0400 Function description D Electrical function, control unit (Webasto no 105 499) Auxiliary heater Models 124, 126, 201 a

background image

83-400

Function description

D. Electrical function, control unit as of approx. 08/86 (Webasto no.
105.499)

Note

3. Repeat start:

The following functions of this control unit

If combustion does not occur during the

(N33)

first start, the combustion air blower

have been modified or added:

continues running for 30 seconds.
Thereafter, a second start is performed

1. Undervoltage cutout:

automatically. If this also does not result

If the power supply drops below 9.5

in combustion, the combustion air blower

0.5 volts during the cut-in period, the

continues running for 60 seconds. The
total time to a fault cut-off is increased

auxiliary heater switches off. The

from the previous 4 minutes to 5 1/2

auxiliary heater can only be restarted

minutes.

after it is switched off and on again.

4. After-running controller of combustion

2. Glow plug monitoring:

air blower after interruption of

If the glow coil of the glow plug or the

combustion:

power supply is interrupted, the control

If combustion is interrupted, e.g. because

unit switches to fault. The combustion air

of a shortage of fuel, a photo-transistor in

blower continues running for approx. 60

the flame monitor assures optically

seconds. The operating indicator lamp

controlled after-running of the

then goes out and the auxiliary heater

combustion air blower. This is limited to

switches off. No automatic repeat start is

max. 80 seconds. Thereafter, the

performed as before.

electronically controlled after-running of
60 seconds commences, as before.

5. Temperature-switching points

Coolant temperature in heater (°C)

Full load to part load

78

Part load to full load

70

Start of combustion interval

86

End of combustion interval (full-load start)

78

Copyright Daimler AG 02.12.14 G/08/07. Ten wydruk WIS nie jest obj

ę

ty funkcj

ą

aktualizacji.

strona 1


Wyszukiwarka

Podobne podstrony:
0400 Function description electrical function of control unit Auxiliary heater Models 124, 126, 201
0400 Function description B Operating principle with function diagram Auxiliary heater Models 124,
0400 Function description auxiliary heater A General Models 124, 126, 201
0410 Function test Auxiliary heating BBW DBW 46 Models 124, 126, 201
Description Electronic Hotel Locks
M001816 B Eng Oil control unit
C102965 0 SERVICE CONTROL UNIT
11 Electronic linkage control
C102966 0 INSTALLATION CONTROL UNIT
0622 Removal and installation of control unit for airbag seat belt tensioner Model 126 (from 09 87)
0620 Removal and installation of control unit for airbag seat belt tensioner Model 126 (to 08 87)
US Patent 611,719 Electrical Circuit Controller
US Patent 609,249 Electric Circuit Controller
US Patent 609,248 Electric Circuit Controller

więcej podobnych podstron