 and Table 1 shows that daily average values of non-productive losses of electric power, at first, exceed productive losses A Wb by many days. Secondly, non-productive losses are 5.62...9.93 (and maximal values - up to 15 %) of consumed (active) energy W by electro-mobile composition and up to 140 % in comparison with productive losses. Conseąuently, non-productive (additional) losses exceed the productive losses of electric power almost by 40%.

POJAZDY SZYNOWE NR 3/2011

15



Wyszukiwarka

Podobne podstrony:
local side friction fs to the cone resistance qc, has to be expressed as a percentage in order
must be performed in order to implement a high performance hardware component that carries out the o
(31) In order to increase the availability of information on the use of medicinal products in t
The goals of Design Survey are to (1) provide an introductory knowledge of design in order to assist
jff 019 SACRIFICE THROWS A Sacrifice Throw is one in which you place your-self on the ground in orde
NOTICE EDIT/ UPDATION BY APPLICANTS IN THE REGISTRATION FORM In order to make the process morę stude
168 A. Wyszomirski principles of public relations in order to gain favour of voters and raise the pr
EPIA 2011 ISBN: 978-989-95618-4-7 In order to use Weka. the extracted gamę States must be converted
Logistyka - nauka It is necessary to make a lot of irwestment in the infrastructure in order to adap
20402 Page TUTORIALS MY FIRST STEP is to choose my papers in order to coordinate the Copic colors&n
6-2012 TRIBOLOGIA 35 In order to eliminate the impact of the axial run-out on the measurement of lin

więcej podobnych podstron