background image

A

We keep power under control.

www.moeller.co.uk

PLS – Miniature 
Circuit Breakers

PKS – RCBOs

PFIM – RCDs

Moeller Consumer Units and the
17

th 

Edition Wiring Regulations

background image

2

3

The introduction of the 17

th 

Edition of the IEE Wiring 

Regulations on the 1

st 

January 2008 has major 

implications for all electrical contractors, designers 
and consultants. From 1

st 

July 2008 all new electrical 

installations will have to be designed to comply with 
the new regulations.

The biggest area of concern at present is the effect 

on an individual’s home being wired or re-wired. The 
examples used in this brochure will help the electrical 
engineer to select the correct assembly. We use the term 
assembly as there are no specific consumer units that 
meet the 17

th 

Edition – it is how the building is wired 

that dictates the components required, which in turn are 
assembled into a consumer unit.

Practically speaking, there are five aspects that 

the 17

th 

Edition identifies as requiring consideration 

for installations that are not under the supervision of 
skilled people (e.g. qualified electricians) or instructed 
people (e.g. facilities managers) – i.e. most domestic 
installations, but also some commercial installations. 
These are:

  Socket outlets for general use in domestic installations 

must have the additional protection of an RCD not 
exceeding 30mA (regulation 411.3.3)

  All circuits in locations containing a bath or shower 

must be protected by an RCD not exceeding 30mA 
(regulation 701.411.3.3)

  Cables buried in a wall or partition at a depth of 

less than 50mm, and not mechanically protected by 
appropriate earthed metal, must be protected by an 
RCD not exceeding 30mA (regulations 522.6.6–8)

  To prevent nuisance tripping, unnecessary hazards, 

and minimise inconvenience, circuits should not be 
connected to a single upstream RCD (regulation 
314.1)

  Separate circuits shall not be affected by the failure of 

other circuits (regulation 314.2)

When designing the installation and selecting the correct 
assembly, the electrician will need to consider the above 
five aspects, in accordance with the regulations. It is not 
solely the function of a particular consumer unit that has 
one, two or three RCDs with an incomer isolator to solve 
the problem of meeting the 17

th 

Edition regulations. 

The following pages will provide a practical guide to 

help you to select the components for an assembly to 
ensure that the installation complies with the 17

th 

Edition 

regulations.

Everything starts from the wiring scheme

When designing an installation in a new build project, 
there are various options to consider, in order to satisfy 
the requirements of the 17

th 

Edition. For example, 

consider burying the cables more than 50mm into the 
walls, or protect the cable with earthed metal, to remove 
the need for RCD protection.

Once the wiring scheme has been finalised, the 

process of selecting how best to protect the circuits and 
the people can begin.

The regulations are open to interpretation, 

particularly regarding the division of installations, where 
acceptable levels of inconvenience resulting from a fault 
can be somewhat subjective. (See page 11 for regulations 
314.1 and 314.2.)

To this end, the following pages outline various 

consumer unit configurations that, dependent on the 
installation design
, will offer a Fully Compliant Assembly 

FCA

 ) or Partially Compliant Assembly ( 

PCA

 ), 

or illustrate possible pitfalls making an installation 
potentially dangerous and so a Non-Compliant Assembly 

NCA

 ).

Note that the above terms indicate Moeller’s 

assessment of how a particular installation may comply 
with the regulations: a Partially Compliant Assembly 
has been judged by Moeller to satisfy all aspects where 
an RCD has to be used for safety reasons but does not 
comply with all parts of regulation 314; a Non-Compliant 
Assembly is judged to satisfy neither safety aspects nor 
regulation 314.

Customers are looking for a competitive offering, 

balanced with potential safety aspects and avoiding the 
hazards and nuisance that a short circuit trip, overload 
condition or earth leakage may cause.

For example, a consumer unit with an isolator and 

double RCD (see page 3 Example A) is often promoted 
as a way of meeting the 17

th 

Edition regulations on the 

basis that every circuit is protected by an RCD, and the 
circuits split evenly between two RCDs. However, in the 
event of a fault on either set of MCBs, the RCD may 
trip as well. This creates an unwanted disconnection 
of the MCBs where no fault exists (contrary to section 
314.1) and also causes unwanted disconnection of other 
circuits (contrary to section 314.2). Many manufacturers 
are promoting the dual RCD board as a fully compliant 
solution; however compliance is dependent on the 
design of the installation and at best this will only be a 
Partially Compliant Assembly.

You can find examples of Fully Compliant Assemblies 

on pages 5 and 6.

Introduction

 

background image

2

3

Dual RCD split load board

A dual RCD split load board will meet the 17

th 

Edition 

requirements for the following:

  Socket outlets for general use in domestic installations 

must have the additional protection of an RCD not 
exceeding 30mA.

  All circuits in locations containing a bath or shower 

must be protected by an RCD not exceeding 30mA.

  Cables buried in a wall or partition at a depth of 

less than 50mm, and not mechanically protected by 
appropriate earthed metal, must be protected by an 
RCD not exceeding 30mA.

However, depending on the installation design, it is 
unlikely to satisfy the regulations on:

  To prevent nuisance tripping, unnecessary hazards, 

and minimise inconvenience, circuits should not be 
connected to a single upstream RCD.

  Separate circuits shall not be affected by the failure of 

other circuits.

6A

MCB

6A

MCB

6A

MCB

32A

MCB

6A

MCB

32A

MCB

32A

MCB

40A

MCB

RCD

RCD

MAIN

ISOLATOR

smoke alarms

upstairs lights

outside lights

shower

downstairs and

bathr

oom lights

upstairs sockets

downstairs sockets

cooker

Example A

NCA

Example A

Dual RCD split load board

In the event of a fault on either set of MCBs, the RCD 
may trip as well. This creates an unwanted disconnection 
of the MCBs where no fault exists (contrary to section 
314.1) and also causes unwanted disconnection of other 
circuits (contrary to section 314.2).

Prior to the 17

th 

Edition, lights have not been part of 

the RCD circuit as they tend to trip the RCD whenever 
an incandescent bulb fails, for example, causing 
unacceptable nuisance. Having the lights in the same 
circuit may cause nuisance disconnection to any other 
circuit supplied on the RCD.

In addition there is a smoke alarm and a light circuit 

on the same RCD, so every time the light circuit trips 
(when a bulb fails) the house and the alarm circuit could 
be disabled, putting the occupants at risk of a fire not 
being detected.

The safety implications of this configuration by not 

addressing the requirements of section 314 make this a 
Non-Compliant Assembly.

background image

4

5

Split load board with independent RCBOs

A split load board with independent RCBOs will meet the 
17

th 

Edition requirements for the following:

  Socket outlets for general use in domestic installations 

must have the additional protection of an RCD not 
exceeding 30mA.

  All circuits in locations containing a bath or shower 

must be protected by an RCD not exceeding 30mA.

  Cables buried in a wall or partition at a depth of 

less than 50mm, and not mechanically protected by 
appropriate earthed metal, must be protected by an 
RCD not exceeding 30mA.

However, depending on the installation design, whilst 
this layout takes into account the danger arising from the 
failure of a single circuit (such as lighting) it does not fully 
comply with:

  To prevent nuisance tripping, unnecessary hazards, 

and minimise inconvenience, circuits should not be 
connected to a single upstream RCD.

  Separate circuits shall not be affected by the failure of 

other circuits.

Example B

32A

MCB

32A

MCB

32A

MCB

40A

MCB

6A

RCBO

6A

RCBO

6A

RCBO

6A

RCBO

RCD

MAIN

ISOLATOR

shower upstairs sockets

downstairs sockets

cooker

outside lights

upstairs lights

downstairs and 

bathr

oom lights

smoke alarms

PCA

Example B

Split load board with independent RCBOs

It may be advisable to have a socket circuit on a 
separate circuit. In larger residential properties it would 
be advisable to separate the downstairs circuit or the 
kitchen circuit from the other circuits supplied by a sole 
RCD to ensure that in the event of a fault there would be 
at least one power circuit available.

Prior to the 17

th 

Edition, it was common to have all 

socket power circuits supplied from one RCD with no 
account of the implications for safety or significant 
inconvenience being apparent. However, the increasing 
number of electronic devices now found in a home 
results in a greater amount of earth leakage current 
that may lead to a tripping of the RCD and fall foul of 
531.2.4.

Note  Also depending on the wiring scheme the smoke 
detector may not need to be an RCBO.

background image

4

5

Example C

Main switch with RCBOs on all circuits

A standard main switch disconnector controlled 
consumer unit with RCBOs for every outgoing circuit 
instead of the usual MCBs, will fully comply with the 
17

th 

Edition regulations. A fault on any circuit will 

not impact on other circuits, and so all aspects of the 
regulations are satisfied.

  Socket outlets for general use in domestic installations 

must have the additional protection of an RCD not 
exceeding 30mA.

  All circuits in locations containing a bath or shower 

must be protected by an RCD not exceeding 30mA.

  Cables buried in a wall or partition at a depth of 

less than 50mm, and not mechanically protected by 
appropriate earthed metal, must be protected by an 
RCD not exceeding 30mA.

  To prevent nuisance tripping, unnecessary hazards, 

and minimise inconvenience, circuits should not be 
connected to a single upstream RCD.

  Separate circuits shall not be affected by the failure of 

other circuits.

6A

RCBO

6A

RCBO

6A

RCBO

6A

RCBO

MAIN

ISOLATOR

shower

upstairs sockets

downstairs sockets

cooker

immersion heater

upstairs lights

downstairs and 

bathr

oom lights

smoke alarms

16A

RCBO

32A

RCBO

32A

RCBO

40A

RCBO

40A

RCBO

burglar alarm

FCA

Example C

Main switch with RCBOs on all circuits

background image

6

7

Example D

Main switch with RCBOs on critical circuits

By looking closely at the wiring scheme in an installation, 
the assembly in Example C can be made more cost 
effective by using MCBs to protect some circuits rather 
than RCBOs, without compromising compliance with the 
17

th 

Edition.

For example, at the point of cable entry to the 

consumer unit, incoming and outgoing cable runs are 
all encased in suitable ‘metal trunking’ or buried deeper 
than 50mm, so do not require RCD protection. As none 
of the cables are in the walls, the smoke alarms similarly 
do not require RCD protection.

The burglar alarm system may have its own trunking 

or metal covering for the supply to the main control 

6A

MCB

6A

MCB

6A

RCBO

6A

RCBO

MAIN

ISOLATOR

shower

upstairs sockets

downstairs sockets

cooker

immersion heater

upstairs lights

downstairs and 

bathr

oom lights

smoke alarms

16A

MCB

32A

RCBO

32A

RCBO

40A

RCBO

40A

MCB

burglar alarm

FCA

Example D

Main switch with RCBOs on critical circuits

console. If it does, and all the other devices are low 
voltage or cable runs in the ceiling, then this too could be 
MCB protected. This will depend on the wiring scheme 
employed for this ancillary piece of equipment.

You could also decide that the immersion heater cable 

and cooker point (without socket) are in areas where 
they can be surface mounted and shrouded inside a short 
length of conduit, or buried deeper than 50mm in the 
wall.

This example illustrates that by analysing the wiring 

scheme, RCBOs can be replaced with MCBs, reducing the 
costs whilst still providing a Fully Compliant Assembly 
(FCA).

background image

6

7

Example E

By reviewing the wiring scheme employed with the split 
load assembly proposed in Example B, the cost of the 
finished assembly can be reduced, and partial compliance 
with the regulations achieved.

The split load board laid out here will meet the 

17

th 

Edition requirements for the following:

  Socket outlets for general use in domestic installations 

must have the additional protection of an RCD not 
exceeding 30mA.

  All circuits in locations containing a bath or shower 

must be protected by an RCD not exceeding 30mA.

  Cables buried in a wall or partition at a depth of 

less than 50mm, and not mechanically protected by 
appropriate earthed metal, must be protected by an 
RCD not exceeding 30mA.

However, depending on the installation design, it is 
unlikely to satisfy the regulations on:

  To prevent nuisance tripping, unnecessary hazards, 

and minimise inconvenience, circuits should not be 
connected to a single upstream RCD.

  Separate circuits shall not be affected by the failure of 

other circuits.

32A

MCB

32A

MCB

40A

MCB

RCD

MAIN

ISOLATOR

shower upstairs sockets

downstairs sockets

cooker

immersion heater

upstairs lights

downstairs and 

bathr

oom lights

smoke alarms

6A

RCBO

6A

RCBO

6A

MCB

6A

MCB

16A

MCB

burglar alarm

40A

MCB

PCA

Example E

Split load board with RCBOs on critical circuits

With this example there is still the risk of one circuit 
failure impacting on another (regulation 314.2); however 
the level of inconvenience could be considered to be 
acceptable (only the sockets and showers are affected), 
and no hazard or safety issues are inherent. Again, the 
installer will need to consider the amount of leakage in 
the installation, due to electronic devices in the house, 
and it may be a consideration to split the power sockets 
and have one of them on an RCBO.

The end result is that no base consumer unit exists 

that complies with the 17

th 

Edition. The choice of 

consumer unit and the configuration of devices within 
it can only be made after the wiring scheme has been 
finalised.

Split load board with RCBOs on critical circuits

background image

8

9

2-Pole · 100A Main Switch Controlled

Outgoing Ways

Dimensions (mm)

  Width  Height  Depth

Part Number

2

172

225

111

BC-P2

6

244

225

111

BC-P6

10

316

225

111

BC-P10

12

351

225

111

BC-P12

18

457

225

111

BC-P18

2-Pole · RCD Controlled

Type

Outgoing Ways

RCD Rated Current I

n

 (A)

Dimensions (mm)

  Width  Height  Depth

Part Number

30mA RCD-controlled

2

40

172

225

111

BC-P2R40

2

63

172

225

111

BC-P2R63

6

63

244

225

111

BC-P6R63

6

80

244

225

111

BC-P6R80

6

100

244

225

111

BC-P6R100

10

63

316

225

111

BC-P10R63

10

80

316

225

111

BC-P10R80

10

100

316

225

111

BC-P10R100

12

63

351

225

111

BC-P12R63

12

80

351

225

111

BC-P12R80

12

100

351

225

111

BC-P12R100

18

80

457

225

111

BC-P18R80

18

100

457

225

111

BC-P18R100

100mA time-delayed

RCD (Type G)

12

100

351

225

111

BC-P12R100G

18

100

457

225

111

BC-P18R100G

Split Load · 2-Pole · 100A Main Switch / 30mA RCD Controlled

Outgoing Ways

RCD Ways Available* RCD Rated Current I

n

 (A)

Dimensions (mm)

  Width  Height  Depth

Part Number

8

 1–7

63

316

225

111

BC-P8SR63

8

 1–7

80

316

225

111

BC-P8SR80

10

 1–9

63

351

225

111

BC-P10SR63

10

 1–9

80

351

225

111

BC-P10SR80

16

 1–15

80

457

225

111

BC-P16SR80

Note

  * number of freely configurable RCD protected ways.

Dual RCD · Split Load · 100A Main Switch / 30mA RCD Controlled

Outgoing Ways

RCD Ways Available* RCD Rated Current I

n

 (A)

Dimensions (mm)

  Width  Height  Depth

Part Number

14

1–14

63 + 63

457

225

111

BC-P14SR63R63

14

1–14

80 + 63

457

225

111

BC-P14SR80R63

14

1–14

80 + 80

457

225

111

BC-P14SR80R80

Note

  * number of freely configurable RCD protected ways.

Toggle Colours

2 A

4 A

6 A

10 A 13 A

16 A

20 A 25 A 32 A

40 A

50 A 63 A

XBoard Consumer Units

Insulated

background image

8

9

2-Pole · 100A Main Switch Controlled

Outgoing Ways

Dimensions (mm)

  Width  Height  Depth

Part Number

2

180

223

113

BC-M2

6

252

223

113

BC-M6

10

324

223

113

BC-M10

12

359

223

113

BC-M12

18

465

223

113

BC-M18

2-Pole · RCD Controlled

Type

Outgoing Ways

RCD Rated Current I

n

 (A)

Dimensions (mm)

  Width  Height  Depth

Part Number

30mA RCD-controlled

2

40

180

223

113

BC-M2R40

2

63

180

223

113

BC-M2R63

6

63

252

223

113

BC-M6R63

6

80

252

223

113

BC-M6R80

6

100

252

223

113

BC-M6R100

10

63

324

223

113

BC-M10R63

10

80

324

223

113

BC-M10R80

10

100

324

223

113

BC-M10R100

12

63

359

223

113

BC-M12R63

12

80

359

223

113

BC-M12R80

12

100

359

223

113

BC-M12R100

18

80

465

223

113

BC-M18R80

18

100

465

223

113

BC-M18R100

100mA time-delayed

RCD (Type G)

12

100

359

223

113

BC-M12R100G

18

100

465

223

113

BC-M18R100G

Split Load · 2-Pole · 100A Main Switch / 30mA RCD Controlled

Outgoing Ways

RCD Ways Available* RCD Rated Current I

n

 (A)

Dimensions (mm)

  Width  Height  Depth

Part Number

8

 1–7

63

324

223

113

BC-M8SR63

8

 1–7

80

324

223

113

BC-M8SR80

10

 1–9

63

359

223

113

BC-M10SR63

10

 1–9

80

359

223

113

BC-M10SR80

16

 1–15

80

465

223

113

BC-M16SR80

Note

  * number of freely configurable RCD protected ways.

Dual RCD · Split Load · 100A Main Switch / 30mA RCD Controlled

Outgoing Ways

RCD Ways Available* RCD Rated Current I

n

 (A)

Dimensions (mm)

  Width  Height  Depth

Part Number

14

1–14

63 + 63

465

223

113

BC-M14SR63R63

14

1–14

80 + 63

465

223

113

BC-M14SR80R63

14

1–14

80 + 80

465

223

113

BC-M14SR80R80

Note

  * number of freely configurable RCD protected ways.

Toggle Colours

2 A

4 A

6 A

10 A 13 A

16 A

20 A 25 A 32 A

40 A

50 A 63 A

XBoard Consumer Units

Metal

background image

10

11

Miniature Circuit Breakers

 · single-pole · 6kA

Rated Current I

n

 (A)

B Curve

C Curve

2

PLS6-B2

PLS6-C2

6

PLS6-B6

PLS6-C6

10

PLS6-B10

PLS6-C10

13

PLS6-B13

PLS6-C13

16

PLS6-B16

PLS6-C16

20

PLS6-B20

PLS6-C20

25

PLS6-B25

PLS6-C25

32

PLS6-B32

PLS6-C32

40

PLS6-B40

PLS6-C40

50

PLS6-B50

PLS6-C50

63

PLS6-B63

PLS6-C63

Combined RCD/MCB (RCBO)

 · single-pole + Neutral · conditionally surge current proof 250A · B & C curve · type AC  

Rated Current I

n

 (A)

Type / Tripping Current

B Curve · 30mA

B Curve · 100mA

C Curve · 30mA

C Curve · 100mA

6

PKS6-6/1N/B/003

PKS6-6/1N/B/01

PKS6-6/1N/C/003

PKS6-6/1N/C/01

10

PKS6-10/1N/B/003

PKS6-10/1N/B/01

PKS6-10/1N/C/003

PKS6-10/1N/C/01

13

PKS6-13/1N/B/003

PKS6-13/1N/B/01

PKS6-13/1N/C/003

PKS6-13/1N/C/01

16

PKS6-16/1N/B/003

PKS6-16/1N/B/01

PKS6-16/1N/C/003

PKS6-16/1N/C/01

20

PKS6-20/1N/B/003

PKS6-20/1N/B/01

PKS6-20/1N/C/003

PKS6-20/1N/C/01

25

PKS6-25/1N/B/003

PKS6-25/1N/B/01

PKS6-25/1N/C/003

PKS6-25/1N/C/01

32

PKS6-32/1N/B/003

PKS6-32/1N/B/01

PKS6-32/1N/C/003

PKS6-32/1N/C/01

40

PKS6-40/1N/B/003

PKS6-40/1N/B/01

PKS6-40/1N/C/003

PKS6-40/1N/C/01

Main Incoming Switch · 2-Pole · 10kA

Rated Current I

n

 (A)

Part Number

63

IS-63/2

80

IS-80/2

100

IS-100/2

125

IS-125/2

Outgoing Devices

Incoming Devices

XBoard Consumer Units

Incoming and Outgoing Devices

Toggle Colours

2 A

4 A

6 A

10 A 13 A

16 A

20 A 25 A 32 A

40 A

50 A 63 A

Standard AC RCDs · 2-Pole  

Rated Current I

n

 (A)

Tripping Current

30mA

100mA

300mA

500mA

16 *

PFIM-16/2/001

25

PFIM-25/2/003

PFIM-25/2/01

PFIM-25/2/03

PFIM-25/2/05

40

PFIM-40/2/003

PFIM-40/2/01

PFIM-40/2/03

PFIM-40/2/05

63

PFIM-63/2/003

PFIM-63/2/01

PFIM-63/2/03

PFIM-63/2/05

80

PFIM-80/2/003

PFIM-80/2/01

PFIM-80/2/03

PFIM-80/2/05

100

PFIM-100/2/003

PFIM-100/2/01

PFIM-100/2/03

PFIM-100/2/05

Note

  * 16 A RCD is rated for 10mA earth leakage.

background image

10

11

Key Extracts

from 17

th 

Edition Regulations

Note:  There are exceptions when the socket 
outlets are used by skilled or instructed 
persons, but not relevant in residential 
property. For example 411.3.3 relates to socket 
outlets located anywhere in a home, including 
the socket in the cooker outlet. However RCD 
protection for the cooker outlet is required if 
any of the cables are buried in the wall and 
not deeper than 50mm, as indicated in 522.6.

Part 5   Requirements for protecting cable against impact 
This will often result in the need for additional RCD protection. This 
is covered in 522.6.6, 522.6.7 and 522.6.8 and can be summarised 
as follows:
All circuits buried in a wall or partition at less than 50mm depth and 
without mechanical protection require RCD protection.

Key extracts from 17

th 

Edition of the 

IEE Wiring Regulations BS 7671 : 2008

314   Division of Installation
314.1
  Every installation shall be divided into circuits, as necessary, to 

(i) avoid hazards and minimize inconvenience in the event of a fault
(iii) take account of danger that may arise from the failure of a 
single circuit such as a lighting circuit.

314.2  Separate circuits shall be provided for parts of the installation 

which need to be separately controlled, in such a way that those 
circuits are not affected by the failure of other circuits, and due 
account shall be taken of the consequences of the operation of any 
single protective device.

411.3.3  Additional protection
In a.c. systems, additional protection by means of an RCD in 
accordance with Regulation 415.1 shall be provided for:
(i) socket-outlets with a rated current not exceeding 20A that are 
for use by ordinary persons and are intended for general use.

Section 701   Locations containing a bath or shower
701.411.3.3
  Additional protection by RCDs
Additional protection shall be provided for all circuits of the 
location, by the use of one or more RCDs having the characteristics 
specified in Regulation 415.1.1 (30mA RCD)

531.2.4  An RCD shall be so selected and the electrical circuits so 

sub divided that any protective conductor current which may be 
expected to occur during normal operation of the connected load(s) 
will be unlikely to cause unnecessary tripping of the device.

Note:  see regulations 314.1 and 531.2.4.

Extracts printed with permission of The Institute of Engineering and Technology.

background image

12

A

We keep power under control.

Moeller Electric Limited

PO Box 35, Gatehouse Close

Aylesbury

Buckinghamshire HP19 8DH

Direct sales ordering and technical support

tel 01296 397400
fax 01296 392413
email sales@moeller.co.uk
email support@moeller.co.uk

© Moeller Electric Limited 05/08
T0200-276GB