Understanding Fan Curves


®
FAN ENGINEERING
Information and Recommendations for the Engineer FE-2000
Understanding Fan Curves
Figure 1. Static Pressure Curve, Vaneaxial
Introduction
A
This document contains introductory material designed
to familiarize the user with the conventions and terminol-
6
ogy related to fan curves. Various axial and centrifugal
fan performance curves will be illustrated throughout this
article with no attempt made to rationalize any particular
5
selection. For a more in-depth look into the character-
B
istics of different fan types, refer to FE-2300 for axial
STALL
C
fans and FE-2400 for centrifugal fans.
REGION
4
Pressure Volume Curve
3
The most important characteristic of a fan or a system
is the relationship that links the primary variables asso-
ciated with its operation. The most commonly used fan
2
characteristic is the relationship between pressure rise
and volume flow rate for a constant impeller speed
1
(RPM). Similarly the relationship between pressure loss
and volume flow rate is the most commonly used sys-
D
tem characteristic.
0
Fan pressure rise characteristics are normally
4
0 1 2 3 5 6
CFM
expressed in either total pressure (TP) or static pressure
(SP), with static pressure being the units most com-
Figure 2. Static Pressure Curve, Backward Inclined
monly used in the United States. The fan volume flow
Centrifugal
rate (airflow) is commonly expressed in cubic feet per
minute, or CFM. Therefore, the system pressure loss and
volume flow rate requirements are typically expressed as
7
a certain value of static pressure (SP) at some CFM.
The fan  pressure-volume curve is generated by con-
C
necting the fan to a laboratory test chamber. By follow- 6
ing very specific test procedures as outlined in the Air
A
Movement and Control Association (AMCA) Standard
5
210, data points are collected and plotted graphically for
a constant RPM, from a  no flow block off condition
4
to a  full flow or wide condition. Figure 1 represents
such a curve that is typical for a vaneaxial fan, and is
3
commonly referred to as a  static pressure curve.
Point A represents the point of zero airflow on the
static pressure curve. It is frequently referred to as  block
2
off,  shut off,  no flow, and  static no delivery.
Point B depicts the stall region of the static pressure
1
curve. Operation in this area is discouraged because of
erratic airflow that generates excessive noise and vibra-
D
0
tion. For a more in-depth look into this phenomenon
0 1 2 3 4 5 6 7 8 9
CFM
refer to ED-600,  Surge, Stall & Instabilities in Fans.
Point C depicts what is referred to as the peak of
the static pressure curve, and point D is the point of angle propeller fans and forward curve centrifugal fans.
maximum airflow. Point D is also referred to as  free In contrast, compare this curve to Figure 2, which rep-
delivery,  free air,  wide open performance, and  wide resents a typical curve for a backward inclined centrifu-
open volume. gal fan. This curve shape is also representative of
Curve segment CD is often referred to as the right radial blade centrifugal fans.
side of the fan curve. This is the stable portion of the Note the lack of a pronounced dip on this curve.
fan curve and is where the fan is selected to operate. Nevertheless, the area left of peak is also a stall region
It then follows that curve segment AC is the left side and selections in this area should be avoided.
of the fan curve and is considered to be the unstable The fan static pressure curve is the basis for all air-
portion of the curve. flow and pressure calculations. For a given SP on the
Figure 1 is a vaneaxial curve with a pronounced dip static pressure curve there is a corresponding CFM at
(stall region) that is also a typical curve shape for high a given RPM (see Figure 3).
©2001 Twin City Fan Companies, Ltd.
STATIC PRESSURE
STATIC PRESSURE
RE
SELECTION RANGE
COMMENDED
B
ALL REGION
ST
SELECTION RANGE
RECOMMENDE
D
Figure 3. Static Pressure Curve, Vaneaxial Figure 5. Static Pressure/Horsepower Curve
Backward Inclined Centrifugal
6
7 7
5
6 6
4 5 5
4 4
3
3 3
2
2 2
1
1 1
0
4
0 1 2 3 5 6
0
CFM
0 1 2 3 4 5 6 7 8 9
CFM
Simply locate some unit of pressure on the left hand
SP scale and project a horizontal line to the point of Even though the performance curves for the vane-
intersection on the static pressure curve. From the point axial fan and the centrifugal fan have completely differ-
of intersection project a vertical line to the bottom CFM ent shapes, the curves are read in the same way.
scale to establish the corresponding airflow at that par- Locate some unit of pressure on the left hand SP scale
ticular speed. In this example a static pressure of three (4 units) and project a horizontal line to the point of
units results in a CFM of 4.71 units. intersection with the SP curve. Projecting downward
from this point of intersection to the CFM scale we
establish an airflow of 6.55 units. Now project vertically
Brake Horsepower Curve upward to intersect the BHP curve. Project a horizontal
line from this point to the BHP scale and read a BHP
Having established a static pressure (SP) and an airflow
of 6.86 units.
(CFM), an operating brake horsepower (BHP) can be
established (Figure 4).
Operating Point
Figure 4. Static Pressure/Horsepower Curve, Vaneaxial
The operating point (point of operation or design point)
is defined as the fan pressure rise (SP)/volumetric flow
rate (CFM) condition where the fan and system are in a
6
12
stable equilibrium. This corresponds to the condition at
which the fan SP/CFM characteristic intersects the sys-
tem pressure loss/flow rate characteristics.
5
10
Figure 6 illustrates this fan/system operating point using
the centrifugal fan performance curve from Figure 5.
4
8
Figure 6. Fan/System Operating Point,
Backward Inclined Centrifugal
3
6
2
4
7 7
1 6 6
2
5 5
0
4
0 1 2 3 5 6
CFM
SYSTEM
4 4
LINE
OPERATING
By adding the BHP curve to the static pressure curve
POINT
3 3
from Figure 3 we complete the fan performance curve.
To determine BHP simply extend vertically the CFM
point established in Figure 3 until it intersects the BHP
2 2
curve. Draw a horizontal line from this point of intersec-
tion to the right to the BHP scale to establish a BHP of
1 1
7.27 units, which corresponds to the previously estab-
lished performance of 4.71 CFM units at 3.0 SP units.
0
Similarly, we can add the BHP curve to the static
0 1 2 3 4 5 6 7 8 9
CFM
pressure curve of the backward inclined centrifugal fan
from Figure 2 to complete that fan performance curve
(Figure 5).
Page 2 Fan Engineering FE-2000
BHP
STATIC PRESSURE
STATIC PRESSURE
BHP
STATIC PRESSURE
BHP
STATIC PRESSURE
BHP
SP
B
H
P
SP
BHP
SP
The system line is simply a parabolic curve made up Figure 8. Variable System Characteristic Curve,
of all possible SP and CFM combinations within a given Backward Inclined Centrifugal
system and is determined from the fan law that SP var-
ies as RPM2. Another fan law states that CFM varies as
the RPM. Therefore, we can also say that SP varies as
7 7
CFM2. Note: Some systems have modulating dampers
which will not follow this parabolic curve.
6 6
Sometimes a fan system does not operate properly
according to the design conditions. The measured air-
flow in the fan system may be deficient or it may be
5 5
delivering too much CFM. In either case, it is necessary
to either speed the fan up or slow it down to attain
4 4
design conditions. OPERATING
LINE
Knowing that the fan must operate somewhere along
SYSTEM
3 3
the system curve, and knowing that it is possible to
LINES
predict the fan performance at other speeds by applying
the following fan laws:
2 2
1. CFM varies as RPM
2. SP varies as RPM2 1 1
3. BHP varies as RPM3
0
We can now graphically present an  operating line
0 1 2 3 4 5 6 7 8 9
CFM
between various fan speeds using the fan/system oper-
ating point data from Figure 6. This results in new SP
curves and BHP curves as shown in Figure 7. Combining the fan control curve (Figure 7) with the
system controlled curve (Figure 8) results in a fan/system
Figure 7. Variable Fan Characteristic Curve, controlled curve having an  operating region as shown
Backward Inclined Centrifugal in Figure 9.
Figure 9. Variable Fan/System Characteristic Curve
INCREASING
RPM Backward Inclined Centrifugal
7 7
6 6
7 7
5 5
6 6
SYSTEM
LINE
4 OPERATING 4
LINE
5 5
INCREASING
3 3
SPEED (RPM)
4 4
OPERATING
REGION
2 2
SYSTEM
3 3
LINES
FAN
1 1
CHARACTERISTICS
2 2
0
0 1 2 3 4 5 6 7 8 9
1 1
CFM
0
These speed changes represent an example of fan
0 1 2 3 4 5 6 7 8 9
CFM
control that can be accomplished through drive changes
or a variable speed motor.
Another way to present an  operating line is to add
a damper, making the system the variable characteristic. Conclusion
By modulating the damper blades, new system lines are
The foregoing methodology provides the knowledge nec-
created resulting in an operating line along the fan
essary to understand fan curves. When used in conjunc-
curve. This can be seen graphically in Figure 8.
tion with FE-100, FE-600, FE-2300 and FE-2400, it
provides the user with the working knowledge necessary
to understand the fan performance characteristics and
capabilities of different fan equipment.
Page 3 Fan Engineering FE-2000
BHP
SP, FAN PRESSURE RISE  SYSTEM PRESSURE LOSS
BHP
BHP
SP, FAN PRESSURE RISE  SYSTEM PRESSURE LOSS
SP, FAN PRESSURE RISE  SYSTEM PRESSURE LOSS
BHP
{
SP
BHP
BHP
BHP
BHP
SP
SP
{
{
SP
SP
®
AERovENt | www.AERovENt.com
5959 trenton Lane N | minneapolis, mN 55442 | Phone: 763-551-7500 | Fax: 763-551-7501


Wyszukiwarka

Podobne podstrony:
understanding peerpoints
understanding switching?sics
Understanding and Managing Polymorphic Viruses
understanding peerpoints
understanding peerpoints
Photography Understanding Exposure
Fan 10T MS ( G54AG) L192 82
Fan Performance Characteristics of Axial Fans
understanding garmin online
understanding computers
Interpretation of DSC curves in polymer analysis 2000 Toledo
Understanding Your Relationship with money
understanding peerpoints
understanding peerpoints
Fan 0T Miy BNC S [WB] L260 82m

więcej podobnych podstron