Heating control
File: Heat.doc
Last edition: 4 of March 2003
Author: Mikael Krantz
History: 96-02-13/MK First released version.
96-10-03/MK Updated to Menta 1.20
97-08-29/MK Updated to Menta 3.0
98-03-09/MK Unit corrected.
98-12-30/MK New filename
2003-03-04/MK Updated to Menta 4.0
Description
Heating control with adjustable P-band and I-times. If the flag for "Normal control" is true and the "Heating allowed" flag is true, the controller is activated. In all other cases, the heating valve is forced to closed position.
Inputs
(Real) SP supply temperature, °C
(Real) Supply temperature, °C
(Binary) Normal control flag
(Binary) Heating allowed flag
Outputs
(Real) Heating control signal 0 - 100%
Parameters
(Real) HeatingPBand 25 °C
(Real) HeatingITime 4 minutes
(Real) HeatingTravelTime 300 seconds
Public signals
(Real) HeatingITime
(Real) HeatingPBand
(Real) HeatSupply