Description
Night heating starts when the AHU is stopped, if the room temperature goes below the "NightSetpoint", with a hysteresis of 0.75°C. Night heating is blocked if there is no room sensor connected.
Inputs
(Binary) Normal day operation
(Real) Room temperature, °C.
Outputs
(Binary) Night heating
Parameters
(Real) NightSetpoint 16 °C
Public signals
(Binary) NightHeat
(Real) NightSetpoint