inst dtrcs12 pl

background image

1 SERVICE MANUAL FOR CMV

DC Inverter Multi-Split Air-Condition Unit

CMV-71V3A-T

CMV-V80WC3AQ

CMV-50V3A-E2

CMV-V40H13AD

REFRIGERENT

R410A

HEAT PUMP

SERVICE

MANUAL

background image

2 SERVICE MANUAL FOR CMV

Table of Contents

1. INTRODUCTION .................................................................................................1-1

2. PRODUCT

DATA SHEET ...................................................................................2-1

3. RATING

CONDITIONS ........................................................................................3-1

4. OUTLINE

DIMENSIONS .....................................................................................4-1

5. PERFORMANCE

DATA ......................................................................................5-1

6. PRESSURE

CURVES .........................................................................................6-1

7. ELECTRICAL DATA .............................................................................................7-1

8. WIRING

DIAGRAMS ...........................................................................................8-1

9. REFRIGERATION

DIAGRAMS ...........................................................................9-1

10. TUBING

CONNECTIONS .....................................................................................10-1

11. CONTROL

SYSTEM ...........................................................................................11-1

12. TROUBLESHOOTING ........................................................................................12-1

13. EXPLODED VIEWS AND SPARE PARTS LISTS ................................................13-1

14. APPENDIX

A























background image

3 SERVICE MANUAL FOR CMV

1. INTRODUCTION

1.1 General

The new CMV is a high efficiency DC inverter technology outdoor unit,
since it’s a lego concept unit, it can be matched to several inverter indoor units such as wall
mounted type with a capacity range of 2.0 – 5.0 Kw for each single indoor unit.

1.2 Main

Features

DC Inverter

R410a
sine wave form and 120 degree rectangurlar wave form in comprssor driver
sensor less inverter compressor driver
high speed calculation for accurate sine wave form vector control
smart PFC control
fuzzy logic con

trol

High COP (“A “ or “B” class energy rating)
Lego Concept
Pre-Charged

.

Cooling operation at outdoor temperature down to 10

0

C.

Heating operation at outdoor temperature down to -15

0

C.

Variable Speed outdoor fan.
Low noise level
EEV for each indoor unit

1.3 Tubing Connections

Flare type interconnecting tubing to be produced on site.
For further details please refer to APPENDIX A on this manual, and to the relevant indoor
service Manual,

1.4 Inbox Documentation

Each indoor unit is supplied with its own installation and operation manuals.
















background image

4 SERVICE MANUAL FOR CMV

2 .

P R O D U C T D A T A S H E E T

2 . 1 . 1

O u t d o o r U n i t C M V - 5 0 V 3 A - E 2 S p e c i f i c a t i o n s .

OUTDOOR UNNIT

Model

CMV-50V3A-E2

Operation Model

Cooling

Heating

Kcal/hr

4300(1032-5848)

5160(860-6278)

Btu/hr

17064(4095-23207)

20477(3412-24913)

Capacity

W

5000(1400-6800)

6000(1300-7300)

Total Input

W

1400(460-2300)

1600(450-2200)

E.E.R(Cooling)/C.O.P(Heating)

W/W

3.57

3.75

Starting Current

A

1

Inrush Current

A

<35

Power Supply

V/PH/Hz

220-240V 1PH 50Hz

Refrigerant control

Electronic expansion valve

Compressor Type

Twin Rotary DC Inverter

Model

C-6RZ146H1A

Starter Type

Low frequency start

Protection Device

Outdoor SW control

Heat Exchanger

Hydrophilic corrugated fins ,Grooved tube

Fan×No.

Propeller×1

Airflow

m

3

/hr

2450

Motor Output

W

60

Defrost method

Reverse cycle

Pressure

55

55

Noise Level

Power

dB(A)

65

65

Dimensions

W*D*H

mm

850×292×607

Weight

Kg

50

Package

W*D*H

mm

995×415×680

O

U

TDOO

R UN

NI

T

Unit Stacking

#

4

Refrigerant Charge

g

R410A-1580g

Liquid

mm

2×6.35

Tube Size O.D

Suction

mm

2×9.52

Indoor & outdoor

Flared

Height difference betweeen indoor unit

Max.10m

Height difference betweeen indoor & outdoor

Max.10m

Tubing length

Max.20m for one unit and 30m total

TUBING

Connection method
between the indoor
and the outdoor
units

Additional charge

No need

background image

5 SERVICE MANUAL FOR CMV

2 . 1 . 2 O u t d o o r

U n i t

C M V - 7 1 V 3 A - T S p e c i f i c a t i o n s .

OUTDOOR UNIT

Model

CMV-71V3A-T

Operation Model

Cooling

Heating

Kcal/hr

6106(1290-7998)

7740(1118-9030)

Btu/hr

24231(5118-31731)

30708(4435-35826)

Capacity

W

7100(1500-9000)

8500(1700-10500)

Total Input

W

2200(580-3200)

2330(540-3000)

E.E.R(Cooling)/C.O.P(Heating)

W/W

3.227

3.648

Starting Current

A

2

Inrush Current

A

<35

Power Supply

V/PH/Hz

220-240V 1PH 50Hz

Refrigerant control

Electronic expansion valve

Compressor Type

Twin Rotary DC Inverter

Model

C-7RVN153HOW

Starter Type

Low frequency start

Protection Device

Outdoor SW control

Heat Exchanger

Hydrophilic corrugated fins ,Grooved tube

Fan×No.

Propeller×1

Airflow

m

3

/hr

3200

Motor Output

W

90

Defrost method

Reverse cycle

Pressure

57

57

Noise Level

Power

dB(A)

65

65

Dimensions

W*D*H

mm

960×344×846

Weight

Kg

82

Package

W*D*H

mm

1060×470×925

O

U

TDOO

R UN

NI

T

Unit Stacking

#

2

Refrigerant Charge

g

R410A-3,000

Liquid

mm

3×6.35

Tube Size O.D

Suction

mm

2×9.52+1×12.7

Indoor & outdoor

Flared

Height difference betweeen indoor unit

Max.15m

Height difference betweeen indoor &
outdoor

Max.15m

Tubing length

Max.25m for one unit and 50m total

TUBING

Connection method
between the indoor
and the outdoor units

Additional charge

No need

background image

6 SERVICE MANUAL FOR CMV

2 . 1 . 3 O u t d o o r

U n i t

C M V - V 8 0 W C 3 A Q S p e c i f i c a t i o n s .

OUTDOOR UNNIT

Model

CMV-V80WC3AQ

Operation Model

Cooling

Heating

Kcal/hr

6880(1720-7740)

8256(1720-9460)

Btu/hr

27296(6824-30708)

32755(6824-37532)

Capacity

W

8000(2000-9000) 9600(2000-11000)

Total Input

W

2450(710-3350)

2400(910-2950)

E.E.R(Cooling)/C.O.P(Heating)

W/W

3.26

4

Starting Current

A

2

Inrush Current

A

<35

Power Supply

V/PH/Hz

220-240V 1PH 50Hz

Refrigerant control

Electronic expansion valve

Compressor Type

Twin Rotary DC Inverter

Model

C-7RVN153HOW

Starter Type

Low frequency start

Protection Device

Outdoor SW control

Heat Exchanger

Hydrophilic corrugated fins ,Grooved tube

Fan×No.

Propeller×1

Airflow

m

3

/hr

3200

Motor Output

W

90

Defrost method

Reverse cycle

Pressure

57

57

Noise Level

Power

dB(A)

65

65

Dimensions

W*D*H

960×344×846

960×344×846

Weight

Kg

86

Package

W*D*H

1060×470×925

1060×470×925

O

U

TDOO

R UN

NI

T

Unit Stacking

#

2

Refrigerant Charge

g

R410A-3,600g

Liquid

mm

4×6.35

Tube Size O.D

Suction

mm

3×9.52+12.7

Indoor & outdoor

Flared

Height difference betweeen
indoor unit

Max.10m

Height difference betweeen
indoor & outdoor

Max.10m

Tubing length

Max.25m for one unit and 70m total

TUBING

Connection method
between the indoor
and the outdoor units

Additional charge

No need

background image

7 SERVICE MANUAL FOR CMV

2 . 1 . 4

O u t d o o r U n i t C M V - V 4 0 H 1 3 A D S p e c i f i c a t i o n s .

OUTDOOR UNNIT

Model

CMV-V40H13AD

Operation Model

Cooling

Heating

Kcal/hr

3430(1250-4460)

4000(1300-4600)

Btu/hr

13700(5000-17800)

15700(5200-18100)

Capacity

W

4000(1450-5200)

4600(1500-5300)

Total Input

W

1020(450-1580)

1050(430-1300)

E.E.R(Cooling)/C.O.P(Heating)

W/W

3.92

4.38

Starting Current

A

1

Inrush Current

A

<15

Power Supply

V/PH/Hz

220-240V 1PH 50Hz

Refrigerant control

Electronic expansion valve

Compressor Type

Single Rotary DC Inverter

Model

5RS102XCA01

Starter Type

Low frequency start

Protection Device

Outdoor SW control

Heat Exchanger

Hydrophilic corrugated fins ,Grooved tube

Fan×No.

Propeller×1

Airflow

m

3

/hr

1800

Motor Output

W

35

Defrost method

Reverse cycle

Pressure

53

53

Noise Level

Power

dB(A)

65

65

Dimensions

W*D*H

mm

860×320×550

Weight

Kg

50

Package

W*D*H

mm

905×323×573

O

U

TDOO

R UN

NI

T

Unit Stacking

#

4

Refrigerant Charge

g

R410A-1250g

Liquid

mm

2×6.35

Tube Size O.D

Suction

mm

2×9.52

Indoor & outdoor

Flared

Height difference betweeen indoor unit

Max.10m

Height difference betweeen indoor & outdoor

Max.10m

Tubing length

Max.20m for one unit and25m total

TUBING

Connection method
between the indoor
and the outdoor
units

Additional charge

No need

background image

8 SERVICE MANUAL FOR CMV

2 . 2

I n d o o r U n i t s D a t a

2 . 2 . 1 C M V S - 2 5 V 3 A - A 4 8 A

S p e c i f i c a t i o n s

INDOOR UNIT

Model Indoor Unit/Type

CMVS-25V3A-A48A

Installation method

Flare

Power Supply

V/Ph/Hz

220-240/1/50

Fan Type & Quantity

Crossflow×1

H

500

M

450

Airflow Cooling/Heating

L

m

3

/hr

360

Sound Preesure Level Cooling/Heating

L-H

dB(A)

32-41/32-41

Condensate Drain Tube I.D

mm

16

Dimensions

W/H/D

mm

270×180×790

Weight

kg

12

Packaging Dimensions

W/H/D

mm

870×350×270

IN

D

OOR

Stacking Height

Units

7

Heating Elements

KW

N/A

Moisture Removal

L/hr

0.8

2 . 2 . 2 C M V S - 3 5 V 3 A - A 4 8 A

S p e c i f i c a t i o n s

INDOOR UNIT

Model Indoor Unit/Type

CMVS-35V3A-A48A

Installation method

Flare

Power Supply

V/Ph/Hz

220-240/1/50

Fan Type & Quantity

Crossflow×1

H

550

M

450

Airflow Cooling/Heating

L

m

3

/hr

360

Sound Preesure Level Cooling/Heating

L-H

dB(A)

32-41/32-41

Condensate Drain Tube I.D

mm

16

Dimensions

W/H/D

mm

270×180×790

Weight

kg

12

Packaging Dimensions

W/H/D

mm

870×350×270

IN

D

OOR

Stacking Height

Units

7

Heating Elements

KW

N/A

Moisture Removal

L/hr

1

background image

9 SERVICE MANUAL FOR CMV

2 . 2 . 3

C M V S - 2 5 V 3 A - A 3 8 A C M V S - 2 5 V 3 A - A 3 8 B S p e c i f i c a t i o n s

INDOOR UNIT

Model Indoor Unit/Type

CMVS-25V3A-A38A

CMVS-25V3A-A38B

Installation method

Flare

Power Supply

V/Ph/Hz

220-240/1/50

Fan Type & Quantity

Crossflow×1

H

500

M

450

Airflow Cooling/Heating

L

m

3

/hr

360

Sound Preesure Level Cooling/Heating

L-H

dB(A)

32-41/32-41

Condensate Drain Tube I.D

mm

16

Dimensions

W/H/D

mm

270×180×790

Weight

kg

12

Packaging Dimensions

W/H/D

mm

880×360×250

IN

D

OOR

Stacking Height

Units

7

Heating Elements

KW

N/A

Moisture Removal

L/hr

0.8

2 . 2 . 4

C M V S - 3 5 V 3 A - A 3 8 A C M V S - 3 5 V 3 A - A 3 8 B S p e c i f i c a t i o n s

INDOOR UNIT

Model Indoor Unit/Type

CMVS-35V3A-A38A

CMVS-35V3A-A38B

Installation method

Flare

Power Supply

V/Ph/Hz

220-240/1/50

Fan Type & Quantity

Crossflow×1

H

550

M

450

Airflow Cooling/Heating

L

m

3

/hr

360

Sound Preesure Level Cooling/Heating

L-H

dB(A)

32-41/32-41

Condensate Drain Tube I.D

mm

16

Dimensions

W/H/D

mm

270×180×790

Weight

kg

12

Packaging Dimensions

W/H/D

mm

880×360×250

IN

D

OOR

Stacking Height

Units

7

Heating Elements

KW

N/A

Moisture Removal

L/hr

1

background image

10 SERVICE MANUAL FOR CMV

2 . 2 . 5 C M V S - 2 5 V 3 A - A 4 6 A

S p e c i f i c a t i o n s

INDOOR UNIT

Model Indoor Unit/Type

CMVS-25V3A-A46A

Installation method

Flare

Power Supply

V/Ph/Hz

220-240/1/50

Fan Type & Quantity

Crossflow×1

H

500

M

450

Airflow Cooling/Heating

L

m

3

/hr

360

Sound Preesure Level Cooling/Heating

L-H

dB(A)

32-41/32-41

Condensate Drain Tube I.D

mm

16

Dimensions

W/H/D

mm

270×180×790

Weight

kg

12

Packaging Dimensions

W/H/D

mm

870×350×270

IN

D

OOR

Stacking Height

Units

7

Heating Elements

KW

N/A

Moisture Removal

L/hr

0.8

2 . 2 . 6 C M V S - 3 5 V 3 A - A 4 6 A

S p e c i f i c a t i o n s

INDOOR UNIT

Model Indoor Unit/Type

CMVS-35V3A-A46A

Installation method

Flare

Power Supply

V/Ph/Hz

220-240/1/50

Fan Type & Quantity

Crossflow×1

H

550

M

450

Airflow Cooling/Heating

L

m

3

/hr

360

Sound Preesure Level Cooling/Heating

L-H

dB(A)

32-41/32-41

Condensate Drain Tube I.D

mm

16

Dimensions

W/H/D

mm

270×180×790

Weight

kg

12

Packaging Dimensions

W/H/D

mm

870×350×270

IN

D

OOR

Stacking Height

Units

7

Heating Elements

KW

N/A

Moisture Removal

L/hr

1

background image

11 SERVICE MANUAL FOR CMV

2 . 2 . 7 C M V S - 2 5 V 3 A - A 6 9 A

S p e c i f i c a t i o n s

INDOOR UNIT

Model Indoor Unit/Type

CMVS-25V3A-A69A

Installation method

Flare

Power Supply

V/Ph/Hz

220-240/1/50

Fan Type & Quantity

Crossflow×1

H

500

M

450

Airflow Cooling/Heating

L

m

3

/hr

360

Sound Preesure Level Cooling/Heating

L-H

dB(A)

32-41/32-41

Condensate Drain Tube I.D

mm

16

Dimensions

W/H/D

mm

270×180×790

Weight

kg

12

Packaging Dimensions

W/H/D

mm

875×338×285

IN

D

OOR

Stacking Height

Units

7

Heating Elements

KW

N/A

Moisture Removal

L/hr

0.8

2 . 2 . 8 C M V S - 3 5 V 3 A - A 6 9 A

S p e c i f i c a t i o n s

INDOOR UNIT

Model Indoor Unit/Type

CMVS-35V3A-A69A

Installation method

Flare

Power Supply

V/Ph/Hz

220-240/1/50

Fan Type & Quantity

Crossflow×1

H

550

M

450

Airflow Cooling/Heating

L

m

3

/hr

360

Sound Preesure Level Cooling/Heating

L-H

dB(A)

32-41/32-41

Condensate Drain Tube I.D

mm

16

Dimensions

W/H/D

mm

270×180×790

Weight

kg

12

Packaging Dimensions

W/H/D

mm

875×338×285

IN

D

OOR

Stacking Height

Units

7

Heating Elements

KW

N/A

Moisture Removal

L/hr

1

background image

12 SERVICE MANUAL FOR CMV

2 . 2 . 9 C M V - V 2 5 G 3 A / A 6 7

S p e c i f i c a t i o n s

INDOOR UNIT

Model Indoor Unit/Type

CMV-V25G3A/A67

Installation method

Flare

Power Supply

V/Ph/Hz

220-240/1/50

Fan Type & Quantity

Crossflow×1

H

500

M

450

Airflow Cooling/Heating

L

m

3

/hr

360

Sound Preesure Level Cooling/Heating

L-H

dB(A)

32-41/32-41

Condensate Drain Tube I.D

mm

16

Dimensions

W/H/D

mm

270×180×790

Weight

kg

12

Packaging Dimensions

W/H/D

mm

875×338×285

IN

D

OOR

Stacking Height

Units

7

Heating Elements

KW

N/A

Moisture Removal

L/hr

0.8

2 . 2 . 1 0

C M V - V 3 5 G 3 A / A 6 7 S p e c i f i c a t i o n s

INDOOR UNIT

Model Indoor Unit/Type

CMV-V35G3A/A67

Installation method

Flare

Power Supply

V/Ph/Hz

220-240/1/50

Fan Type & Quantity

Crossflow×1

H

550

M

450

Airflow Cooling/Heating

L

m

3

/hr

360

Sound Preesure Level Cooling/Heating

L-H

dB(A)

32-41/32-41

Condensate Drain Tube I.D

mm

16

Dimensions

W/H/D

mm

270×180×790

Weight

kg

12

Packaging Dimensions

W/H/D

mm

875×338×285

IN

D

OOR

Stacking Height

Units

7

Heating Elements

KW

N/A

Moisture Removal

L/hr

1

background image

13 SERVICE MANUAL FOR CMV

2 . 2 . 1 1 C M V - V 2 5 G 3 A / A 7 8

S p e c i f i c a t i o n s

INDOOR UNIT

Model Indoor Unit/Type

CMV-V25G3A/A78

Installation method

Flare

Power Supply

V/Ph/Hz

220-240/1/50

Fan Type & Quantity

Crossflow×1

H

500

M

450

Airflow Cooling/Heating

L

m

3

/hr

360

Sound Preesure Level Cooling/Heating

L-H

dB(A)

32-41/32-41

Condensate Drain Tube I.D

mm

16

Dimensions

W/H/D

mm

270×180×790

Weight

kg

12

Packaging Dimensions

W/H/D

mm

875×338×285

IN

D

OOR

Stacking Height

Units

7

Heating Elements

KW

N/A

Moisture Removal

L/hr

0.8

2 . 2 . 1 2

C M V - V 3 5 G 3 A / A 7 8 S p e c i f i c a t i o n s

INDOOR UNIT

Model Indoor Unit/Type

CMV-V35G3A/A78

Installation method

Flare

Power Supply

V/Ph/Hz

220-240/1/50

Fan Type & Quantity

Crossflow×1

H

550

M

450

Airflow Cooling/Heating

L

m

3

/hr

360

Sound Preesure Level Cooling/Heating

L-H

dB(A)

32-41/32-41

Condensate Drain Tube I.D

mm

16

Dimensions

W/H/D

mm

270×180×790

Weight

kg

12

Packaging Dimensions

W/H/D

mm

875×338×285

IN

D

OOR

Stacking Height

Units

7

Heating Elements

KW

N/A

Moisture Removal

L/hr

1

background image

14 SERVICE MANUAL FOR CMV

2 . 2 . 1 3 C M V - V 2 0 G 3 A / G 3 8 A

S p e c i f i c a t i o n s

INDOOR UNIT

Model Indoor Unit/Type

CMV-V20G3A/G38A

Installation method

Flare

Power Supply

V/Ph/Hz

220-240/1/50

Fan Type & Quantity

Crossflow×1

H

450

M

350

Airflow Cooling/Heating

L

m

3

/hr

270

Sound Preesure Level Cooling/Heating

L-H

dB(A)

32-41/32-41

Condensate Drain Tube I.D

mm

16

Dimensions

W/H/D

mm

270×180×790

Weight

kg

9

Packaging Dimensions

W/H/D

mm

880×360×250

IN

D

OOR

Stacking Height

Units

7

Heating Elements

KW

N/A

Moisture Removal

L/hr

0.6

2 . 2 . 1 4 C M V - V 5 0 G 3 A / H 3 8 A

S p e c i f i c a t i o n s

INDOOR UNIT

Model Indoor Unit/Type

CMV-V50G3A/H38A

Installation method

Flare

Power Supply

V/Ph/Hz

220-240/1/50

Fan Type & Quantity

Crossflow×1

H

750

M

550

Airflow Cooling/Heating

L

m

3

/hr

450

Sound Preesure Level Cooling/Heating

L-H

dB(A)

35-43/35-43

Condensate Drain Tube I.D

mm

16

Dimensions

W/H/D

mm

930×270×180

Weight

kg

14

Packaging Dimensions

W/H/D

mm

1010×360×280

IN

D

OOR

Stacking Height

Units

7

Heating Elements

KW

N/A

Moisture Removal

L/hr

1.2

background image

15 SERVICE MANUAL FOR CMV

2 . 2 . 1 5 C M V S - 5 0 V 3 A - N 4 6 A

S p e c i f i c a t i o n s

INDOOR UNIT

Model Indoor Unit/Type

CMVS-50V3A-N46A

Installation method

Flare

Power Supply

V/Ph/Hz

220-240/1/50

Fan Type & Quantity

Crossflow×1

H

750

M

550

Airflow Cooling/Heating

L

m

3

/hr

450

Sound Preesure Level Cooling/Heating

L-H

dB(A)

35-43/35-43

Condensate Drain Tube I.D

mm

16

Dimensions

W/H/D

mm

998×320×210

Weight

kg

14

Packaging Dimensions

W/H/D

mm

1085×380×300

IN

D

OOR

Stacking Height

Units

7

Heating Elements

KW

N/A

Moisture Removal

L/hr

1.2

2 . 2 . 1 6 C M V S - 5 0 V 3 A - N 1 7 A

S p e c i f i c a t i o n s

INDOOR UNIT

Model Indoor Unit/Type

CMVS-50V3A-N17A

Installation method

Flare

Power Supply

V/Ph/Hz

220-240/1/50

Fan Type & Quantity

Crossflow×1

H

750

M

550

Airflow Cooling/Heating

L

m

3

/hr

450

Sound Preesure Level Cooling/Heating

L-H

dB(A)

35-43/35-43

Condensate Drain Tube I.D

mm

16

Dimensions

W/H/D

mm

1015×320×204

Weight

kg

14

Packaging Dimensions

W/H/D

mm

1085×380×300

IN

D

OOR

Stacking Height

Units

7

Heating Elements

KW

N/A

Moisture Removal

L/hr

1.2

background image

16 SERVICE MANUAL FOR CMV

2 . 2 . 1 7 C M V - V 2 5 G 3 A / M 8 5 S p e c i f i c a t i o n s

INDOOR UNIT

Model Indoor Unit/Type

CMV-V25G3A/M85

Installation method

Flare

Power Supply

V/Ph/Hz

220-240/1/50

Fan Type & Quantity

Crossflow×1

H

500

M

450

Airflow Cooling/Heating

L

m

3

/hr

360

Sound Preesure Level
Cooling/Heating

L-H

dB(A)

29-39

Condensate Drain Tube I.D

mm

16

Dimensions

W/H/D

mm

800×280×187

Weight

kg

12

Packaging Dimensions

W/H/D

mm

860×350×265

IN

D

OOR

Stacking Height

Units

8

Heating Elements

KW

N/A

Moisture Removal

L/hr

0.6

2 . 2 . 1 8 C M V - V 3 5 G 3 A / M 8 5 S p e c i f i c a t i o n s

INDOOR UNIT

Model Indoor Unit/Type

CMV-V35G3A/M85

Installation method

Flare

Power Supply

V/Ph/Hz

220-240/1/50

Fan Type & Quantity

Crossflow×1

H

550

M

480

Airflow Cooling/Heating

L

m

3

/hr

380

Sound Preesure Level
Cooling/Heating

L-H

dB(A)

29-39

Condensate Drain Tube I.D

mm

16

Dimensions

W/H/D

mm

800×280×187

Weight

kg

12

Packaging Dimensions

W/H/D

mm

860×350×265

IN

D

OOR

Stacking Height

Units

8

Heating Elements

KW

N/A

Moisture Removal

L/hr

0.8

background image

17 SERVICE MANUAL FOR CMV

2 . 2 . 1 9 C M V - V 2 5 G 3 A / A 2 7 S p e c i f i c a t i o n s

INDOOR UNIT

Model Indoor Unit/Type

CMV-V25G3A/A27

Installation method

Flare

Power Supply

V/Ph/Hz

220-240/1/50

Fan Type & Quantity

Crossflow×1

H

500

M

450

Airflow Cooling/Heating

L

m

3

/hr

360

Sound Preesure Level Cooling/Heating

L-H

dB(A)

32-41/32-41

Condensate Drain Tube I.D

mm

16

Dimensions

W/H/D

mm

270×180×790

Weight

kg

12

Packaging Dimensions

W/H/D

mm

875×338×285

IN

D

OOR

Stacking Height

Units

7

Heating Elements

KW

N/A

Moisture Removal

L/hr

0.8

2 . 2 . 2 0 C M V - V 3 5 G 3 A / A 2 7 S p e c i f i c a t i o n s

INDOOR UNIT

Model Indoor Unit/Type

CMV-V35G3A/A27

Installation method

Flare

Power Supply

V/Ph/Hz

220-240/1/50

Fan Type & Quantity

Crossflow×1

H

550

M

450

Airflow Cooling/Heating

L

m

3

/hr

360

Sound Preesure Level Cooling/Heating

L-H

dB(A)

32-41/32-41

Condensate Drain Tube I.D

mm

16

Dimensions

W/H/D

mm

270×180×790

Weight

kg

12

Packaging Dimensions

W/H/D

mm

875×338×285

IN

D

OOR

Stacking Height

Units

7

Heating Elements

KW

N/A

Moisture Removal

L/hr

1

background image

18 SERVICE MANUAL FOR CMV

2 . 2 . 2 1 C M V - V 2 5 G 3 A / A 7 7 S p e c i f i c a t i o n s

INDOOR UNIT

Model Indoor Unit/Type

CMV-V25G3A/A77

Installation method

Flare

Power Supply

V/Ph/Hz

220-240/1/50

Fan Type & Quantity

Crossflow×1

H

500

M

450

Airflow Cooling/Heating

L

m

3

/hr

360

Sound Preesure Level Cooling/Heating

L-H

dB(A)

32-41/32-41

Condensate Drain Tube I.D

mm

16

Dimensions

W/H/D

mm

270×180×790

Weight

kg

12

Packaging Dimensions

W/H/D

mm

875×338×285

IN

D

OOR

Stacking Height

Units

7

Heating Elements

KW

N/A

Moisture Removal

L/hr

0.8

2 . 2 . 2 2 C M V - V 3 5 G 3 A / A 7 7 S p e c i f i c a t i o n s

INDOOR UNIT

Model Indoor Unit/Type

CMV-V35G3A/A27

Installation method

Flare

Power Supply

V/Ph/Hz

220-240/1/50

Fan Type & Quantity

Crossflow×1

H

550

M

450

Airflow Cooling/Heating

L

m

3

/hr

360

Sound Preesure Level Cooling/Heating

L-H

dB(A)

32-41/32-41

Condensate Drain Tube I.D

mm

16

Dimensions

W/H/D

mm

270×180×790

Weight

kg

12

Packaging Dimensions

W/H/D

mm

875×338×285

IN

D

OOR

Stacking Height

Units

7

Heating Elements

KW

N/A

Moisture Removal

L/hr

1

background image

19 SERVICE MANUAL FOR CMV

2 . 2 . 2 3 C M V - V 5 0 G 3 A / H 2 7 S p e c i f i c a t i o n s

INDOOR UNIT

Model Indoor Unit/Type

CMV-V50G3A/H27

Installation method

Flare

Power Supply

V/Ph/Hz

220-240/1/50

Fan Type & Quantity

Crossflow×1

H

750

M

550

Airflow Cooling/Heating

L

m

3

/hr

450

Sound Preesure Level Cooling/Heating

L-H

dB(A)

35-43/35-43

Condensate Drain Tube I.D

mm

16

Dimensions

W/H/D

mm

930×270×180

Weight

kg

14

Packaging Dimensions

W/H/D

mm

1010×360×280

IN

D

OOR

Stacking Height

Units

7

Heating Elements

KW

N/A

Moisture Removal

L/hr

1.2

2 . 2 . 2 3 C M V - V 5 0 G 3 A / H 7 7 S p e c i f i c a t i o n s

INDOOR UNIT

Model Indoor Unit/Type

CMV-V50G3A/H77

Installation method

Flare

Power Supply

V/Ph/Hz

220-240/1/50

Fan Type & Quantity

Crossflow×1

H

750

M

550

Airflow Cooling/Heating

L

m

3

/hr

450

Sound Preesure Level Cooling/Heating

L-H

dB(A)

35-43/35-43

Condensate Drain Tube I.D

mm

16

Dimensions

W/H/D

mm

930×270×180

Weight

kg

14

Packaging Dimensions

W/H/D

mm

1010×360×280

IN

D

OOR

Stacking Height

Units

7

Heating Elements

KW

N/A

Moisture Removal

L/hr

1.2

background image

20 SERVICE MANUAL FOR CMV

2 . 2 . 2 4 C M V - V 5 0 G 3 A / H 4 8 S p e c i f i c a t i o n s

INDOOR UNIT

Model Indoor Unit/Type

CMV-V50G3A/H48

Installation method

Flare

Power Supply

V/Ph/Hz

220-240/1/50

Fan Type & Quantity

Crossflow×1

H

750

M

550

Airflow Cooling/Heating

L

m

3

/hr

450

Sound Preesure Level Cooling/Heating

L-H

dB(A)

35-43/35-43

Condensate Drain Tube I.D

mm

16

Dimensions

W/H/D

mm

930×270×180

Weight

kg

14

Packaging Dimensions

W/H/D

mm

1010×360×280

IN

D

OOR

Stacking Height

Units

7

Heating Elements

KW

N/A

Moisture Removal

L/hr

1.2

2 . 2 . 2 5 C M V - V 5 0 G 3 A / H 6 9 S p e c i f i c a t i o n s

INDOOR UNIT

Model Indoor Unit/Type

CMV-V50G3A/H69

Installation method

Flare

Power Supply

V/Ph/Hz

220-240/1/50

Fan Type & Quantity

Crossflow×1

H

750

M

550

Airflow Cooling/Heating

L

m

3

/hr

450

Sound Preesure Level Cooling/Heating

L-H

dB(A)

35-43/35-43

Condensate Drain Tube I.D

mm

16

Dimensions

W/H/D

mm

930×270×180

Weight

kg

14

Packaging Dimensions

W/H/D

mm

1010×360×280

IN

D

OOR

Stacking Height

Units

7

Heating Elements

KW

N/A

Moisture Removal

L/hr

1.2

background image

21 SERVICE MANUAL FOR CMV

3 . R A T I N G

C O N D I T I O N S

Standard conditions in accordance with ISO 5151, and EN 14511.

Cooling:
Indoor: 27

o

C DB 19

o

C WB

Outdoor: 35

o

C DB 24

o

C WB

Heating:
Indoor: 20

o

C DB 15

o

C WB

Outdoor: 7

o

C DB 6

o

C WB

3 . 1 O p e r a t i n g

L i m i t s

Outdoor

Upper limit (DB)

46

o

C

Cooling

Lower limit (DB)

10

o

C

Upper limit (DB)

24

o

C

Heating

Lower limit (DB)

-15

o

C

2PH 198–264V

Voltage

3PH N/A

background image

22 SERVICE MANUAL FOR CMV

4 . O U T L I N E

D I M E N S I O N S

4.1 outdoor Unit: CMV-V40H13AD

4.2 outdoor Unit: CMV-50V3A-E2

background image

23 SERVICE MANUAL FOR CMV

4.3 outdoor Unit: CMV-V80WC3AQ, CMV-71V3A-T

560

37

8

34

2

84

5

35

1

72

50

956

82

5

50

×3

(=1

50)

50

5 . P E R F O R M A N C E

D A T A

5 . 1 O u t d o o r u n i t s d a t a

5 . 1 . 1

CMV-V40H13AD

C o m b i n a t i o n s ( b a s e d o n s p l i t i n d o o r u n i t s )

Data For Outdoor Unit CMV-V40H13AD Combinations (Based on Split indoor units)

Cooling

Heating

RoomA RoomB

Total

Capacity

Power
Input

RoomA

RoomB

Total

Capacity

Power Input

Indoor Units
Combinations

[W]

[W]

[W]

[W]

[W]

[W]

[W]

[W]

20

2000

*

2000

(1450-3200)

540

(450-1050)

2500

*

2500

(1500-3200)

690

(430-940)

25

2500

*

2500

(1450-3350)

710

(450-1140)

3000

*

3000

(1500-3400)

840

(430-990)

35

3500

*

3500

(1450-4700)

1020

(450-1250)

3500

*

3500

(1450-3800)

950

(450-1100)

20+20

2000

2000

4000

(1450-5200)

1020

(450-1550)

2300

2300

4600

(1500-5050)

1050

(430-1300)

20+25S

2000

2500

4500

(1450-5200)

1250

(450-1570)

2265

2835

5100

(1500-5300)

1250

(430-1320)

25S+25S

2500

2500

5000

(1450-5200)

1470

(450-1610)

2600

2600

5200

(1500-5300)

1270

(430-1350)

25S+35

2100

2950

5050

(1450-5250)

1480

(450-1620)

2200

3100

5300

(1500-5400)

1290

(430-1380)

background image

24 SERVICE MANUAL FOR CMV

5 . 1 . 2

CMV-50V3A-E2

C o m b i n a t i o n s ( b a s e d o n s p l i t i n d o o r u n i t s )

Data For Outdoor Unit CMV-50V3A-E2 Combinations (Based on Split indoor units)

Cooling

Heating

RoomA RoomB

Total

Capacity

Power Input

RoomA

RoomB

Total

Capacity

Power
Input

Indoor Units
Combinations

[W]

[W]

[W]

[W]

[W]

[W]

[W]

[W]

20

2000

*

2000

(1420-2960)

650

(460-950)

2500

*

2500

(1280-3300)

710

(420-980)

25

2600

*

2600

(1420-3700)

660

(460-990)

3200

*

3200

(1280-3700)

880

(420-1020)

35

3500

*

3500

(1420-4350)

1010

(460-1280)

4200

*

4200

(1300-5200)

1160

(435-1420)

20+20

2150

2150

4300

(1600-6150)

1320

(460-2100)

2550

2550

5100

(1300-6850)

1480

(450-2130)

20+25

2050

2550

4600

(1600-6400)

1380

(460-2130)

2450

3050

5500

(1300-7000)

1470

(450-2100)

25+25

2600

2600

5200

(1600-6800)

1400

(460-2250)

3000

3000

6000

(1300-7300)

1600

(450-2200)

20+35

2040

3050

5600

(1600-6850)

1750

(460-2250)

2450

3050

6200

(1300-7300)

1700

(450-2200)

25+35

2450

3450

5900

(1600-6850)

1820

(460-2260)

3100

3450

6550

(1300-7350)

1850

(450-2220)

35+35

3100

3050

6150

(1600-6880)

1890

(460-2270)

3450

3450

6900

(1300-7400)

1890

(450-2220)

5 . 1 . 3 C M V - 7 1 V 3 A - T C o m b i n a t i o n s ( b a s e d o n s p l i t i n d o o r u n i t s )

Data For Outdoor Unit CMV-71V3A-T Combinations

(Based on Split indoor units)

Cooling

Heating

RoomA RoomB

RoomC

Total

Capacity

Power
Input

RoomA

RoomB

RoomC

Total

Capacity

Power
Input

Indoor Units
Combinations

[W]

[W]

[W]

[W]

[W]

[W]

[W]

[W]

[W]

[W]

20

*

*

2000

2000

(1500-2960)

665

(580-950)

*

*

2500

2500

(1700-3300)

720

(540-940)

25

*

*

2500

2500

(1500-3700)

785

(580-1125)

*

*

3000

3000

(1700-3700)

810

(540-1030)

26

*

*

2600

2600

(1500-3700)

785

(580-1125)

*

*

3000

3000

(1700-3700)

810

(540-1030)

35

*

*

3500

3500

(1600-4350)

1070

(580-1330)

*

*

4300

4300

(2000-5200)

1160

(610-1410)

50

*

*

5000

5000

(1900-5930)

1490

(580-1790)

*

*

6000

6000

(2300-6800)

1600

(690-1860)

20+20

*

2000

2000

4000

(1500-5140)

1250

(580-1650)

*

2800

2800

5600

(2100-6800)

1550

(540-1950)

20+26

*

2000

2600

4600

(1500-5630)

1350

(580-1850)

*

2600

3200

5800

(2200-7300)

1600

(540-2050)

20+35

*

1900

3200

5100

(1500-6100)

1550

(580-2010)

*

2600

3500

7100

(2200-7700)

1950

(540-2250)

20+50

*

1860

4640

6500

(1500-8700)

2100

(580-2900)

*

2450

6050

8500

(1700-9300)

2320

(540-2660)

background image

25 SERVICE MANUAL FOR CMV

25+25

*

2520

2520

5040

(1500-6000)

1480

(580-1770)

*

3000

3000

6000

(1700-7700)

1590

(540-2090)

25+35

*

2510

3390

5900

(1500-7000)

1780

(580-2160)

*

3100

4240

7340

(1700-8300)

1990

(540-2270)

25+50

*

2350

4880

7030

(1500-8900)

2150

(580-2960)

*

2900

5800

8700

(1700-9400)

2370

(540-2660)

26+26

*

2520

2520

5040

(1500-6000)

1480

(580-1770)

*

3000

3000

6000

(1700-7700)

1590

(540-2090)

26+35

*

2550

3350

5900

(1500-7000)

1780

(580-2160)

*

3140

4200

7340

(1700-8300)

1990

(540-2270)

26+50

*

2410

4620

7030

(1500-8900)

2150

(580-2960)

*

3000

5700

8700

(1700-9400)

2370

(540-2660)

35+35

*

3450

3450

6900

(1600-8600)

2120

(580-2860)

*

3900

3900

7800

(2000-8800)

2150

(610-2400)

35+50

*

2960

4280

7040

(1600-8900)

2150

(580-2960)

*

3400

5400

8800

(1700-9500)

2400

(540-2670)

20+20+20

2115

2115

2120

6350

(1500-8500)

1980

(580-2900)

2810

2790

2790

8390

(1700-9800)

2330

(540-3010)

20+20+26

2000

2000

2600

6600

(1500-8700)

2050

(580-2900)

2545

2545

3310

8400

(1700-9850)

2320

(540-3010)

20+20+35

1840

1840

3220

6900

(1500-8700)

2100

(580-2900)

2250

2250

3950

8450

(1700-9900)

2330

(540-3000)

20+20+50

1575

1575

3950

7100

(1500-8900)

2210

(580-2950)

1875

1875

4750

8500

(1700-10350)

2360

(540-3000)

20+26+26

1900

2450

2450

6800

(1500-8800)

2090

(580-2920)

2350

3050

3050

8450

(1700-10400)

2300

(540-3000)

20+26+35

1760

2300

3040

7100

(1500-8800)

2200

(580-2930)

2150

2760

3690

8600

(1700-10500)

2350

(540-3000)

20+26+50

1500

1950

3700

7150

(1500-9000)

2210

(580-2980)

1800

2350

4500

8650

(1700-10600)

2380

(540-3010)

20+35+35

1580

2760

2760

7100

(1500-8850)

2210

(580-2940)

1900

3350

3350

8600

(1700-10400)

2380

(540-3000)

20+35+50

1370

2400

3420

7190

(1500-9000)

2220

(580-2980)

1660

2900

4140

8700

(1700-10500)

2390

(540-3020)

25+25+25

2350

2350

2400

7100

(1500-9000)

2200

(580-2980)

2820

2820

2860

8500

(1700-10500)

2330

(540-3000)

25+25+35

2200

2200

2830

7230

(1500-9000)

2250

(580-2970)

2500

2500

3700

8700

(1700-10500)

2380

(540-3000)

25+25+50

1810

1810

3630

7250

(1500-9000)

2260

(580-2990)

2150

2150

4400

8700

(1700-10700)

2400

(540-3010)

25+35+35

1950

2650

2650

7250

(1500-9000)

2260

(580-2970)

2400

3150

3150

8700

(1700-10500)

2380

(540-3000)

25+35+50

1660

2230

3370

7260

(1500-9000)

2280

(580-2990)

2020

2760

4020

8800

(1700-10700)

2410

(540-3020)

26+26+26

2365

2365

2370

7100

(1500-9000)

2200

(580-2980)

2840

2830

2830

8500

(1700-10500)

2330

(540-3000)

26+26+35

2160

2160

2910

7230

(1500-9000)

2250

(580-2970)

2600

2600

3500

8700

(1700-10500)

2380

(540-3000)

26+26+50

1850

1850

3550

7250

(1500-9000)

2260

(580-2990)

2220

2220

4260

8700

(1700-10700)

2400

(540-3010)

26+35+35

1950

2650

2650

7250

(1500-9000)

2260

(580-2970)

2400

3150

3150

8700

(1700-10500)

2380

(540-3000)

26+35+50

1700

2300

3280

7280

(1500-9000)

2270

(580-2990)

2060

2780

3960

8800

(1700-10700)

2410

(540-3020)

35+35+35

2410

2410

2410

7230

(1500-9000)

2270

(580-2980)

2850

2850

2850

8550

(2000-10500)

2340

(610-3000)

background image

26 SERVICE MANUAL FOR CMV

5 . 1 . 4 C M V - V 8 0 W C 3 A Q C o m b i n a t i o n s ( b a s e d o n s p l i t i n d o o r u n i t s )

Data For Outdoor Unit CMV-V80WC3AQ Combinations

(Based on Split indoor units)

Cooling

Heating

RoomA RoomB RoomC RoomD

Total

Capacity

Power
Input

RoomA

RoomB

RoomC RoomD

Total

Capacity

Power
Input

Indoor Units
Combinations

[W]

[W]

[W]

[W]

[W]

[W]

[W]

[W]

[W]

[W]

[W]

[W]

20

*

*

*

2000

2000

(1800-2960)

720

(710-1050)

*

*

*

2800

2800

(2000-3300)

930

(910-1050)

26

*

*

*

2600

2600

(1800-3700)

785

(710-1200)

*

*

*

3200

3200

(2000-3700)

970

(910-1170)

35

*

*

*

3500

3500

(1800-4300)

1050

(710-1400)

*

*

*

4300

4300

(2000-5200)

1210

(910-1630)

50

*

*

*

5000

5000

(1800-5900)

1530

(710-1890)

*

*

*

6000

6000

(2200-6800)

1660

(890-1920)

20+20

*

*

2175

2175

4350

(1800-5800)

1350

(710-1890)

*

*

2850

2850

5700

(2000-6700)

1580

(910-1950)

20+26

*

*

2000

2600

4600

(1800-5800)

1430

(710-1900)

*

*

2520

3280

5800

(2000-7000)

1610

(910-1950)

20+35

*

*

2000

3500

5500

(1800-6300)

1700

(710-2050)

*

*

2220

3880

6100

(2000-8000)

1690

(910-2270)

20+50

*

*

1970

4930

6900

(1800-8500)

2150

(710-2950)

*

*

2370

5930

8300

(2000-8500)

2250

(910-2400)

26+26

*

*

2600

2600

5200

(1800-6000)

1510

(710-1920)

*

*

3000

3000

6000

(2000-7000)

1580

(910-1990)

26+35

*

*

2590

3490

6080

(1800-6800)

1840

(710-2200)

*

*

2680

3600

6280

(2000-8200)

1680

(910-2260)

26+50

*

*

2390

4610

7000

(1800-8600)

2170

(710-3020)

*

*

2900

5590

8490

(2000-8900)

2210

(910-2400)

35+35

*

*

3430

3430

6860

(1800-8450)

2130

(710-2880)

*

*

4040

4040

8080

(2000-8500)

1920

(910-2340)

35+50

*

*

2910

4160

7070

(1800-8700)

2180

(710-3050)

*

*

3570

5110

8680

(2000-8900)

2240

(910-2480)

20+20+20

*

2130

2130

2140

6400

(1800-8600)

2000

(710-3050)

*

2780

2780

2790

8350

(2000-8900)

2300

(910-2600)

20+20+26

*

2000

2000

2600

6600

(1800-8600)

2050

(710-3040)

*

2545

2545

3310

8400

(2000-8900)

2290

(910-2600)

20+20+35

*

1890

1890

3320

7100

(1800-8600)

2200

(710-3050)

*

2255

2255

3940

8450

(2000-8900)

2290

(910-2600)

20+20+50

*

1620

1620

4060

7300

(1800-8900)

2280

(710-3080)

*

1900

1900

4750

8550

(2000-9200)

2280

(910-2650)

20+26+26

*

1960

2545

2545

7050

(1800-8600)

2200

(710-3030)

*

2330

3035

3035

8400

(2000-9000)

2280

(910-2550)

20+26+35

*

1800

2340

3160

7300

(1800-8700)

2270

(710-3040)

*

2110

2745

3695

8550

(2000-9000)

2270

(910-2530)

20+26+50

*

1520

1980

3800

7300

(1800-8900)

2280

(710-3100)

*

1800

2340

4510

8650

(2000-9700)

2250

(910-2650)

20+35+35

*

1620

2840

2840

7300

(1800-8800)

2280

(710-3080)

*

1910

3345

3345

8600

(2000-8900)

2260

(910-2620)

20+35+50

*

1410

2470

3520

7400

(1800-9000)

2300

(710-3090)

*

1660

2900

4140

8700

(2000-9700)

2250

(910-2670)

26+26+26

*

2400

2400

2400

7200

(1800-9000)

2250

(710-3160)

*

2940

2940

2940

8820

(2000-9200)

2250

(850-2580)

26+26+35

*

2200

2200

2970

7370

(1800-9000)

2260

(710-3160)

*

2640

2640

3550

8830

(2000-9300)

2250

(850-2580)

26+26+50

*

1905

1905

3670

7480

(1800-9100)

2300

(710-3180)

*

2260

2260

4350

8870

(2000-9800)

2270

(850-2650)

26+35+35

*

2010

2705

2705

7420

(1800-9000)

2290

(710-3160)

*

2400

3225

3225

8850

(2000-9350)

2260

(850-2610)

26+35+50

*

1840

2480

3540

7860

(1800-9100)

2320

(710-3190)

*

2080

2805

4005

8890

(2000-9800)

2280

(850-2660)

35+35+35

*

2570

2570

2570

7710

(1800-9040)

2300

(710-3200)

*

2960

2960

2970

8890

(2000-10200)

2270

(850-2780)

35+35+50

*

2305

2305

3290

7900

(1800-9100)

2330

(710-3190)

*

2595

2595

3710

8900

(2000-10200)

2280

(850-2780)

20+20+20+20

1920

1920

1920

1920

7680

(1800-9300)

2400

(710-3290)

2300

2300

2300

2300

9200

(2000-10600)

2550

(850-3100)

20+20+20+26

1800

1800

1800

2350

7750

(1800-9300)

2420

(710-3290)

2160

2160

2160

2820

9300

(2000-10700)

2530

(850-3100)

background image

27 SERVICE MANUAL FOR CMV

20+20+20+35

1650

1650

1650

6190

7840

(1800-9300)

2440

(710-3290)

1970

1970

1970

3440

9350

(2000-10700)

2530

(850-3100)

20+20+20+50

1430

1430

1430

3590

7880

(1800-9350)

2460

(710-3300)

1720

1720

1720

4290

9450

(2000-11000)

2520

(850-3050)

20+20+26+26

1700

1700

2215

2215

7830

(1800-9300)

2440

(710-3290)

2075

2075

2700

2700

9550

(2000-11000)

2500

(850-3050)

20+20+26+35

1565

1565

2030

2740

7900

(1800-9300)

2460

(710-3290)

1905

1905

2480

3340

9630

(2000-11000)

2500

(850-3050)

20+20+25+50

1390

1390

1740

3480

8000

(1800-9350)

2490

(710-3300)

1690

1690

2105

4215

9700

(2000-11000)

2490

(850-3050)

20+20+35+35

1450

1450

2550

2550

8000

(1800-9300)

2480

(710-3290)

1760

1760

3080

3080

9680

(2000-11000)

2500

(850-3050)

20+20+35+50

1310

1310

2240

3240

8100

(1800-9400)

2520

(710-3300)

1560

1560

2720

3890

9730

(2000-11000)

2490

(850-3050)

20+26+26+26

1600

2100

2100

2100

7900

(1800-9400)

2460

(710-3290)

1970

2560

2560

2560

9650

(2000-11000)

2490

(850-3050)

20+26+26+35

1480

1935

1935

2600

7950

(1800-9400)

2480

(710-3290)

1810

2350

2350

3170

9680

(2000-11000)

2490

(850-3050)

20+26+26+50

1300

1725

1725

3300

8050

(1800-9400)

2510

(710-3300)

1585

2070

2070

3975

9700

(2000-11000)

2480

(850-3050)

20+26+35+35

1380

1790

2400

2400

7970

(1800-9400)

2490

(710-3290)

1670

2170

2925

2925

9690

(2000-11000)

2470

(850-3050)

20+26+35+50

1230

1600

2150

3080

8060

(1800-9400)

2510

(710-3350)

1480

1925

2590

3705

9700

(2000-11000)

2470

(850-3050)

20+35+35+35

1310

2250

2250

2250

8020

(1800-9400)

2490

(710-3350)

1555

2715

2715

2715

9700

(2000-11000)

2460

(850-3050)

25+25+25+25

2000

2000

2000

2000

8000

(1800-9400)

2450

(710-3350)

2400

2400

2400

2400

9600

(2000-11000)

2400

(910-3050)

25+25+25+35

1870

1870

1870

2490

8100

(1800-9400)

2470

(710-3350)

2195

2195

2195

3065

9650

(2000-11000)

2400

(910-3050)

25+25+25+50

1610

1610

1610

3280

8110

(1800-9400)

2480

(710-3350)

1950

1950

1950

3930

9780

(2000-11000)

2460

(910-3050)

25+25+35+35

1720

1720

2340

2340

8120

(1800-9400)

2460

(710-3350)

2065

2065

2800

2800

9730

(2000-11000)

2440

(910-3050)

25+25+35+50

1520

1520

2040

3020

8100

(1800-9400)

2480

(710-3350)

1800

1800

2430

3750

9780

(2000-11000)

2460

(910-3050)

25+35+35+35

1620

2160

2160

2160

8110

(1800-9400)

2480

(710-3350)

1930

2600

2600

2600

9730

(2000-11000)

2450

(910-3050)

35+35+35+35

2030

2030

2030

2030

8120

(1800-9400)

2490

(710-3350)

2425

2425

2425

2425

9700

(2000-11000)

2470

(910-3050)

5.2 Indoor Units Data

5.2.1 Indoor Units Capacity For 2.5KW

Capacity

Model

CMVS-25V3A-A38A
CMVS-25V3A-A38B
CMVS-25V3A-A48A
CMVS-25V3A-A69A
CMVS-25V3A-A46A
CMV-V25G3A/A67
CMV-V25G3A/A78
CMV-V25G3A/A27

2.5KW

CMV-V25G3A/A77

background image

28 SERVICE MANUAL FOR CMV

5.2.1.1

Cooling Capacity (KW)---Run Model (Unit A,B,C or D),230V,Indoor fan at

high speed

INDOOR ENTERING AIR DB/WB TEMPERATURE [

0

C]

OUTDOOR

ENTERING AIR DB

TEMPERATURE

[

0

C] DATA

22/15

24/17

27/19

29/21

32/23

TC

80 - 110 % of nominal

-10 - 20

SC

80 - 105 % of nominal

(protection range)

PI

25 - 50 % of nominal

TC 2.42 2.57 2.73 2.89 3.05

25

SC 1.72 1.75 1.79 1.82 1.86

PI 0.58 0.59 0.60 0.61 0.62

TC 2.30 2.46 2.62 2.77 2.93

30

SC 1.67 1.71 1.74 1.78 1.81

PI 0.65 0.66 0.67 0.68 0.69

TC 2.18 2.34 2.50 2.66 2.82

35

SC 1.63 1.66 1.70 1.74 1.77

PI 0.71 0.72 0.74 0.75 0.76

TC 2.07 2.23 2.38 2.54 2.70

40

SC 1.59 1.62 1.66 1.69 1.73

PI 0.78 0.79 0.80 0.81 0.82

TC 1.93 2.09 2.24 2.40 2.56

46

SC 1.53 1.57 1.60 1.64 1.67

PI 0.86 0.87 0.88 0.89 0.91

L E G E N D

TC – Total Cooling Capacity, kW
SC – Sensible Capacity, Kw
PI – Power Input, kW
WB – Wet Bulb Temp., (

o

C)

DB – Dry Bulb Temp., (

o

C)

ID – Indoor

OD – Outdoor

background image

29 SERVICE MANUAL FOR CMV

5.2.1.2

Heating Capacity (KW)---Run Model (Unit A,B,C or D),230V,Indoor fan at

high speed

ID COIL ENTERING AIR DB TEMPERATURE [

0

C]

OD COIL

ENTERING

AIR DB/WB

TEM PERATU RE

[

0

C]

DATA 15

20

25

-15/-16

TC

1.92 1.77 1.65

PI 0.49

0.54

0.59

-10/-12

TC 2.13

1.98

1.86

PI

0.59 0.64 0.70

-7/-8

TC 2.28

2.16

2.01

PI

0.67

0.72

0.77

-1/-2

TC 2.37

2.25

2.10

PI

0.71 0.75 0.80

2/1

TC

2.43 2.28 2.16

PI

0.73

0.78

0.83

7/6

TC

3.12 3.00 2.88

PI

0.77 0.82 0.87

10/9

TC

3.30 3.18 3.03

PI

0.82

0.87

0.92

15/12

TC

3.48 3.36 3.21

PI

0.86

0.90

0.96

15-24

TC

85 - 105 % of nominal

(Protection Range)

PI

80 - 120 % of nominal

5.2.1.3 Capacity

Correction

Factors

Cooling Capacity Ratio Vs. Outdoor Temperature

Cooling Capacity Correction Factor

0

0.2

0.4

0.6

0.8

1

1.2

1.4

25

30

35

40

45

Outdoor Temperature (deg C)

Capacity Ratio

32/23
29/27
27/19
24/17
22/15

background image

30 SERVICE MANUAL FOR CMV

Heating Capacity Ratio Vs. Outdoor Temperature

Heating Capacity Correction Factor

0

0.2

0.4

0.6

0.8

1

1.2

1.4

-15

-10

-5

0

5

10

15

20

Outdoor Temperature (deg C)

Capacity Ratio

15
20
25

5.2.2 Indoor Units Capacity For 3.5KW

5.2.2 Indoor

Units

Capac

ity For

3.5KW

Capacity

Model

CMVS-35V3A-A38A
CMVS-35V3A-A38B
CMVS-35V3A-A48A
CMVS-35V3A-A69A
CMVS-35V3A-A46A
CMV-V35G3A/A67
CMV-V35G3A/A78
CMV-V35G3A/A27

3.5KW

CMV-V35G3A/A77

background image

31 SERVICE MANUAL FOR CMV

5.2.2.1

Cooling Capacity (KW)---Run Model (Unit A,B,C or D),230V,Indoor fan at

high speed

INDOOR ENTERING AIR DB/WB TEMPERATURE [

0

C]

OUTDOOR

ENTERING AIR DB

TEMPERATURE

[

0

C] DATA

22/15

24/17

27/19

29/21

32/23

TC

80 - 110 % of nominal

-10 - 20

SC

80 - 105 % of nominal

(protection range)

PI

25 - 50 % of nominal

TC

3.40

3.61

3.82

4.06

4.27

25

SC

3.03

3.09

3.15

3.21

3.27

PI

0.86

0.87

0.89

0.90

0.93

TC

3.22

3.43

3.68

3.89

4.10

30

SC

2.94

3.00

3.09

3.15

3.21

PI

0.96

0.97

0.99

1.00

1.02

TC

3.05

3.29

3.50

3.71

3.96

35

SC

2.88

2.94

3.00

3.06

3.12

PI

1.06

1.08

1.09

1.11

1.12

TC

2.91

3.12

3.33

3.57

3.78

40

SC

2.79

2.85

2.91

3.00

3.06

PI

1.16

1.18

1.19

1.21

1.22

TC

2.70

2.91

3.15

3.36

3.57

46

SC

2.70

2.76

2.82

2.88

2.97

PI

1.28

1.30

1.31

1.33

1.34

5.2.2.2

Heating Capacity (KW)---Run Model (Unit A,B,C or D),230V,Indoor fan at

high speed

ID COIL ENTERING AIR DB TEMPERATURE [

0

C]

OD COIL

ENTERING

AIR DB/WB

TEM PERATU RE

[

0

C]

DATA 15

20

25

-15/-16

TC

2.56

2.36

2.20

PI

0.67

0.73

0.80

-10/-12

TC

2.84

2.64

2.48

PI

0.80

0.87

0.94

-7/-8

TC

3.04

2.88

2.68

PI

0.91

0.98

1.04

-1/-2

TC

3.16

3.00

2.80

PI

0.95

1.02

1.09

2/1

TC

3.24

3.04

2.88

PI

0.99

1.05

1.12

7/6

TC

4.16

4.00

3.84

PI

1.04

1.11

1.18

10/9

TC

4.40

4.24

4.04

PI

1.11

1.18

1.24

15/12

TC

4.64

4.48

4.28

PI

1.17

1.23

1.30

1524

TC

85 - 105 % of nominal

(Protection Range)

PI

80 - 120 % of nominal

background image

32 SERVICE MANUAL FOR CMV

5.2.2.3 Capacity

Correction

Factors

Cooling Capacity Ratio Vs. Outdoor Temperature

Cooling Capacity Correction Factor

0

0.2

0.4

0.6

0.8

1

1.2

1.4

25

30

35

40

45

Outdoor Temperature (deg C)

Capacity Ratio

32/23
29/27
27/19
24/17
22/15

Heating Capacity Ratio Vs. Outdoor Temperature

Heating Capacity Correction Factor

0

0.2

0.4

0.6

0.8

1

1.2

1.4

-15

-10

-5

0

5

10

15

20

Outdoor Temperature (deg C)

Capacity Ratio

15
20
25

5.2.3 Indoor Units Capacity For 5.0KW

Capacity

Model

CMV-V50G3A/H38A

CMVS-50V3A-N46A

CMVS-50V3A-N17A

CMV-V50G3A/H27

CMV-V50G3A/H69

CMV-V50G3A/H48

5.0KW

CMV-V50G3A/H77

background image

33 SERVICE MANUAL FOR CMV

5.2.3.1 Cooling Capacity (KW)---Run Model (Unit A,B,C or D),230V,Indoor fan at high

speed

INDOOR ENTERING AIR DB/WB TEMPERATURE [

0

C]

OUTDOOR

ENTERING AIR DB

TEMPERATURE

[

0

C] DATA

22/15

24/17

27/19

29/21

32/23

TC

80 - 110 % of nominal

-10 - 20

SC

80 - 105 % of nominal

(protection range)

PI

25 - 50 % of nominal

TC

4.85

5.15

5.45

5.80

6.10

25

SC

4.55

4.64

4.73

4.82

4.91

PI

1.23

1.25

1.28

1.29

1.33

TC

4.60

4.90

5.25

5.55

5.85

30

SC

4.41

4.50

4.64

4.73

4.82

PI

1.37

1.39

1.42

1.44

1.47

TC

4.35

4.70

5.00

5.30

5.65

35

SC

4.32

4.41

4.50

4.59

4.68

PI

1.51

1.54

1.56

1.59

1.61

TC

4.15

4.45

4.75

5.10

5.40

40

SC

4.19

4.28

4.37

4.50

4.59

PI

1.65

1.68

1.70

1.73

1.75

TC

3.85

4.15

4.50

4.80

5.10

46

SC

4.05

4.14

4.23

4.32

4.46

PI

1.83

1.86

1.87

1.90

1.92

5.2.3.2 Heating Capacity (KW)---Run Model (Unit A,B,C or D),230V,Indoor fan at

high speed

ID COIL ENTERING AIR DB TEMPERATURE [

0

C]

OD COIL

ENTERING

AIR DB/WB

TEM PERATU RE

[

0

C]

DATA 15

20

25

-15/-16

TC

3.71

3.42

3.19

PI

0.97

1.06

1.16

-10/-12

TC

4.12

3.83

3.60

PI

1.16

1.26

1.37

-7/-8

TC

4.41

4.18

3.89

PI

1.32

1.42

1.51

-1/-2

TC

4.58

4.35

4.06

PI

1.38

1.48

1.58

2/1

TC

4.70

4.41

4.18

PI

1.43

1.53

1.63

7/6

TC

6.03

5.80

5.57

PI

1.51

1.61

1.71

10/9

TC

6.38

6.15

5.86

PI

1.61

1.71

1.80

15/12

TC

6.73

6.50

6.21

PI

1.69

1.79

1.88

15-24

TC

85 - 105 % of nominal

(Protection Range)

PI

80 - 120 % of nominal

background image

34 SERVICE MANUAL FOR CMV

5.2.3.3 Capacity

Correction

Factors

Cooling Capacity Ratio Vs. Outdoor Temperature

Cooling Capacity Correction Factor

0

0.2

0.4

0.6

0.8

1

1.2

1.4

25

30

35

40

45

Outdoor Temperature (deg C)

Capacity Ratio

32/23
29/27
27/19
24/17
22/15

Heating Capacity Ratio Vs. Outdoor Temperature

Heating Capacity Correction Factor

0

0.2

0.4

0.6

0.8

1

1.2

1.4

-15

-10

-5

0

5

10

15

20

Outdoor Temperature (deg C)

Capacity Ratio

15
20
25

5.2.4

Indoor Units Capacity For 2.0KW

Capacity

Model

2.0KW

CMV-V20G3A/G38A

background image

35 SERVICE MANUAL FOR CMV

5.2.4.1

Cooling Capacity (KW)---Run Model (Unit A,B,C or D),230V,Indoor fan at

high speed

INDOOR ENTERING AIR DB/WB TEMPERATURE [

0

C]

OUTDOOR

ENTERING AIR DB

TEMPERATURE

[

0

C] DATA

22/15

24/17

27/19

29/21

32/23

TC

80 - 110 % of nominal

SC

80 - 105 % of nominal

-10 - 20

(protection range)

PI

25 - 50 % of nominal

TC

1.94

2.06

2.18

2.32

2.44

SC

1.72

1.75

1.79

1.82

1.85

25

PI

0.49

0.50

0.51

0.51

0.53

TC

1.84

1.96

2.10

2.22

2.34

SC

1.67

1.70

1.75

1.79

1.82

30

PI

0.55

0.55

0.56

0.57

0.58

TC

1.74

1.88

2.00

2.12

2.26

SC

1.63

1.67

1.70

1.73

1.77

35

PI

0.60

0.61

0.62

0.63

0.64

TC

1.66

1.78

1.90

2.04

2.16

SC

1.58

1.62

1.65

1.70

1.73

40

PI

0.66

0.67

0.68

0.69

0.69

TC

1.54

1.66

1.80

1.92

2.04

SC

1.53

1.56

1.60

1.63

1.68

46

PI

0.73

0.74

0.74

0.76

0.76

5.2.4.2

Heating Capacity (KW)---Run Model (Unit A,B,C or D),230V,Indoor fan at

high speed

ID COIL ENTERING AIR DB TEMPERATURE [

0

C]

OD COIL

ENTERING

AIR DB/WB

TEM PERATU RE

[

0

C]

DATA 15

20

25

-15/-16

TC

1.54

1.42

1.32

PI

0.40

0.44

0.48

-10/-12

TC

1.70

1.58

1.49

PI

0.48

0.52

0.57

-7/-8

TC

1.82

1.73

1.61

PI

0.55

0.59

0.63

-1/-2

TC

1.90

1.80

1.68

PI

0.58

0.62

0.66

2/1

TC

1.94

1.82

1.73

PI

0.60

0.64

0.68

7/6

TC

2.50

2.40

2.30

PI

0.63

0.67

0.71

10/9

TC

2.64

2.54

2.42

PI

0.67

0.71

0.75

15/12

TC

2.78

2.69

2.57

PI

0.70

0.74

0.78

1524

TC

85 - 105 % of nominal

(Protection Range)

PI

80 - 120 % of nominal

background image

36 SERVICE MANUAL FOR CMV

5.2.4.3 Capacity

Correction

Factors

Cooling Capacity Ratio Vs. Outdoor Temperature

Cooling Capacity Correction Factor

0

0.2

0.4

0.6

0.8

1

1.2

1.4

25

30

35

40

45

Outdoor Temperature (deg C)

Capacity Ratio

32/23
29/27
27/19
24/17
22/15

Heating Capacity Ratio Vs. Outdoor Temperature

Heating Capacity Correction Factor

0

0.2

0.4

0.6

0.8

1

1.2

1.4

-15

-10

-5

0

5

10

15

20

Outdoor Temperature (deg C)

Capacity Ratio

15
20
25

background image

37 SERVICE MANUAL FOR CMV

5.3 Capacity Correction Factor Due to Tubing Length (One Way)

5.3.1 Indoor units Model

CMVS-25V3A-A38A

CMVS-35V3A-A38A

CMV-V20G3A/G38A

CMV-V50G3A/H38A

CMVS-25V3A-A38B

CMVS-35V3A-A38B

CMVS-25V3A-A48A

CMVS-35V3A-A48A

CMVS-25V3A-A69A

CMVS-35V3A-A69A

CMVS-25V3A-A46A

CMVS-35V3A-A46A

CMV-V25G3A/A27

CMV-V35G3A/A27

CMV-V25G3A/A77

CMV-V35G3A/A77

CMV-V25G3A/M85

CMV-V35G3A/M85

CMVS-50V3A-N46A

CMVS-50V3A-N17A

CMV-V25G3A/A67

CMV-V35G3A/A67

CMV-V25G3A/A78

CMV-V35G3A/A78

CMV-V50G3A/H27

CMV-V50G3A/H69

CMV-V50G3A/H48

CMV-V50G3A/H77

5.3.1.1 Cooling

5.3.1.2 Heating

background image

38 SERVICE MANUAL FOR CMV

6. Pressure Curve

6.1 Model

CMV-50V3A-E2

CMV-71V3A-T CMV-V80WC3AQ

CMV-V40H13AD

6.1.1 Cooling--------------Test Model

6.1.2 Heating-----------Test Model

background image

39 SERVICE MANUAL FOR CMV

7 . E L E C T R I C A L

D A T A

Model

CMV-50V3A-E2

Power Supply

1 PH, 220-240 VAC, 50Hz

Connected to

Outdoor

Maximum Current

11 A

Inrush Current

35A

Starting Current

1A

Circuit breaker

20A

Power supply wiring - No. x cross section

1 X 3 X 2.5 mm

2

Interconnecting cable - No. x cross section

2 X 4 X 1 mm

2

Model

CMV-71V3A-T

Power Supply

1 PH, 220-240 VAC, 50Hz

Connected to

Outdoor

Maximum Current

16A

Inrush Current

35A

Starting Current

2A

Circuit breaker

20A

Power supply wiring - No. x cross section

1 X 3 X 2.5 mm

2

Interconnecting cable - No. x cross section

3X 4 X 1 mm

2

Model

CMV-V80WC3AQ

Power Supply

1 PH, 220-240 VAC, 50Hz

Connected to

Outdoor

Maximum Current

16A

Inrush Current

35A

Starting Current

2A

Circuit breaker

20A

Power supply wiring - No. x cross section

1 X 3 X 2.5 mm

2

Interconnecting cable - No. x cross section

3X 4 X 1 mm

2

Model

CMV-V40H13AD

Power Supply

1 PH, 220-240 VAC, 50Hz

Connected to

Outdoor

Maximum Current

8 A

Inrush Current

35A

Starting Current

1A

Circuit breaker

20A

Power supply wiring - No. x cross section

1 X 3 X1.5 mm

2

Interconnecting cable - No. x cross section

2 X 4 X 1 mm

2


Note:

Inrush current is the current when power is up. (charging the DC capacitors at outdoor unit
controller).
Starting current is the current when starting the compressor
NOTE

Power wiring cord should comply with local lows and electrical regulations
requirements.

background image

40 SERVICE MANUAL FOR CMV

8 . W I R I N G

D I A G R A M S

8 . 1 C M V - 5 0 V 3 A - E 2

C M V - V 4 0 H 1 3 A D

CN13

CN12

CN1

CN6

SW

SC
N

2

.5

-2

P

C

N

15

V
H

3

.9

6

-4P

CN7

CN8

WH
RD
RD

COM

953-1A-12DB

NO

CN5

P

U

V

W

N

BR

BK
BL

CN9

RD

BR
BK

RD

OR

YL

BK

YL

OR

RD

BR

RD

WH

IA

1

IA

2

IA

3

IA

4

CN1

BK

WH

To compressor

temperature protector

RD

WH

EARTH

AC-N

AC-L

WB1021B8004

MBZ102B120

3

VB109B3118

BL

RD

AC-L

AC-N

L

2

N

WH
RD

ZB102B9108

COMPRESSOR

BL

RD

N

N

A

S

A

L

B

N

B

S

B

L

A

BR

BL

BK

HI

N

ME

D
LOW

F

o

u

r-p
o

sitio
n

Va
lv

e

Expansion Valve:B Expansion Valve:A

1

2

1

5

L

1

p

AC-N

AC-L

AC-L1

AC-N1

AC-N1

AC-N

AC-L

BK

BK

BK

WH

CN10

L

3
2

BK

WH

1

BR

BR
BK

WH

P

N

BK

UF-1330A

Y/G

BL

RD

RD

BL

HT225-15-L8-H2

CN1

SB
SA

AC-L

AC-N

reactor

AC-L1

T3

T1

T2

T4

simulant quantity input:

IA4: inspiration temperature

IA3:condensator midpiont

temperature

IA2:outside temperature

IA1:exhaust temperature

others:

Y/G

Y/G

WH

GR

RD

RD

GR

ZB102B9108:PFC board
WB1021B8004:filter board

VB109B3118:IPM board

MBZ102B1203:mainboard

HT225-15-L8-H2:filter

WIRE COLOUR:
BL(BLUE),BK(BLACK),
BR(BROWN),RD(RED),
GR(GREEN),YL(YELLOW),
Y/G(YELLOW/GREEN),
WH(WHITE),OR(ORANGE)

YL

BK

BL

WH

8 . 2 C M V - V 8 0 W C 3 A

W i r i n g D i a g r a m

background image

41 SERVICE MANUAL FOR CMV

8 . 3 C M V - 7 1 V 3 A - T

W i r i n g D i a g r a m


8 . 4 C M V - 5 0 V 3 A - E 2 C M V - V 4 0 H 1 3 A D

I n d o o r - O u t d o o r W i r i n g D i a g r a m

background image

42 SERVICE MANUAL FOR CMV


8 . 5 C M V - 7 1 V 3 A - T I n d o o r - O u t d o o r W i r i n g D i a g r a m

8 . 6 C M V - V 8 0 W C 3 A Q I n d o o r - O u t d o o r W i r i n g D i a g r a m


























background image

43 SERVICE MANUAL FOR CMV

9. REFRIGERATION

DIAGRAMS


9 . 1 C M V - 5 0 V 3 A - E 2 R e f r i g e r a t i o n D i a g r a m






















9 . 2 C M V - 7 1 V 3 A - T R e f r i g e r a t i o n D i a g r a m




























background image

44 SERVICE MANUAL FOR CMV

9 . 3 C M V - V 8 0 W C 3 A Q R e f r i g e r a t i o n D i a g r a m


























9 . 4 C M V - V 4 0 H 1 3 A D R e f r i g e r a t i o n D i a g r a m

background image

45 SERVICE MANUAL FOR CMV

1 0 . T U B I N G C O N N E C T I O N S
























When the outdoor unit is installed above the indoor unit an oil trap is required every 5m along the suction line at
the lowest point of the riser. Incase the indoor unit is installed above the outdoor, no trap is required












T U B E ( I n c h )

T O R Q U E ( N m )

¼ ” ~ ” ½ ” ~ ” ¾ ”

F l a r e N u t s

11-13

40-45

60-65 70-75

80-85

V a l v e C a p

13-20

13-20

18-25 18-25

40-50

Service Port Cap

11-13 11-13 11-13 11-13 11-13

1.

Valve Protection Cap-end

2.

Refrigerant Valve Port (use Allen wrench to open/close)

3.

Valve Protection Cap

4. Refrigerant

Valve

5.

Service Port Cap

6. Flare

Nut

7.

Unit Back Side

8. Copper

Tube

background image

46 SERVICE MANUAL FOR CMV

1 1 . C O N T R O L S Y S T E M

Function of Inverter indoor unit

一、summary

1. This control is use for DC Multi-Spilt air conditioners.
2. Power of indoor unit supply is 220-240V/50Hz, voltage range is 170V~270V.
3. Control precision of indoor temperature is ±1℃.
4. Indoor fan motor is PG motor.
5. Control accord with :

GB5956-91《safe requirement of air conditioner》
GB7725-2004《air conditioner》;GB3797-87《control equipment of electrical

equipment》

Vibrancy test:frequency 50Hz,acceleration 2.5g
PCB ought to accord with GB4588.1 and GB4588.2
Electromagnetism compatibility ought to accord with relate standard of nation.

二.Base parameter

1. Use condition:ambient temperature -15℃~85℃, relative humidity =30-95%.
2. Receive distance of remote:<10m
3. Angle of remote:<120 degree
4. Control precision of temperature: ±1℃
5. Speed precision of indoor fan motor: ±10RPM
6. Time precision: <0.1%

三.Major function of control

1. Remote

Turn on/off
Mode select

auto
cooling
dehumidify
heating

ventilation

Indoor fan speed select

manual mode: high, middle, low speed
auto mode: accord difference of indoor room temp. and set temp. automatic select.

Temperature setting

Cooling: 16℃――32℃, default is 25℃
Heating : 16℃――32℃, default is 25℃
Dehumidify: default is 25℃ and it can’t adjust.
Auto: default is 25℃ and it can’t adjust.
Ventilation: 16℃――32℃, default is 25℃

Sleeping

It can set or cancel 24HR sleep .

Timer on or timer off

Timer can set 24HR on or off.

background image

47 SERVICE MANUAL FOR CMV

Air flower control.
Turbo running
Hold key

2. Main PCB board

five running modes

Auto, cooling, heating, dehumidify, ventilation.

Timer function

Indoor temperature detect.
Indoor coil temperature detect.

Indoor fan speed control

cooling: turbo/high speed/middle speed/low speed/ lower speed
heating: turbo/high speed/middle speed/low speed/ lower speed

Indicate lamp

green—running indicate
yellow—timer indicate
red—turbo running
green—economic running

Indoor temperature control
Coil pipe of indoor unit overheat protection
Coil pipe of indoor unit anti frost protection
Sleep
Swing
Anti cold air in heating mode
Indoor fan motor protection

Fault display

PG motor speed:
5.0KW:

mode

higher

high

middle

low

lower

Cooling

speed

1350

1250

950

850

750

Heating

speed

1350

1250

950

850

750


3.5KW:

mode

higher

high

middle

low

lower

Cooling

speed

1350

1250

950

850

750

Heating

speed

1350

1250

950

850

750

2.5KW

mode

higher

high

middle

low

lower

Cooling

speed

1250

1150

950

850

750

Heating

speed

1250

1150

950

850

750

background image

48 SERVICE MANUAL FOR CMV

2.0KW:

mode

higher

high

middle

low

lower

Cooling

speed

1250

1150

950

850

750

Heating

speed

1250

1150

950

850

750




四、operating mode

Air conditioner have four operating mode: auto, cooling, dehumidify, heating.
1.Cooling(ΔT=Troom temp.-Tset temp.)

range of set temp. 16℃~32℃;
compressor running as below figure:

compressor

on

CONT 5 MIN
off

-1ºC +1ºC ΔT

It require outdoor unit to reduce power if indoor room temp. continuous less than

set temp. for 5 minutes.

Air blow function:indoor blower fan continuous running 20 seconds at low speed

after air conditioner turn off in cooling mode. if the flap is swing, shutdown the
flap after turn off indoor blower fan.

Indoor blower fan can select one of four speed.

Fan speed is determined by the difference of room temp. and set temp. in auto wind.

speed

high
middle

low

1ºC 3ºC 5ºC ΔT

It have anti freeze protection of indoor coil ,fan motor fault protection, sensor

fault protection, unit abnormal protection in cooling mode.

2.Dehumidify:(ΔT=Troom temp.-Tset temp.)

range of set temp.: default is 25℃ and it can’t change.
The indoor blower fan is running at low speed for thirty seconds after air

conditioner shutdown in dehumidify mode.

The indoor blower fan is running at low speed and it can’t change.
Air conditioner haven’t turbo and economic function in dehumidify mode.

Flap position: flap at 85 degree position and it can’t change.

It require indoor unit to reduce power if indoor room temp. continuous less than

or equal to 15 degree for 5 minutes, when room temp. is more than or equal to 17
degree, it add the power of indoor unit.

3.Heating(ΔT=Troom temp.-Tset temp.)

Range of set temp. 16℃~32℃;
Compressor running as below figure.



background image

49 SERVICE MANUAL FOR CMV


compressor

on

CONT 5 MIN
off

-4℃

-2℃

ΔT

It require outdoor unit to reduce power if indoor room temp. continuous more than

set temp. for 5 minutes.

Indoor blower fan continuous running for 30 seconds at current speed after indoor

unit reduce power.

Indoor blower fan can select one of four speed.

Fan speed is determined by the difference of room temp. and set temp. in auto

wind.(but anti cold wind is prior)

speed

high
middle

low

0ºC 2ºC 3ºC 5ºC ΔT

Anti cold wind:

When air conditioner first power on or change mode, indoor blower fan didn’t running. When

the coil pipe temp. of indoor unit is more than 30℃,start turnning on indoor blower
fan(lower speed).if the coil pipe temp. of indoor unit drop to less than or equal
to 25℃,it shutdown indoor blower fan.

Heat wind control:

If coil pipe temp. of indoor unit is more than or equal to 32℃, indoor blower fan is

running at set speed.

If coil pipe temp. of indoor unit is less than 32℃, indoor blower fan is running as below

figure.

speed

set speed
lower

turn off

25℃ 30℃ 32℃ coil pipe temp.

Note:①When Tp≤30℃,flap is open at 85°and is running at lower speed, when Tp

≥32℃, it is running at set speed and flap revert to prior state.

②If Tp≤25℃,turn off indoor blower fan.

Defrost control

Indoor blower fan turn off when it enter defrost.

Clear quantity of heat

Turn off air conditioner in heating mode, if the coil pipe temp. of indoor unit

is more than 40℃, indoor blower fan is running at low speed. If the coil pipe
temp. of indoor unit is less than or equal to 40℃ or turn off air conditioner
over 2 minutes, It shutdown indoor blower fan.

4. Auto mode

set temp. is 25℃ and it can’t change;

Press emergency key in waiting state or select auto mode by remote, air

conditioner enter auto mode and set temp. is 25℃.

Indoor blower fan is running for 20 seconds at lower speed after select auto

background image

50 SERVICE MANUAL FOR CMV

mode, the running lamp is light, it select correspond running mode accord to room

temp.:

room temp. >26℃, select cooling mode.
room temp. <21℃, select heating mode.
21ºC≤room temp.≤26ºC,select ventilation mode.

When the running mode has confirmed, it can’t change, if it reenter auto mode,
it select running mode again accord to room temp..

When the mode of auto select is clash with other indoor unit running mode:

If it auto select is cooling mode and other indoor unit is running heating mode, then it select

ventilation mode.

If it auto select is heating mode, but other indoor unit is running cooling mode, display error of

mode clash.

if it select is ventilation mode, then it running is ventilation.

5.Ventilation

1) Range of set temp.:16℃-32℃.

2) Indoor blower fan is operate same as cooling mode.
3) Flap is operate same as cooling mode.

4) Indoor unit no power require in ventilation mode.


6 Timer and sleep

timer

Remote can set 1-24 hours timer on or timer off.
Air conditioner is running .

If set timer off, air conditioner is continuous running and display timer time, when timer time is
end, it shutdown air conditioner.

air conditioner is shutdown .

If set timer on, air conditioner at waiting state, it display timer time. when timer time is end, it
turn on air conditioner.

when it set timer , the timer lamp is light and display set temp.

sleep

If set sleep, the sleep lamp is light, set temp. and fan speed can be adjust.
Timer and sleep can set together, which time is end then perform this function.

7. Air flow control

Define:flap full open angle is 0°, and full close angle is 125°。

Power on, flap run to full close position.

Full open

Full close

Fixed

background image

51 SERVICE MANUAL FOR CMV

Turn off air conditioner, flap run to full close position.
Turn on air conditioner, flap first run to full open position, then run to correspond position.
Fixed wind:

If turn on air conditioner and set fixed wind at first power on, flap first run to full open

position then stop at 40°position.

If change to fixed wind from swing wind or natural wind, the flap stop at current position

and store the position.

Swing wind:

Flap start position is 20°.
Flap is running between 20°and 85°.

Natural wind is swing two cycle and stop 15 seconds, flap is stop at current

position at that moment.

Flap stop at 85°at anti cold wind or defrost procedure in heating mode.
Flap stop at 85°in first 20 seconds of auto mode.
Flap is drive by step motor.

8. Turbo function

Turbo is use in cooling /heating/ventilation mode, the indoor blower fan is running

at super speed.

(1) enter condition: press turbo key of remote.

(2)end condition:

① running time more than or equal to 15 minutes.
② press turbo key of remote again.

(3) all restrict and protect condition are active in turbo running.
(4) return to prior state after end turbo running.

五、Protection

1. Prevent frost of indoor coil pipe (cooling and dehumidify mode)

When the temp. of middle coil pipe is less than or equal to 0℃, indoor blower

fan is running at high speed, if the temp. less than or equal to -1℃ for 5 minutes,
it turn off compressor, when the temp. more than or equal to 7℃, it exit
protection.

2. Overheat of indoor coil pipe(heating mode)

When the temp. of middle coil pipe more than or equal to 57℃, indoor blower fan

is running at high speed, if the temp. more than or equal to 65℃ , it turn off
outdoor unit, when the temp. less than or equal to 54℃, it exit protection.

3. Indoor fan motor fault(only PG motor)

If no feedback signal continuous 30 seconds during PG motor running, it turn off

air conditioner and display fan motor error.

4. Communicate fault

If it can’t receive correct signals after air conditioner has run for 60 seconds,

it turn off air conditioner and display communicate error.

5.Indoor sensor fault
When indoor sensor cut off or short, it shutdown air conditioner and display sensor

error.

6. When outdoor unit is fault, indoor unit only display fault.

六、Other function

Emergency key

Press emergency key after power on, air conditioner select auto mode, auto fan speed, natural wind,

it set temp. is 25℃. If press emergency key again, air conditioner is shutdown.

background image

52 SERVICE MANUAL FOR CMV

七、Sound indication

1. The buzzer will sound when air conditioner turn on , turn off, power on or receive remote signal.

八、Display

1.After turn on air conditioner, mode clash display

d1

and timer lamp flash (light

one second, extinguish one second), defrost display

dF

, the running lamp flash (light

one second, extinguish one second)indicate anti cold wind ,when air conditioner is
normal running , the running lamp is light.

2.Set timer or sleep , the yellow lamp is light.
3.Outdoor unit and indoor unit fault display:

Fault display of indoor unit:

fault

display

Communicate fault

F1

Fan motor fault

F4

Room temp. sensor fault

F2

Temp. sensor of coil pipe outlet fault

F3

Temp. sensor of coil pipe entrance

fault

F3

Temp. sensor of coil pipe middle

fault

F3

Fault display of outdoor unit:

fault

display

Transducer module protection

P2

Over current

P3

Discharge temperature of

compressor overheat, ambient

temperature overheat

P4

DC voltage of outdoor unit abnormal

P7

Leakage or reverse valve fault

P8

Outdoor sensor fault

F6

Compressor drive fault

FC

Function of Dual DC Inverter Type

. System Frame Drawing

R

everse Valve(Current in cooling condition

Condenser of Outdoor Unit

Temperature of the Middle of Outdoor Coils

Temperature of Exhaust

Expansion Valve 1 Expansion Valve 2

Temperature of suction

M M

Compressor

Liquid Tank

T11 T12 T13

Evaporator 1 of Indoor Unit

Ambient Temperature of Indoor 1

Ambient Temperature of Outdoor T21 T22 T23
Evaporator 2 of Indoor Unit

Ambient Temperature of Indoor 2

Diagram 1

background image

53 SERVICE MANUAL FOR CMV

二.Major Performance Index

a) Voltage of Power Supply: AC220V ±15%;
b) Power of Controller: ≤15W;
c) Output of Three-phase Frequency Conversion:

Wire Voltage: 70V∽180V; Power: ≤5KW; Frequency: 10Hz∽120Hz;

d) Precision of Temperature Control:±1℃;
e) Applicable Environment:

Temperature:-20∽55℃,Relative Humidity: ≤90%RH (No dew);

f) Conservation Environment:

Temperature:-25∽70℃,Relative Humidity: ≤95%RH (No dew);

g) Executive Standard: GB/T7725-2004 & GB4706.32-2000.


三.Input & Output of Outdoor Controller

1.

Outputs of one three-phase Frequency Conversion, two relays, one indicator led and one

communication signal:
1) Controlling the three-phase output of compressor
2) Controlling the output of outdoor motor
3) Controlling the output of 4-way valve
4) Controlling the output of communication signals of indoor unit
5) Controlling the output of expansion valve

2. Inputs of five analogue inputs (the temperature measuring points distributing as Diagram 1, all

the analogues go through digital filter for disposal), and two switch signals and two
communication signals:

a) Signal input of outdoor ambient temperature
b) Signal input of median temperature of outdoor coil
c) Signal input of discharge temperature of compressor
d) Signal input of suction temperature of compressor
e) Signal input of power supply voltage
f) over-heat protection signal of compressor
g) communication signal of indoor unit 1
h) communication signal of indoor unit 2
i) protection signal of outdoor IPM module

. Operation in Cooling Mode

Control of Expansion Valve in Cooling Mode

1. Reset of Expansion Valve

In the first time ,the expansion valves in all channels shall be shut down 600 steps, then the

expansion valve corresponding to the indoor unit in normal communications with the outdoor unit
shall be opened to standby mode steps. If accomplished, the outdoor unit shall be on standby mode,
until the turn-on the indoor unit.

2. Adjustment of Expansion Valve

1) Setting of Basic Step

After the confirmation of the turn-on order of cooling mode, the expansion valve of the
relevant indoor unit shall be set to the basic step and the other to zero step.

2) Adjustment of Expansion Valve according to the difference in temperature between the inlet

and outlet of evaporator

background image

54 SERVICE MANUAL FOR CMV

During the first ten minutes of cooling mode, the expansion valve of the indoor unit at the
request of cooling shall be set to the basic step. Ten minutes later, the expansion valve step and
its adjust cycle shall be adjusted according to the difference in temperature between the inlet
and outlet of evaporator.

Control of compressor’s frequency:

1.Range of compressor’s frequency:Fmin~Fmax (Fmin:the lowest frequency, Fmax:the highest

frequency)

2.Frequency decrease protection of compressor: frequency decrease protection is

prior during frequency adjustment of compressor (Frequency decrease protection
have: high temperature of compressor discharge, high temperature of outdoor coil
pipe, high temperature of indoor coil pipe, low temperature of compressor suction,
over current)

Control of fan motor in cooling mode:
1.The fan motor of outdoor unit is ahead run 20 seconds before compressor turn on.;
2.After compressor turn off, the fan motor of outdoor unit delay 30 seconds.
3. The fan motor speed of outdoor unit as below table in normal running, it has 20 seconds delay

after speed change.

Speed table of outdoor fan motor

indoor unit

capacity

outdoor ambient

<2hp

2hp

3hp

cooling Speed

grade

T<19℃

low low

middle

19℃≤T<27℃

low middle high

T≥27℃

middle high high






compressor

outdoor FM

20s 30s 30s

figure 3

Operation in Dehumidify Mode

Dehumidify mode is same as cooling mode.

Operation in heating Mode

Adjustment of Expansion Valve:
1.Reset of Expansion Valve

In the first time,the expansion valves in two channels shall be shut down 600 steps, then the

expansion valve corresponding to the indoor unit in normal communications with the outdoor unit

background image

55 SERVICE MANUAL FOR CMV

shall be opened to standby mode steps. If accomplished, the outdoor unit shall be on standby mode,
until the turn-on the indoor unit.
2.Adjustment of Expansion Valve

1) Setting of Basic Step

After the confirmation of the turn-on order in heating mode, the expansion valve of the
relevant indoor unit shall be set to the basic step.

2) Adjustment of Expansion Valve according to the difference in temperature between the inlet

and outlet of evaporator

During the first ten minutes of heating mode, the expansion valve of the indoor unit shall be
set to the basic step and can’t adjust. Ten minutes later, the expansion valve step and its adjust
cycle shall be adjusted according to the difference in temperature between the inlet and outlet
of evaporator.

Control of compressor’s frequency

Range of compressor’s frequency:Fmin~Fmax (Fmin:the lowest frequency, Fmax:the highest
frequency)

Control of fan motor in heating mode:(figure 5)

1. The fan motor of outdoor unit is ahead run 20 seconds before compressor turn on.
2. After compressor turn off, the fan motor of outdoor unit delay 30 seconds.
3. The fan motor speed of outdoor unit as below table in normal running, it has 20 seconds delay

after speed change.

4. The control of outdoor fan motor as figure 6 during defrost process.

Speed table of outdoor fan motor

indoor unit

capacity

outdoor ambient

<2hp

≥2hp

≥3hp

heating Speed

grade

T≥20℃

low low

middle

12℃≤T<20℃

low middle high

T<12℃

middle high high


Control of reverse valve
(figure 5)

1. The reverse valve is ahead run 20 seconds before compressor turn on.
2. After compressor turn off, the reverse valve delay 60 seconds shutdown.
3. The control of reverse valve as figure 6 during defrost process.

compressor

outdoor FM

reverse valve

20s 30s 30s

figure 5

七.Defrost of heating mode(figure 6)

1. Defrost start condition

If outdoor ambient is more than or equal to 16℃,it can’t defrost. When the time of
defrost interval is end , outdoor coil pipe temp. and outdoor ambient temp.
continuous meet all conditions for 5 minutes, it enter defrost process:

1) If outdoor ambient temp. less than or equal to 0℃,when T

≤0.8T

+a℃(a is a adjust

constant), it enter defrost process.

background image

56 SERVICE MANUAL FOR CMV

2) If outdoor ambient temp. more than 0℃ and less than or equal to 15℃,when T

≤ 0.2 T

+a℃, it enter defrost process.

3) If outdoor temp. sensor is failure, when outdoor coil temp. T

≤+a℃, it enter defrost

process.

4) If coil temp. sensor of outdoor unit is failure, when defrost interval time is end, it enter defrost,

the time of defrost is four minutes.

5) During the first ten minutes of outdoor running in heating mode, the time is clear and it judge

whether outdoor coil pipe temp. and outdoor ambient temp. satisfy defrost condition, if the
frequency of compressor is 25HZ and satisfy defrost condition, then if enter defrost process.
After end defrost process or over 10 minutes it return normal running.

2. Defrost end condition

1) T

≥b℃(b is a adjust constant)or defrost time more than or equal to c minutes

(c is a adjust constant),it exit defrost process.

2) When outdoor coil pipe sensor is failure, defrost time is four minutes, it exit defrost process

after four minutes.

3. Interval time of defrost

1) Defrost interval time restriction: Max 120 minutes, Min 25 minutes.
2) The first frost interval time is 0 minute after heating.
3) The second defrost interval time is base on 60 minutes, it adjust according to below table.
4) Form second time, defrost interval time adjustment as below table.

Interval time(Td)

change

Td <2 minutes

Last interval time add 5

minutes

3 minutes≥Td≥2

minutes

Same as last interval time

≥4 minutes

Last interval time reduce 5

minutes


4. Time sequence of defrost process(figure 6).

background image

57 SERVICE MANUAL FOR CMV

八.Control of oil return circle

1. Oil return circle period

When air conditioner has run for 10 minutes or accumulate time T

msro

is end, it execute oil return

circle once.

2.

When compressor is running to oil return circle, the indoor unit which have communication

is return oil, expand valve is open fully and compressor’s frequency increase more than 3/5
of max frequency for 90 seconds, the expand valve of indoor unit which no communication is
close.

九. Operation mode control of outdoor unit(dehumidify、cooling or heating)

The indoor unit can require cooling mode and dehumidify mode together, but it can’t require cooling mode

or dehumidify with heating mode together, the outdoor unit operate state is decided by the indoor unit which is
applied first.


十.Protect function

1. Delay protection of compressor

The compressor can’t run after it stop within 3 minutes.

2. Fault protection of module

The air conditioner stop running immediately and display error code if the module

is fault.

3. Protection of communicate fault

The control of outdoor unit can connect with all indoor units, when it power on,

it sent data to each indoor unit continuously, if it receive a correct data from
correspond indoor unit, then the indoor unit is exist. when the control of outdoor
unit didn’t receive communication data from indoor unit which is exist within 30
seconds, it will display communication fault. If all communication channels are
failure, air conditioner will shutdown and display fault code.

4. Leakage or reverse valve fault

The air conditioner shutdown immediately when meet one of below conditions.

1) Heating: coil pipe temp. of outdoor unit can’t decrease 3 degree within setting

time and coil pipe temp. of indoor unit can’t increase 3 degree all along.

2) Cooling: coil pipe temp. of outdoor unit can’t increase 3 degree within setting

time and coil pipe temp. of indoor unit can’t decrease 3 degree all along.

5. High temp. protection of compressor discharge

1) The protection don’t effect if the temp. sensor of compressor discharge fault.
2) The air conditioner stop running immediately and display error code when the

temp. of compressor discharge more than Tsd.

3) The compressor decrease frequency until the temp. of compressor discharge less

than 99℃ if the temp. of compressor discharge more than 95℃. The compressor resume
normal frequency when the temp. of compressor discharge less than 90℃.

6. Temperature switch protection of compressor

The air conditioner will shutdown immediately and display fault code if the temp.
switch of compressor switch off.

7. High temp. protection of middle coil pipe of condenser

1) The protection don’t effect if the temp. sensor of middle coil pipe fault.
2) The compressor decrease frequency until the temp. of middle coil pipe less than

58 ℃.if the temp. of middle coil pipe more than 57℃..

3) It resume normal frequency when the temp. of middle coil pipe less than 56℃..

background image

58 SERVICE MANUAL FOR CMV

8. High temp. protection of indoor coil pipe

1) The compressor decrease frequency until the temp. of indoor coil pipe more than

(Tsce-2) if the temp. of indoor coil pipe less than (Tsce-2)in cooling mode.

The compressor decrease frequency until the temp. of indoor coil pipe less than
(Tsce+2) if the temp. of indoor coil pipe more than (Tsce+2) in heating mode.

2) It resume normal frequency when the temp. of indoor coil pipe less than Tsce(cooling mode)

or less than Tshe(heating mode).

9. Low temp. protection of compressor suction

1) The protection don’t effect if the temp. sensor of compressor suction fault or compressor

don’t run or in heating mode..

2) The compressor decrease frequency until the temp. of compress suction more than

Tss if the temp. of compressor suction less than Tss. It resume normal frequency when the
temp. of compressor suction more than (Tss+2).

10.Fault protection of outdoor sensor

The air conditioner is running at the frequency of less than (3/5)*Fmax and display fault code

if the temp. sensor of compressor discharge fault, or the temp. sensor of outdoor middle
coil pipe fault, or the temp. sensor of compressor suction fault, or the temp. sensor
of outdoor ambient fault.

11.High temp. of ambient

1) The protection don’t effect if the temp. sensor of outdoor ambient fault.
2) The air conditioner stop running immediately and display error code if outdoor

ambient temp. more than 55℃or less than -20℃.

12. Over current protection of compressor

1) The air conditioner stop running immediately and display error code when input

current more than or equal to Imax.

2) The compressor decrease 2Hz per 3 seconds until input current less than or equal

to (Imax-13) when the input current more than (Imax-13).

2)The compressor decrease 1Hz per 3 seconds until input current less than or equal

to (Imax-16) when the input current more than (Imax-16).

3) It resume normal frequency when the input current less than or equal to (Imax-20).

13.DC voltage of wire protection

1) The air conditioner stop running and display DC voltage abnormal when it less

than 260V.

2)The compressor decrease frequency and display FA6 when DC voltage less than 285V.
3) The air conditioner resume normal running when DC voltage more than 290V.

十一、Outdoor unit fault of indoor unit display

fault

display

Transducer module protection

P2

Over current

P3

Discharge temperature of

compressor overheat, ambient

temperature overheat

P4

DC voltage of outdoor unit abnormal

P7

Leakage or reverse valve fault

P8

Outdoor sensor fault

F6

Compressor drive fault

FC

background image

59 SERVICE MANUAL FOR CMV

12. TROUBLESHOOTING

WARNING!!!

When Power Up – the whole outdoor unit controller, including the wiring, is under HIGH

VOLTAGE!!!

Never open the Outdoor unit before turning off the Power!!!

When turned off, the system is still charged (400V)!!!

It takes about 3 Min. to discharge the system.

Touching the controller before discharging may cause an electrical shock!!!

For safe handling of the controller please refer to section 1.6 below.

1.1 Air Conditioner Failures and Corrective Actions

F1:
1,Communicate wire cut off ,loose or wrong wiring---check wires
2,Communication interfere---check wires connection with circuit diagram.(earth line must be

wired)。


F2:
1,Temp. sensor of indoor room short or cut off.---change sensor

F3:
1,Temp. sensor of indoor coil pipe outlet short or cut off.---change sensor.
2,Temp. sensor of indoor coil pipe entrance short or cut off.---change sensor.
3,Temp. sensor of indoor coil pipe middle short or cut off.---change sensor.

F4:
1,PG motor fault.---change motor. PG.
2,Fixed screw loose.---fix cross flow fan.
3,Communication interfere. (earth wire can’t with communicate wire in same cable)---check cable.

F6:
1,Temp. sensor of discharge short or cut off.---change sensor.
2,Temp. sensor of suction short or cut off.---change sensor.
3,Temp. sensor of condenser middle short or cut off.---change sensor.

P2:(auto-restart)
1,over current protection of inverter module.
2,over voltage protection of inverter module.
3,high temp. protection of inverter module.

P3:
1,over load (outdoor ambient temp. more high).
2,Voltage over low.

background image

60 SERVICE MANUAL FOR CMV


P4:
1: discharge temp. too high.---maybe leak refrigerant, add refrigerant.
2:outdoor ambient temp. too high, if (T<-20,T>55), it will alarm.
3:temp. switch of compressor cut off.。
4:Communication interfere. (earth wire can’t with communicate wire in same cable)---check cable.


P7:
1,PFC board fault.---change PFC board.
2,Communication of main board and PFC board fault.---check wires of main board and PFC board.

P8:
1,Less refrigerant.---add refrigerant.
2,Coil pipe sensor can’t contact with coil pipe.
3,4-way valve fault.---change 4-way vavle fault.



































background image

61 SERVICE MANUAL FOR CMV

1 3 . E X P L O D E D V I E W S A N D S P A R E P A R T S L I S T S

13.1 outdoor unit :CMV-50V3A-E2

NO. description

name

number

1

前网罩

front grill

1

2

前面板

front panel

1

3

风叶

fan 1

4

室外电机

motor 1

5

电机支架组件 motor bracket assemble

1

6

左护网

left grill

1

7

左侧立柱

left pole

1

8

顶盖板

top cover

1

9

背网

rear grill

1

10

冷凝器

condenser 1

11

四通阀

4-way valve

1

12

消音器

muffle 1

13

过滤器

filter 1

14

控制器

controllor 1

background image

62 SERVICE MANUAL FOR CMV

15

电控盒盖

control box cover

1

16

电控盒

electrical control box

1

17

A机DN8截止阀

DN8 valve for A unit

1

18

A机DN4截止阀

DN4 valve for A unit

1

19

B机DN8截止阀

DN8 valve for B unit

1

20

B机DN4截止阀

DN4 valve for B unit

1

21

阀座板

valve installation plate

1

22

大抽手

handle 1

23

右侧板

right panel

1

24

电子膨胀阀

expand valve

2

25

压缩机

compressor 1

26

压缩机胶垫

compressor pad

1

27

中隔板

partition board

1

28

底盘组件

base assemble

1

13.2 outdoor unit :CMV-71V3A-T

background image

63 SERVICE MANUAL FOR CMV

NO. description

name

number

NO.

description name

number

1

顶盖

top cover

1

15

单接头 DN8 sigle tie-in DN8

3

2

冷凝器

condenser 1

16

单接头 DN4 sigle tie-in DN4

4

3

电机支架

motor bracket

1

17

单接头 DN10

sigle tie-in

DN10 1

4

中隔板

partition board

1

18

电子膨胀阀

expand valve

3

5

汽液分离器

gas and liquid

segregator 1

19

右前面板

right front panel

1

6

干燥过滤器

filter 1

20

储液罐

store pot

1

7

油汽分离头

gas and oil segregator

1

21

压缩机

compressor 1

8

后板

rear panel

1

22

四通阀

reverse valve

1

9

电控组件

electrical control

assemble 1

23

底盘

base 1

10

阀座板

valve installation plate

1

24

前面板

front panel

1

11

低压阀

low pressure valve

1

25

网罩

grill 1

12

维修板

repair plate

1

26

风叶

fan 1

13

抽手

handle 2

27

电机

motor 1

14

高压阀

high pressure valve

1

13.2 outdoor unit :CMV-V80WC3AQ

background image

64 SERVICE MANUAL FOR CMV

NO. description

name

number

NO.

description name

number

1

顶盖

top cover

1

15

单接头 DN8 sigle tie-in DN8

3

2

冷凝器

condenser 1

16

单接头 DN4 sigle tie-in DN4

4

3

电机支架

motor bracket

1

17

单接头 DN10

sigle tie-in

DN10 1

4

中隔板

partition board

1

18

电子膨胀阀

expand valve

3

5

汽液分离器

gas and liquid

segregator

1 19 右前面板

right front panel

1

6

干燥过滤器

filter 1

20

储液罐

store pot

1

7

油汽分离头

gas and oil segregator

1

21

压缩机

compressor 1

8

后板

rear panel

1

22

四通阀

reverse valve

1

9

电控组件

electrical control

assemble

1 23 底盘

base 1

10

阀座板

valve installation plate

1

24

前面板

front panel

1

11

低压阀

low pressure valve

1

25

网罩

grill 1

12

维修板

repair plate

1

26

风叶

fan 1

13

抽手

handle 2

27

电机

motor 1

14

高压阀

high pressure valve

1

13.2 outdoor unit :CMV-V40H13AD

background image

65 SERVICE MANUAL FOR CMV

NO. description

name

number

1

前网罩

Front Grill

1

2

面 板

Front Plate

1

3

轴流风轮

Axial flow fan

1

4

电 机

Motor

1

5

电机支架

Motor support

1

6

冷凝器

Condenser

1

7

顶盖板

Top panel

1

8

电器盒

Electric box

1

9

背网

Rear Grill

1

10

右侧板

Right panel

1

11

抽手

handle

1

12

阀座板

Valve installation plate

1

13

A 机 DN4 阀

DN4 valve

1

14

A 机 DN8 阀

DN8 valve

1

15

B 机 DN4 阀

DN4 valve

1

16

B 机 DN8 阀

DN8 valve

1

17

毛细管组件 Capillary Assy

1

18

电子膨胀阀 Electronic expansion valve

2

19

四通阀组件 Four-way valve assembly

1

20

汽液分离器 Steam liquid segregator

1

21

压缩机

Compressor

1

22

中隔板

Partition board

1

23

底盘

Base

1

background image

66 SERVICE MANUAL FOR CMV

APPENDIX A

APPENDIX A

INSTALLATION AND OPERATION MANUAL

 I N S T A L L A T I O N M A N U A L C M V























background image

67 SERVICE MANUAL FOR CMV

F o r e w o r d

This instruction Manual is the universal-purpose version for the models of separate wall-mounted
air conditioners manufactured by our Co. The appearance of the units that you purchase might be
s l i g h t l y d i f f e r e n t from the ones described in the Manual, but it does not affect your proper
operations and usage.

Please read carefully the sections corresponding to the specific model you choose, and keep the
Manual properly so as to facilitate your reference at later time.

I M P O R T A N T !
P l e a s e R e a d B e f o r e S t a r t i n g

This air conditioning system meets strict safety and operating standards.
As the installer or service person, it is an important part of your job to install or service the system
so it operates safely and efficiently.

For safe installation and trouble-free operation, you must:
? Carefully read this instruction booklet before beginning.

?

Follow each installation or repair step exactly as shown.

?

Observe all local, state, and national electrical codes.

? Pay close attention to all danger, warning, and caution notices given in this manual. WARNING:

This symbol refers to a hazard or unsafe practice which can result in severe personal injury or
death.

CAUTION: This symbol refers to a hazard or unsafe practice which can result in personal injury

and the potential for product or property damage.


CONTENTS

LOCATION OF OUTDOOR UNIT

1

ELECTRICAL CONNECTION BETWEEN INDOOR AND OUTDOOR UNIT

3

INSTALLATION/SERVICE TOOLS (ONLY FOR R410A PRODUCT)

7

REFRIGERANT TUBING

9

FINAL TASKS

11

NOTE: This manual is for Multi split applications only.

For indoor units installation please refer to the installation manual
supplied within the indoor unit package.

background image

68 SERVICE MANUAL FOR CMV

1 LOCATION OF OUTDOOR UNIT

Select the location considering the following:

O U T D O O R U N I T

1 .The location must allow easy servicing and provide good air circulation as shown in fig2.

2.The unit may be suspended from a wall by a bracked(Optional)or located in a free standing

position on the floor(preferably slightly elevated).

3.If the unit is suspended , ensure that the bracket is firmly connected and the wall is strong

enough to withstand vibrations.

4.Unit location should not disturb neighbours with noise or exhaust air stream.

5.Place the mounting pads under the unit legs.

6.Refer to figure 2 for allowed installation distances.

.

background image

Fig 1

2 ELECTRICAL CONNECTION BETWEEN

OUTDOOR AND INDOOR UNIT

ELECTRICAL REQUIREMENTS
Electrical wiring and connections should be made by qualified electricians and in accordance
with local electrical codes and regulation.The air conditioner units must be grounded. The air
conditioner units must be connected to an adequate power outlet from a separate branch
circuit protected by a time delay circuit breaker,as specified on unit's nameplate. Voltage
should not vary beyond ± 10% of the rated voltage.
1 .Remove the power supply cable that is connected to the indoor unit!
2.To connect the indoor units to the outdoor units,use the following electrical cables.
Electrical connections:
Power input cable: 1 group 3 wiresX2.5mm

2

cable between indoor and

outdoor units:

1 group 4 wiresX 1.0mm

2

see Fig 6.7.8.9.10 for detail .
3.Prepare the cable ends for the power input and for the cables between outdoor and indoor

units as shown in figure 3a and 3b respectively.

4.Connect the cable ends to the terminals of the indoor and outdoor units , as show in fig4, figs.
Please select corresponding connection according to the different indoor units. 5.Secure the
multiple wire power cable with the cable clamps.
•Power input cable

background image

70 SERVICE MANUAL FOR CMV




















background image

71 SERVICE MANUAL FOR CMV

3 INSTALLATION/SERVICE TOOLS(QNLY

FOR R410A PRODUCT)

C A U T I O N

New Refrigerant Air Conditioner Installation

This air conditioner adopts the new HFC refrigerant (R410A) which does not destroy ozone layer.

R410A refrigerant is approx . 1.6 times of refigerant R22. Accompanied with the adoption of the

new refrigerant , the refrigeration machine oil has also been changed.

Therefore,during installation work, be sure that water , dust , former refrigerant , or refrigeration

machine oil does not enter into the new type refrigerant R410A air conditioner circuit.The system

must not be left open to the atmosphere for any reason for any period of time as the systems oil

quickly absorbs moisture and will contaminate and damage the system.

A refrigerant liquid line drier is recommended.

To prevent mixing of refrigerant or refrigerating machine oil ,the sizes of conneting sections of

charging port on main unit and installation tools are different from those used for the conventional

refrigerant units. Accordingly,special tools are required for the new refrigerant (R410A) units,

For connecting pipes use new and clean piping materials with high pressure f i t t i n g made for

R410A only, so that water and/or dust does not enter.Moreover, do not use the existing piping

because there are some problems w i t h presure f i t t i n g s and possible i m p u r i t i e s in e x i s t i n g

piping .

Changes in the product and components

In air conditioners using R410A ,in order to prevent any other refrigerant from being accedentally

charged .the service port diameter size of the outdoor unit control valve (3 way valve) has been

changed. (1/2 UFN 20 threads per inch)

• In order to increase the pressure resisting strength of the refrigerant piping ,flare processing

diameter and opposing flare nuts sizes have been changed.( fot copper pipes with nomensions

1/2 and 5/8)

New tools for R410A

Nes tools for R410A

Applicable to R22 model

Chages

Gauge manifold

x

As the working pressure is high ,it is impossible
to measure the working pressure using
conventional gauges . In order to prevent
any other refrigerant from being charged ,
the port diameters have been changed.

Charge hose

x

In order to increase pessure resisting strength.
hose materials and port sizes have been changed(
to 1 /2 UNF 20 threads per inch).
When puchasing a charge hose,be sure to confirm
the port size.

Electronic balance for
refrigerant charging

As working pressure is. high and gasification
speed is fat ,it is difficult to read the indicated
value by means of charging cylinder ,as air
bubbles occur.

Torque wrench
(nominal dia.1/2,5/8)

x

The size of opposing flare nuts have been
increased ,incidentally,a common wrench is
used for nominal diameters 1/4 and 3/8.

background image

72 SERVICE MANUAL FOR CMV

Flare tool
(clutch type)

0

By incressing the clamp bar'receiving hole
size , strength of spring in the tool has been
improved.

Gauge for projection
adjustment

_

Used when flare is made by using conventional
flare tool.

Vacuum pump adapter 0

Connected to conventional vacuum pump,it is
necessary to use an adapter to prevent vacuum
pump oil from flowing back into the charge
hose ,
The charge hose connecting part has two
ports-one for conventional refrigerant (7/16
UNF 20 theads per inch )and one for R41 OA ,if

Gas leakage detector

x

Exclusive for HFC refrigerant

• I n c i d e n t a l l y , t h e " r e f r i g e r a n t cylinder"comes w i t h the r e f r i g e r a n t designation(R410A)and

protector coating in the U.S's ARI specified rose color (Ari color code; PMS 507).

•Also the "charge port and packing for refrigerant cylinder"requires 1/2 UNF 20 theads per inch

corresponding to the charge pOse's port size.

4 REFRIGERANT TUBING

CONNECT THE INDOOR TO THE OUTDOOR UNIT

The indoor unit contains a small quantity of nitrogen.Do not unscrew the nuts from the unit until
you are ready to

connect the tubing.The outdoor unit is supplied
with suffcient refrigerant charge(R410A). Refer
to outdoor unit nameplate.
To prevent crushing,bend tubes using a bending
tool.
NOTE:Use refrigeration R410Atype copper
tubing only.
1.Open the valve cover.
2.Use tubing diameter that corresponds to the
tubing diameter of the indoor and outdoor units.
Note that the liquid and suction tubes have
different diameters.(See tube size,torque
tightening table.)
3.Place flares nuts on tube ends before preparing
them with a flaring tool.Use the flare nuts that
are mounted on the supplied outdoor and indoor
units.
4.Connect the all ends of the tubing to the
indoor and outdoor units.Notice the sign . All
ends should correspond one by one.
5.Insulate each tube separately,and their
unions,with at least 6mm thick of
insulation .Wrap the refrigerant tubing,drain

hose and electric cables together with a vinyl tape (UV protected).

background image

73 SERVICE MANUAL FOR CMV

Caution!
When unscrewing the

valve caps, do not stand
in front of them or the

spindles at any time,as
the system is under

pressure.

Fig 11
1.INDOOR UNIT
2.Liquid tube(small dia.) 3.Suction
tube(large dia.) 4. Plugs

5.Flare nuts
6.Tubing between units 7.Suction

tube

8.Liquid tube

9.OUTDOOR UNIT

10.FIare nuts

11 .Suction valve(larger) 12.Liquid
valve(smal)

NOTE:1.For unit use connectionsA,B and D

2.For large indoor unit of 5.0KW Use the

lower connection(unit D) and use the
3/8"-1/2"transition( supplied)

3.The electric control channel must match

the tube channel.

TUBE SIZE

TORQUE

Liquid line 1/4"

1 5 - 2 0 N.M.

Suction line 3/8"

3 0 - 3 5 N.M.

Suction line 1/2"

5 0 - 5 4 N.M.

Suction line 5/8"

7 5 - 7 8 N.M.

Fig 13 To prevent refrigerant

leakage,coat the flared
surface with
refrigeration oil

Fig 14

1.Suction valve
2.Service port
3.Liquid valve

EVACUATION OF THE REFRIGERATION TUBES AND THE INDOOR UNIT

After connecting the unions of the indoor and outdoor units,evacuate the air from the

tubes and indoor unit as follows:

Tightening torques
of unions and
valve caops:

background image

74 SERVICE MANUAL FOR CMV

1.Connect the charging hoses with a push pin to the low and high sides of the charging

set and the service ports of the suction and liquid valves.

Be sure to connect the end of the charging hose with the push pin to the service

ports. 2.Connect the center hose of the charging set to a vacuum pump.

3.Open Fully the low and high pressure sides of the manifold gauge valves.

4.Turn on the vacuum pump.Perform evacuating for at least 30 minutes and than confirm

that the needle in the gauge moves from 0 MPa(Ocm Hg) t 0 - 0 . 1 MPa(-76cm Hg).

5.Close the valves of the low and high sides of the charging set and turn off the vacuum

pump. After few m i n u t e s , i f the gauge needle has moved,there is a leak which must be

found and repaired before moving to the next stage.

6.Disconnect the charging hose from the vacuum pump and from the service ports of the

suction and liquid valves.

7.Tighten the service port caps of suction and liquid valves.

8.Remove the valve caps from all valves,and open them using a hexagonal Allen

wrench, 9.Securely tighten the caps onto all of the valves.

10.Check for gas leaks from all the connecting p os i t io n . Tes t w i t h electronic leak

detector or with a sponge immersed in soapy water for bubbles.

1 .Charging set

5.Cap

9.Liquid valve

2.Vacuum pump

6.Suction valve

10.INDOOR UNIT

3.OUTDOOR UNIT

7.Service valve

1 1.Suction flare connection

4.Service valve

8.Cap

12.Liquid flare connection

background image

75 SERVICE MANUAL FOR CMV

5 FINAL TASKS

1 .Check all valve caps and ensure that they had tightened properly.Close the valve

cover. 2.Fill gaps on the wall between hole sides and tubing with sealer.

3.Attach wiring and tubing to the wall with clamps where necessary.

4.Operate the unit for no less than 5 minutes at heating or cooling

mode. 5.Explain filter removal,cleaning and installation.

6.Operate the air conditioner together with the customer and explain all

functions. 7.Give the operating and installation manuals to the customer


Wyszukiwarka

Podobne podstrony:
elFF WSK LE 03M inst D141125 PL
inst ext pl pcm 04
FF LE 03M CT inst D170823 PL
elFF WSK LE 03MP inst D160118 PL
FF DRM 01 inst D161129 PL
Pl Inst zcz rok1 L
Instrukcja obslugi FIAT LINEA Blue&MeNav szybka inst PL up by dunaj2
http, mandriva org pl instalacja programow repozytoria 75 inst
Pl Inst zcz rok1 L
Instrukcja obslugi FIAT LINEA Blue&MeNav szybka inst PL up by dunaj2
http, mandriva org pl instalacja programow repozytoria 75 inst
download Zarządzanie Produkcja Archiwum w 09 pomiar pracy [ www potrzebujegotowki pl ]
Wyklad 6 Testy zgodnosci dopasowania PL
WYKŁAD PL wersja ostateczna
Course hydro pl 1
PERFORMANCE LEVEL, PL
struktura organizacyjna BTS [ www potrzebujegotowki pl ]

więcej podobnych podstron