1 SERVICE MANUAL FOR CMV
DC Inverter Multi-Split Air-Condition Unit
CMV-71V3A-T
CMV-V80WC3AQ
CMV-50V3A-E2
CMV-V40H13AD
REFRIGERENT
R410A
HEAT PUMP
SERVICE
MANUAL
2 SERVICE MANUAL FOR CMV
Table of Contents
1. INTRODUCTION .................................................................................................1-1
2. PRODUCT
DATA SHEET ...................................................................................2-1
3. RATING
CONDITIONS ........................................................................................3-1
4. OUTLINE
DIMENSIONS .....................................................................................4-1
5. PERFORMANCE
DATA ......................................................................................5-1
6. PRESSURE
CURVES .........................................................................................6-1
7. ELECTRICAL DATA .............................................................................................7-1
8. WIRING
DIAGRAMS ...........................................................................................8-1
9. REFRIGERATION
DIAGRAMS ...........................................................................9-1
10. TUBING
CONNECTIONS .....................................................................................10-1
11. CONTROL
SYSTEM ...........................................................................................11-1
12. TROUBLESHOOTING ........................................................................................12-1
13. EXPLODED VIEWS AND SPARE PARTS LISTS ................................................13-1
14. APPENDIX
A
3 SERVICE MANUAL FOR CMV
1. INTRODUCTION
1.1 General
The new CMV is a high efficiency DC inverter technology outdoor unit,
since it’s a lego concept unit, it can be matched to several inverter indoor units such as wall
mounted type with a capacity range of 2.0 – 5.0 Kw for each single indoor unit.
1.2 Main
Features
DC Inverter
R410a
sine wave form and 120 degree rectangurlar wave form in comprssor driver
sensor less inverter compressor driver
high speed calculation for accurate sine wave form vector control
smart PFC control
fuzzy logic con
trol
High COP (“A “ or “B” class energy rating)
Lego Concept
Pre-Charged
.
Cooling operation at outdoor temperature down to 10
0
C.
Heating operation at outdoor temperature down to -15
0
C.
Variable Speed outdoor fan.
Low noise level
EEV for each indoor unit
1.3 Tubing Connections
Flare type interconnecting tubing to be produced on site.
For further details please refer to APPENDIX A on this manual, and to the relevant indoor
service Manual,
1.4 Inbox Documentation
Each indoor unit is supplied with its own installation and operation manuals.
4 SERVICE MANUAL FOR CMV
2 .
P R O D U C T D A T A S H E E T
2 . 1 . 1
O u t d o o r U n i t C M V - 5 0 V 3 A - E 2 S p e c i f i c a t i o n s .
OUTDOOR UNNIT
Model
CMV-50V3A-E2
Operation Model
Cooling
Heating
Kcal/hr
4300(1032-5848)
5160(860-6278)
Btu/hr
17064(4095-23207)
20477(3412-24913)
Capacity
W
5000(1400-6800)
6000(1300-7300)
Total Input
W
1400(460-2300)
1600(450-2200)
E.E.R(Cooling)/C.O.P(Heating)
W/W
3.57
3.75
Starting Current
A
1
Inrush Current
A
<35
Power Supply
V/PH/Hz
220-240V 1PH 50Hz
Refrigerant control
Electronic expansion valve
Compressor Type
Twin Rotary DC Inverter
Model
C-6RZ146H1A
Starter Type
Low frequency start
Protection Device
Outdoor SW control
Heat Exchanger
Hydrophilic corrugated fins ,Grooved tube
Fan×No.
Propeller×1
Airflow
m
3
/hr
2450
Motor Output
W
60
Defrost method
Reverse cycle
Pressure
55
55
Noise Level
Power
dB(A)
65
65
Dimensions
W*D*H
mm
850×292×607
Weight
Kg
50
Package
W*D*H
mm
995×415×680
O
U
TDOO
R UN
NI
T
Unit Stacking
#
4
Refrigerant Charge
g
R410A-1580g
Liquid
mm
2×6.35
Tube Size O.D
Suction
mm
2×9.52
Indoor & outdoor
Flared
Height difference betweeen indoor unit
Max.10m
Height difference betweeen indoor & outdoor
Max.10m
Tubing length
Max.20m for one unit and 30m total
TUBING
Connection method
between the indoor
and the outdoor
units
Additional charge
No need
5 SERVICE MANUAL FOR CMV
2 . 1 . 2 O u t d o o r
U n i t
C M V - 7 1 V 3 A - T S p e c i f i c a t i o n s .
OUTDOOR UNIT
Model
CMV-71V3A-T
Operation Model
Cooling
Heating
Kcal/hr
6106(1290-7998)
7740(1118-9030)
Btu/hr
24231(5118-31731)
30708(4435-35826)
Capacity
W
7100(1500-9000)
8500(1700-10500)
Total Input
W
2200(580-3200)
2330(540-3000)
E.E.R(Cooling)/C.O.P(Heating)
W/W
3.227
3.648
Starting Current
A
2
Inrush Current
A
<35
Power Supply
V/PH/Hz
220-240V 1PH 50Hz
Refrigerant control
Electronic expansion valve
Compressor Type
Twin Rotary DC Inverter
Model
C-7RVN153HOW
Starter Type
Low frequency start
Protection Device
Outdoor SW control
Heat Exchanger
Hydrophilic corrugated fins ,Grooved tube
Fan×No.
Propeller×1
Airflow
m
3
/hr
3200
Motor Output
W
90
Defrost method
Reverse cycle
Pressure
57
57
Noise Level
Power
dB(A)
65
65
Dimensions
W*D*H
mm
960×344×846
Weight
Kg
82
Package
W*D*H
mm
1060×470×925
O
U
TDOO
R UN
NI
T
Unit Stacking
#
2
Refrigerant Charge
g
R410A-3,000
Liquid
mm
3×6.35
Tube Size O.D
Suction
mm
2×9.52+1×12.7
Indoor & outdoor
Flared
Height difference betweeen indoor unit
Max.15m
Height difference betweeen indoor &
outdoor
Max.15m
Tubing length
Max.25m for one unit and 50m total
TUBING
Connection method
between the indoor
and the outdoor units
Additional charge
No need
6 SERVICE MANUAL FOR CMV
2 . 1 . 3 O u t d o o r
U n i t
C M V - V 8 0 W C 3 A Q S p e c i f i c a t i o n s .
OUTDOOR UNNIT
Model
CMV-V80WC3AQ
Operation Model
Cooling
Heating
Kcal/hr
6880(1720-7740)
8256(1720-9460)
Btu/hr
27296(6824-30708)
32755(6824-37532)
Capacity
W
8000(2000-9000) 9600(2000-11000)
Total Input
W
2450(710-3350)
2400(910-2950)
E.E.R(Cooling)/C.O.P(Heating)
W/W
3.26
4
Starting Current
A
2
Inrush Current
A
<35
Power Supply
V/PH/Hz
220-240V 1PH 50Hz
Refrigerant control
Electronic expansion valve
Compressor Type
Twin Rotary DC Inverter
Model
C-7RVN153HOW
Starter Type
Low frequency start
Protection Device
Outdoor SW control
Heat Exchanger
Hydrophilic corrugated fins ,Grooved tube
Fan×No.
Propeller×1
Airflow
m
3
/hr
3200
Motor Output
W
90
Defrost method
Reverse cycle
Pressure
57
57
Noise Level
Power
dB(A)
65
65
Dimensions
W*D*H
960×344×846
960×344×846
Weight
Kg
86
Package
W*D*H
1060×470×925
1060×470×925
O
U
TDOO
R UN
NI
T
Unit Stacking
#
2
Refrigerant Charge
g
R410A-3,600g
Liquid
mm
4×6.35
Tube Size O.D
Suction
mm
3×9.52+12.7
Indoor & outdoor
Flared
Height difference betweeen
indoor unit
Max.10m
Height difference betweeen
indoor & outdoor
Max.10m
Tubing length
Max.25m for one unit and 70m total
TUBING
Connection method
between the indoor
and the outdoor units
Additional charge
No need
7 SERVICE MANUAL FOR CMV
2 . 1 . 4
O u t d o o r U n i t C M V - V 4 0 H 1 3 A D S p e c i f i c a t i o n s .
OUTDOOR UNNIT
Model
CMV-V40H13AD
Operation Model
Cooling
Heating
Kcal/hr
3430(1250-4460)
4000(1300-4600)
Btu/hr
13700(5000-17800)
15700(5200-18100)
Capacity
W
4000(1450-5200)
4600(1500-5300)
Total Input
W
1020(450-1580)
1050(430-1300)
E.E.R(Cooling)/C.O.P(Heating)
W/W
3.92
4.38
Starting Current
A
1
Inrush Current
A
<15
Power Supply
V/PH/Hz
220-240V 1PH 50Hz
Refrigerant control
Electronic expansion valve
Compressor Type
Single Rotary DC Inverter
Model
5RS102XCA01
Starter Type
Low frequency start
Protection Device
Outdoor SW control
Heat Exchanger
Hydrophilic corrugated fins ,Grooved tube
Fan×No.
Propeller×1
Airflow
m
3
/hr
1800
Motor Output
W
35
Defrost method
Reverse cycle
Pressure
53
53
Noise Level
Power
dB(A)
65
65
Dimensions
W*D*H
mm
860×320×550
Weight
Kg
50
Package
W*D*H
mm
905×323×573
O
U
TDOO
R UN
NI
T
Unit Stacking
#
4
Refrigerant Charge
g
R410A-1250g
Liquid
mm
2×6.35
Tube Size O.D
Suction
mm
2×9.52
Indoor & outdoor
Flared
Height difference betweeen indoor unit
Max.10m
Height difference betweeen indoor & outdoor
Max.10m
Tubing length
Max.20m for one unit and25m total
TUBING
Connection method
between the indoor
and the outdoor
units
Additional charge
No need
8 SERVICE MANUAL FOR CMV
2 . 2
I n d o o r U n i t s D a t a
2 . 2 . 1 C M V S - 2 5 V 3 A - A 4 8 A
S p e c i f i c a t i o n s
INDOOR UNIT
Model Indoor Unit/Type
CMVS-25V3A-A48A
Installation method
Flare
Power Supply
V/Ph/Hz
220-240/1/50
Fan Type & Quantity
Crossflow×1
H
500
M
450
Airflow Cooling/Heating
L
m
3
/hr
360
Sound Preesure Level Cooling/Heating
L-H
dB(A)
32-41/32-41
Condensate Drain Tube I.D
mm
16
Dimensions
W/H/D
mm
270×180×790
Weight
kg
12
Packaging Dimensions
W/H/D
mm
870×350×270
IN
D
OOR
Stacking Height
Units
7
Heating Elements
KW
N/A
Moisture Removal
L/hr
0.8
2 . 2 . 2 C M V S - 3 5 V 3 A - A 4 8 A
S p e c i f i c a t i o n s
INDOOR UNIT
Model Indoor Unit/Type
CMVS-35V3A-A48A
Installation method
Flare
Power Supply
V/Ph/Hz
220-240/1/50
Fan Type & Quantity
Crossflow×1
H
550
M
450
Airflow Cooling/Heating
L
m
3
/hr
360
Sound Preesure Level Cooling/Heating
L-H
dB(A)
32-41/32-41
Condensate Drain Tube I.D
mm
16
Dimensions
W/H/D
mm
270×180×790
Weight
kg
12
Packaging Dimensions
W/H/D
mm
870×350×270
IN
D
OOR
Stacking Height
Units
7
Heating Elements
KW
N/A
Moisture Removal
L/hr
1
9 SERVICE MANUAL FOR CMV
2 . 2 . 3
C M V S - 2 5 V 3 A - A 3 8 A C M V S - 2 5 V 3 A - A 3 8 B S p e c i f i c a t i o n s
INDOOR UNIT
Model Indoor Unit/Type
CMVS-25V3A-A38A
CMVS-25V3A-A38B
Installation method
Flare
Power Supply
V/Ph/Hz
220-240/1/50
Fan Type & Quantity
Crossflow×1
H
500
M
450
Airflow Cooling/Heating
L
m
3
/hr
360
Sound Preesure Level Cooling/Heating
L-H
dB(A)
32-41/32-41
Condensate Drain Tube I.D
mm
16
Dimensions
W/H/D
mm
270×180×790
Weight
kg
12
Packaging Dimensions
W/H/D
mm
880×360×250
IN
D
OOR
Stacking Height
Units
7
Heating Elements
KW
N/A
Moisture Removal
L/hr
0.8
2 . 2 . 4
C M V S - 3 5 V 3 A - A 3 8 A C M V S - 3 5 V 3 A - A 3 8 B S p e c i f i c a t i o n s
INDOOR UNIT
Model Indoor Unit/Type
CMVS-35V3A-A38A
CMVS-35V3A-A38B
Installation method
Flare
Power Supply
V/Ph/Hz
220-240/1/50
Fan Type & Quantity
Crossflow×1
H
550
M
450
Airflow Cooling/Heating
L
m
3
/hr
360
Sound Preesure Level Cooling/Heating
L-H
dB(A)
32-41/32-41
Condensate Drain Tube I.D
mm
16
Dimensions
W/H/D
mm
270×180×790
Weight
kg
12
Packaging Dimensions
W/H/D
mm
880×360×250
IN
D
OOR
Stacking Height
Units
7
Heating Elements
KW
N/A
Moisture Removal
L/hr
1
10 SERVICE MANUAL FOR CMV
2 . 2 . 5 C M V S - 2 5 V 3 A - A 4 6 A
S p e c i f i c a t i o n s
INDOOR UNIT
Model Indoor Unit/Type
CMVS-25V3A-A46A
Installation method
Flare
Power Supply
V/Ph/Hz
220-240/1/50
Fan Type & Quantity
Crossflow×1
H
500
M
450
Airflow Cooling/Heating
L
m
3
/hr
360
Sound Preesure Level Cooling/Heating
L-H
dB(A)
32-41/32-41
Condensate Drain Tube I.D
mm
16
Dimensions
W/H/D
mm
270×180×790
Weight
kg
12
Packaging Dimensions
W/H/D
mm
870×350×270
IN
D
OOR
Stacking Height
Units
7
Heating Elements
KW
N/A
Moisture Removal
L/hr
0.8
2 . 2 . 6 C M V S - 3 5 V 3 A - A 4 6 A
S p e c i f i c a t i o n s
INDOOR UNIT
Model Indoor Unit/Type
CMVS-35V3A-A46A
Installation method
Flare
Power Supply
V/Ph/Hz
220-240/1/50
Fan Type & Quantity
Crossflow×1
H
550
M
450
Airflow Cooling/Heating
L
m
3
/hr
360
Sound Preesure Level Cooling/Heating
L-H
dB(A)
32-41/32-41
Condensate Drain Tube I.D
mm
16
Dimensions
W/H/D
mm
270×180×790
Weight
kg
12
Packaging Dimensions
W/H/D
mm
870×350×270
IN
D
OOR
Stacking Height
Units
7
Heating Elements
KW
N/A
Moisture Removal
L/hr
1
11 SERVICE MANUAL FOR CMV
2 . 2 . 7 C M V S - 2 5 V 3 A - A 6 9 A
S p e c i f i c a t i o n s
INDOOR UNIT
Model Indoor Unit/Type
CMVS-25V3A-A69A
Installation method
Flare
Power Supply
V/Ph/Hz
220-240/1/50
Fan Type & Quantity
Crossflow×1
H
500
M
450
Airflow Cooling/Heating
L
m
3
/hr
360
Sound Preesure Level Cooling/Heating
L-H
dB(A)
32-41/32-41
Condensate Drain Tube I.D
mm
16
Dimensions
W/H/D
mm
270×180×790
Weight
kg
12
Packaging Dimensions
W/H/D
mm
875×338×285
IN
D
OOR
Stacking Height
Units
7
Heating Elements
KW
N/A
Moisture Removal
L/hr
0.8
2 . 2 . 8 C M V S - 3 5 V 3 A - A 6 9 A
S p e c i f i c a t i o n s
INDOOR UNIT
Model Indoor Unit/Type
CMVS-35V3A-A69A
Installation method
Flare
Power Supply
V/Ph/Hz
220-240/1/50
Fan Type & Quantity
Crossflow×1
H
550
M
450
Airflow Cooling/Heating
L
m
3
/hr
360
Sound Preesure Level Cooling/Heating
L-H
dB(A)
32-41/32-41
Condensate Drain Tube I.D
mm
16
Dimensions
W/H/D
mm
270×180×790
Weight
kg
12
Packaging Dimensions
W/H/D
mm
875×338×285
IN
D
OOR
Stacking Height
Units
7
Heating Elements
KW
N/A
Moisture Removal
L/hr
1
12 SERVICE MANUAL FOR CMV
2 . 2 . 9 C M V - V 2 5 G 3 A / A 6 7
S p e c i f i c a t i o n s
INDOOR UNIT
Model Indoor Unit/Type
CMV-V25G3A/A67
Installation method
Flare
Power Supply
V/Ph/Hz
220-240/1/50
Fan Type & Quantity
Crossflow×1
H
500
M
450
Airflow Cooling/Heating
L
m
3
/hr
360
Sound Preesure Level Cooling/Heating
L-H
dB(A)
32-41/32-41
Condensate Drain Tube I.D
mm
16
Dimensions
W/H/D
mm
270×180×790
Weight
kg
12
Packaging Dimensions
W/H/D
mm
875×338×285
IN
D
OOR
Stacking Height
Units
7
Heating Elements
KW
N/A
Moisture Removal
L/hr
0.8
2 . 2 . 1 0
C M V - V 3 5 G 3 A / A 6 7 S p e c i f i c a t i o n s
INDOOR UNIT
Model Indoor Unit/Type
CMV-V35G3A/A67
Installation method
Flare
Power Supply
V/Ph/Hz
220-240/1/50
Fan Type & Quantity
Crossflow×1
H
550
M
450
Airflow Cooling/Heating
L
m
3
/hr
360
Sound Preesure Level Cooling/Heating
L-H
dB(A)
32-41/32-41
Condensate Drain Tube I.D
mm
16
Dimensions
W/H/D
mm
270×180×790
Weight
kg
12
Packaging Dimensions
W/H/D
mm
875×338×285
IN
D
OOR
Stacking Height
Units
7
Heating Elements
KW
N/A
Moisture Removal
L/hr
1
13 SERVICE MANUAL FOR CMV
2 . 2 . 1 1 C M V - V 2 5 G 3 A / A 7 8
S p e c i f i c a t i o n s
INDOOR UNIT
Model Indoor Unit/Type
CMV-V25G3A/A78
Installation method
Flare
Power Supply
V/Ph/Hz
220-240/1/50
Fan Type & Quantity
Crossflow×1
H
500
M
450
Airflow Cooling/Heating
L
m
3
/hr
360
Sound Preesure Level Cooling/Heating
L-H
dB(A)
32-41/32-41
Condensate Drain Tube I.D
mm
16
Dimensions
W/H/D
mm
270×180×790
Weight
kg
12
Packaging Dimensions
W/H/D
mm
875×338×285
IN
D
OOR
Stacking Height
Units
7
Heating Elements
KW
N/A
Moisture Removal
L/hr
0.8
2 . 2 . 1 2
C M V - V 3 5 G 3 A / A 7 8 S p e c i f i c a t i o n s
INDOOR UNIT
Model Indoor Unit/Type
CMV-V35G3A/A78
Installation method
Flare
Power Supply
V/Ph/Hz
220-240/1/50
Fan Type & Quantity
Crossflow×1
H
550
M
450
Airflow Cooling/Heating
L
m
3
/hr
360
Sound Preesure Level Cooling/Heating
L-H
dB(A)
32-41/32-41
Condensate Drain Tube I.D
mm
16
Dimensions
W/H/D
mm
270×180×790
Weight
kg
12
Packaging Dimensions
W/H/D
mm
875×338×285
IN
D
OOR
Stacking Height
Units
7
Heating Elements
KW
N/A
Moisture Removal
L/hr
1
14 SERVICE MANUAL FOR CMV
2 . 2 . 1 3 C M V - V 2 0 G 3 A / G 3 8 A
S p e c i f i c a t i o n s
INDOOR UNIT
Model Indoor Unit/Type
CMV-V20G3A/G38A
Installation method
Flare
Power Supply
V/Ph/Hz
220-240/1/50
Fan Type & Quantity
Crossflow×1
H
450
M
350
Airflow Cooling/Heating
L
m
3
/hr
270
Sound Preesure Level Cooling/Heating
L-H
dB(A)
32-41/32-41
Condensate Drain Tube I.D
mm
16
Dimensions
W/H/D
mm
270×180×790
Weight
kg
9
Packaging Dimensions
W/H/D
mm
880×360×250
IN
D
OOR
Stacking Height
Units
7
Heating Elements
KW
N/A
Moisture Removal
L/hr
0.6
2 . 2 . 1 4 C M V - V 5 0 G 3 A / H 3 8 A
S p e c i f i c a t i o n s
INDOOR UNIT
Model Indoor Unit/Type
CMV-V50G3A/H38A
Installation method
Flare
Power Supply
V/Ph/Hz
220-240/1/50
Fan Type & Quantity
Crossflow×1
H
750
M
550
Airflow Cooling/Heating
L
m
3
/hr
450
Sound Preesure Level Cooling/Heating
L-H
dB(A)
35-43/35-43
Condensate Drain Tube I.D
mm
16
Dimensions
W/H/D
mm
930×270×180
Weight
kg
14
Packaging Dimensions
W/H/D
mm
1010×360×280
IN
D
OOR
Stacking Height
Units
7
Heating Elements
KW
N/A
Moisture Removal
L/hr
1.2
15 SERVICE MANUAL FOR CMV
2 . 2 . 1 5 C M V S - 5 0 V 3 A - N 4 6 A
S p e c i f i c a t i o n s
INDOOR UNIT
Model Indoor Unit/Type
CMVS-50V3A-N46A
Installation method
Flare
Power Supply
V/Ph/Hz
220-240/1/50
Fan Type & Quantity
Crossflow×1
H
750
M
550
Airflow Cooling/Heating
L
m
3
/hr
450
Sound Preesure Level Cooling/Heating
L-H
dB(A)
35-43/35-43
Condensate Drain Tube I.D
mm
16
Dimensions
W/H/D
mm
998×320×210
Weight
kg
14
Packaging Dimensions
W/H/D
mm
1085×380×300
IN
D
OOR
Stacking Height
Units
7
Heating Elements
KW
N/A
Moisture Removal
L/hr
1.2
2 . 2 . 1 6 C M V S - 5 0 V 3 A - N 1 7 A
S p e c i f i c a t i o n s
INDOOR UNIT
Model Indoor Unit/Type
CMVS-50V3A-N17A
Installation method
Flare
Power Supply
V/Ph/Hz
220-240/1/50
Fan Type & Quantity
Crossflow×1
H
750
M
550
Airflow Cooling/Heating
L
m
3
/hr
450
Sound Preesure Level Cooling/Heating
L-H
dB(A)
35-43/35-43
Condensate Drain Tube I.D
mm
16
Dimensions
W/H/D
mm
1015×320×204
Weight
kg
14
Packaging Dimensions
W/H/D
mm
1085×380×300
IN
D
OOR
Stacking Height
Units
7
Heating Elements
KW
N/A
Moisture Removal
L/hr
1.2
16 SERVICE MANUAL FOR CMV
2 . 2 . 1 7 C M V - V 2 5 G 3 A / M 8 5 S p e c i f i c a t i o n s
INDOOR UNIT
Model Indoor Unit/Type
CMV-V25G3A/M85
Installation method
Flare
Power Supply
V/Ph/Hz
220-240/1/50
Fan Type & Quantity
Crossflow×1
H
500
M
450
Airflow Cooling/Heating
L
m
3
/hr
360
Sound Preesure Level
Cooling/Heating
L-H
dB(A)
29-39
Condensate Drain Tube I.D
mm
16
Dimensions
W/H/D
mm
800×280×187
Weight
kg
12
Packaging Dimensions
W/H/D
mm
860×350×265
IN
D
OOR
Stacking Height
Units
8
Heating Elements
KW
N/A
Moisture Removal
L/hr
0.6
2 . 2 . 1 8 C M V - V 3 5 G 3 A / M 8 5 S p e c i f i c a t i o n s
INDOOR UNIT
Model Indoor Unit/Type
CMV-V35G3A/M85
Installation method
Flare
Power Supply
V/Ph/Hz
220-240/1/50
Fan Type & Quantity
Crossflow×1
H
550
M
480
Airflow Cooling/Heating
L
m
3
/hr
380
Sound Preesure Level
Cooling/Heating
L-H
dB(A)
29-39
Condensate Drain Tube I.D
mm
16
Dimensions
W/H/D
mm
800×280×187
Weight
kg
12
Packaging Dimensions
W/H/D
mm
860×350×265
IN
D
OOR
Stacking Height
Units
8
Heating Elements
KW
N/A
Moisture Removal
L/hr
0.8
17 SERVICE MANUAL FOR CMV
2 . 2 . 1 9 C M V - V 2 5 G 3 A / A 2 7 S p e c i f i c a t i o n s
INDOOR UNIT
Model Indoor Unit/Type
CMV-V25G3A/A27
Installation method
Flare
Power Supply
V/Ph/Hz
220-240/1/50
Fan Type & Quantity
Crossflow×1
H
500
M
450
Airflow Cooling/Heating
L
m
3
/hr
360
Sound Preesure Level Cooling/Heating
L-H
dB(A)
32-41/32-41
Condensate Drain Tube I.D
mm
16
Dimensions
W/H/D
mm
270×180×790
Weight
kg
12
Packaging Dimensions
W/H/D
mm
875×338×285
IN
D
OOR
Stacking Height
Units
7
Heating Elements
KW
N/A
Moisture Removal
L/hr
0.8
2 . 2 . 2 0 C M V - V 3 5 G 3 A / A 2 7 S p e c i f i c a t i o n s
INDOOR UNIT
Model Indoor Unit/Type
CMV-V35G3A/A27
Installation method
Flare
Power Supply
V/Ph/Hz
220-240/1/50
Fan Type & Quantity
Crossflow×1
H
550
M
450
Airflow Cooling/Heating
L
m
3
/hr
360
Sound Preesure Level Cooling/Heating
L-H
dB(A)
32-41/32-41
Condensate Drain Tube I.D
mm
16
Dimensions
W/H/D
mm
270×180×790
Weight
kg
12
Packaging Dimensions
W/H/D
mm
875×338×285
IN
D
OOR
Stacking Height
Units
7
Heating Elements
KW
N/A
Moisture Removal
L/hr
1
18 SERVICE MANUAL FOR CMV
2 . 2 . 2 1 C M V - V 2 5 G 3 A / A 7 7 S p e c i f i c a t i o n s
INDOOR UNIT
Model Indoor Unit/Type
CMV-V25G3A/A77
Installation method
Flare
Power Supply
V/Ph/Hz
220-240/1/50
Fan Type & Quantity
Crossflow×1
H
500
M
450
Airflow Cooling/Heating
L
m
3
/hr
360
Sound Preesure Level Cooling/Heating
L-H
dB(A)
32-41/32-41
Condensate Drain Tube I.D
mm
16
Dimensions
W/H/D
mm
270×180×790
Weight
kg
12
Packaging Dimensions
W/H/D
mm
875×338×285
IN
D
OOR
Stacking Height
Units
7
Heating Elements
KW
N/A
Moisture Removal
L/hr
0.8
2 . 2 . 2 2 C M V - V 3 5 G 3 A / A 7 7 S p e c i f i c a t i o n s
INDOOR UNIT
Model Indoor Unit/Type
CMV-V35G3A/A27
Installation method
Flare
Power Supply
V/Ph/Hz
220-240/1/50
Fan Type & Quantity
Crossflow×1
H
550
M
450
Airflow Cooling/Heating
L
m
3
/hr
360
Sound Preesure Level Cooling/Heating
L-H
dB(A)
32-41/32-41
Condensate Drain Tube I.D
mm
16
Dimensions
W/H/D
mm
270×180×790
Weight
kg
12
Packaging Dimensions
W/H/D
mm
875×338×285
IN
D
OOR
Stacking Height
Units
7
Heating Elements
KW
N/A
Moisture Removal
L/hr
1
19 SERVICE MANUAL FOR CMV
2 . 2 . 2 3 C M V - V 5 0 G 3 A / H 2 7 S p e c i f i c a t i o n s
INDOOR UNIT
Model Indoor Unit/Type
CMV-V50G3A/H27
Installation method
Flare
Power Supply
V/Ph/Hz
220-240/1/50
Fan Type & Quantity
Crossflow×1
H
750
M
550
Airflow Cooling/Heating
L
m
3
/hr
450
Sound Preesure Level Cooling/Heating
L-H
dB(A)
35-43/35-43
Condensate Drain Tube I.D
mm
16
Dimensions
W/H/D
mm
930×270×180
Weight
kg
14
Packaging Dimensions
W/H/D
mm
1010×360×280
IN
D
OOR
Stacking Height
Units
7
Heating Elements
KW
N/A
Moisture Removal
L/hr
1.2
2 . 2 . 2 3 C M V - V 5 0 G 3 A / H 7 7 S p e c i f i c a t i o n s
INDOOR UNIT
Model Indoor Unit/Type
CMV-V50G3A/H77
Installation method
Flare
Power Supply
V/Ph/Hz
220-240/1/50
Fan Type & Quantity
Crossflow×1
H
750
M
550
Airflow Cooling/Heating
L
m
3
/hr
450
Sound Preesure Level Cooling/Heating
L-H
dB(A)
35-43/35-43
Condensate Drain Tube I.D
mm
16
Dimensions
W/H/D
mm
930×270×180
Weight
kg
14
Packaging Dimensions
W/H/D
mm
1010×360×280
IN
D
OOR
Stacking Height
Units
7
Heating Elements
KW
N/A
Moisture Removal
L/hr
1.2
20 SERVICE MANUAL FOR CMV
2 . 2 . 2 4 C M V - V 5 0 G 3 A / H 4 8 S p e c i f i c a t i o n s
INDOOR UNIT
Model Indoor Unit/Type
CMV-V50G3A/H48
Installation method
Flare
Power Supply
V/Ph/Hz
220-240/1/50
Fan Type & Quantity
Crossflow×1
H
750
M
550
Airflow Cooling/Heating
L
m
3
/hr
450
Sound Preesure Level Cooling/Heating
L-H
dB(A)
35-43/35-43
Condensate Drain Tube I.D
mm
16
Dimensions
W/H/D
mm
930×270×180
Weight
kg
14
Packaging Dimensions
W/H/D
mm
1010×360×280
IN
D
OOR
Stacking Height
Units
7
Heating Elements
KW
N/A
Moisture Removal
L/hr
1.2
2 . 2 . 2 5 C M V - V 5 0 G 3 A / H 6 9 S p e c i f i c a t i o n s
INDOOR UNIT
Model Indoor Unit/Type
CMV-V50G3A/H69
Installation method
Flare
Power Supply
V/Ph/Hz
220-240/1/50
Fan Type & Quantity
Crossflow×1
H
750
M
550
Airflow Cooling/Heating
L
m
3
/hr
450
Sound Preesure Level Cooling/Heating
L-H
dB(A)
35-43/35-43
Condensate Drain Tube I.D
mm
16
Dimensions
W/H/D
mm
930×270×180
Weight
kg
14
Packaging Dimensions
W/H/D
mm
1010×360×280
IN
D
OOR
Stacking Height
Units
7
Heating Elements
KW
N/A
Moisture Removal
L/hr
1.2
21 SERVICE MANUAL FOR CMV
3 . R A T I N G
C O N D I T I O N S
Standard conditions in accordance with ISO 5151, and EN 14511.
Cooling:
Indoor: 27
o
C DB 19
o
C WB
Outdoor: 35
o
C DB 24
o
C WB
Heating:
Indoor: 20
o
C DB 15
o
C WB
Outdoor: 7
o
C DB 6
o
C WB
3 . 1 O p e r a t i n g
L i m i t s
Outdoor
Upper limit (DB)
46
o
C
Cooling
Lower limit (DB)
10
o
C
Upper limit (DB)
24
o
C
Heating
Lower limit (DB)
-15
o
C
2PH 198–264V
Voltage
3PH N/A
22 SERVICE MANUAL FOR CMV
4 . O U T L I N E
D I M E N S I O N S
4.1 outdoor Unit: CMV-V40H13AD
4.2 outdoor Unit: CMV-50V3A-E2
23 SERVICE MANUAL FOR CMV
4.3 outdoor Unit: CMV-V80WC3AQ, CMV-71V3A-T
560
37
8
34
2
84
5
35
1
72
50
956
82
5
50
×3
(=1
50)
50
5 . P E R F O R M A N C E
D A T A
5 . 1 O u t d o o r u n i t s d a t a
5 . 1 . 1
CMV-V40H13AD
C o m b i n a t i o n s ( b a s e d o n s p l i t i n d o o r u n i t s )
Data For Outdoor Unit CMV-V40H13AD Combinations (Based on Split indoor units)
Cooling
Heating
RoomA RoomB
Total
Capacity
Power
Input
RoomA
RoomB
Total
Capacity
Power Input
Indoor Units
Combinations
[W]
[W]
[W]
[W]
[W]
[W]
[W]
[W]
20
2000
*
2000
(1450-3200)
540
(450-1050)
2500
*
2500
(1500-3200)
690
(430-940)
25
2500
*
2500
(1450-3350)
710
(450-1140)
3000
*
3000
(1500-3400)
840
(430-990)
35
3500
*
3500
(1450-4700)
1020
(450-1250)
3500
*
3500
(1450-3800)
950
(450-1100)
20+20
2000
2000
4000
(1450-5200)
1020
(450-1550)
2300
2300
4600
(1500-5050)
1050
(430-1300)
20+25S
2000
2500
4500
(1450-5200)
1250
(450-1570)
2265
2835
5100
(1500-5300)
1250
(430-1320)
25S+25S
2500
2500
5000
(1450-5200)
1470
(450-1610)
2600
2600
5200
(1500-5300)
1270
(430-1350)
25S+35
2100
2950
5050
(1450-5250)
1480
(450-1620)
2200
3100
5300
(1500-5400)
1290
(430-1380)
24 SERVICE MANUAL FOR CMV
5 . 1 . 2
CMV-50V3A-E2
C o m b i n a t i o n s ( b a s e d o n s p l i t i n d o o r u n i t s )
Data For Outdoor Unit CMV-50V3A-E2 Combinations (Based on Split indoor units)
Cooling
Heating
RoomA RoomB
Total
Capacity
Power Input
RoomA
RoomB
Total
Capacity
Power
Input
Indoor Units
Combinations
[W]
[W]
[W]
[W]
[W]
[W]
[W]
[W]
20
2000
*
2000
(1420-2960)
650
(460-950)
2500
*
2500
(1280-3300)
710
(420-980)
25
2600
*
2600
(1420-3700)
660
(460-990)
3200
*
3200
(1280-3700)
880
(420-1020)
35
3500
*
3500
(1420-4350)
1010
(460-1280)
4200
*
4200
(1300-5200)
1160
(435-1420)
20+20
2150
2150
4300
(1600-6150)
1320
(460-2100)
2550
2550
5100
(1300-6850)
1480
(450-2130)
20+25
2050
2550
4600
(1600-6400)
1380
(460-2130)
2450
3050
5500
(1300-7000)
1470
(450-2100)
25+25
2600
2600
5200
(1600-6800)
1400
(460-2250)
3000
3000
6000
(1300-7300)
1600
(450-2200)
20+35
2040
3050
5600
(1600-6850)
1750
(460-2250)
2450
3050
6200
(1300-7300)
1700
(450-2200)
25+35
2450
3450
5900
(1600-6850)
1820
(460-2260)
3100
3450
6550
(1300-7350)
1850
(450-2220)
35+35
3100
3050
6150
(1600-6880)
1890
(460-2270)
3450
3450
6900
(1300-7400)
1890
(450-2220)
5 . 1 . 3 C M V - 7 1 V 3 A - T C o m b i n a t i o n s ( b a s e d o n s p l i t i n d o o r u n i t s )
Data For Outdoor Unit CMV-71V3A-T Combinations
(Based on Split indoor units)
Cooling
Heating
RoomA RoomB
RoomC
Total
Capacity
Power
Input
RoomA
RoomB
RoomC
Total
Capacity
Power
Input
Indoor Units
Combinations
[W]
[W]
[W]
[W]
[W]
[W]
[W]
[W]
[W]
[W]
20
*
*
2000
2000
(1500-2960)
665
(580-950)
*
*
2500
2500
(1700-3300)
720
(540-940)
25
*
*
2500
2500
(1500-3700)
785
(580-1125)
*
*
3000
3000
(1700-3700)
810
(540-1030)
26
*
*
2600
2600
(1500-3700)
785
(580-1125)
*
*
3000
3000
(1700-3700)
810
(540-1030)
35
*
*
3500
3500
(1600-4350)
1070
(580-1330)
*
*
4300
4300
(2000-5200)
1160
(610-1410)
50
*
*
5000
5000
(1900-5930)
1490
(580-1790)
*
*
6000
6000
(2300-6800)
1600
(690-1860)
20+20
*
2000
2000
4000
(1500-5140)
1250
(580-1650)
*
2800
2800
5600
(2100-6800)
1550
(540-1950)
20+26
*
2000
2600
4600
(1500-5630)
1350
(580-1850)
*
2600
3200
5800
(2200-7300)
1600
(540-2050)
20+35
*
1900
3200
5100
(1500-6100)
1550
(580-2010)
*
2600
3500
7100
(2200-7700)
1950
(540-2250)
20+50
*
1860
4640
6500
(1500-8700)
2100
(580-2900)
*
2450
6050
8500
(1700-9300)
2320
(540-2660)
25 SERVICE MANUAL FOR CMV
25+25
*
2520
2520
5040
(1500-6000)
1480
(580-1770)
*
3000
3000
6000
(1700-7700)
1590
(540-2090)
25+35
*
2510
3390
5900
(1500-7000)
1780
(580-2160)
*
3100
4240
7340
(1700-8300)
1990
(540-2270)
25+50
*
2350
4880
7030
(1500-8900)
2150
(580-2960)
*
2900
5800
8700
(1700-9400)
2370
(540-2660)
26+26
*
2520
2520
5040
(1500-6000)
1480
(580-1770)
*
3000
3000
6000
(1700-7700)
1590
(540-2090)
26+35
*
2550
3350
5900
(1500-7000)
1780
(580-2160)
*
3140
4200
7340
(1700-8300)
1990
(540-2270)
26+50
*
2410
4620
7030
(1500-8900)
2150
(580-2960)
*
3000
5700
8700
(1700-9400)
2370
(540-2660)
35+35
*
3450
3450
6900
(1600-8600)
2120
(580-2860)
*
3900
3900
7800
(2000-8800)
2150
(610-2400)
35+50
*
2960
4280
7040
(1600-8900)
2150
(580-2960)
*
3400
5400
8800
(1700-9500)
2400
(540-2670)
20+20+20
2115
2115
2120
6350
(1500-8500)
1980
(580-2900)
2810
2790
2790
8390
(1700-9800)
2330
(540-3010)
20+20+26
2000
2000
2600
6600
(1500-8700)
2050
(580-2900)
2545
2545
3310
8400
(1700-9850)
2320
(540-3010)
20+20+35
1840
1840
3220
6900
(1500-8700)
2100
(580-2900)
2250
2250
3950
8450
(1700-9900)
2330
(540-3000)
20+20+50
1575
1575
3950
7100
(1500-8900)
2210
(580-2950)
1875
1875
4750
8500
(1700-10350)
2360
(540-3000)
20+26+26
1900
2450
2450
6800
(1500-8800)
2090
(580-2920)
2350
3050
3050
8450
(1700-10400)
2300
(540-3000)
20+26+35
1760
2300
3040
7100
(1500-8800)
2200
(580-2930)
2150
2760
3690
8600
(1700-10500)
2350
(540-3000)
20+26+50
1500
1950
3700
7150
(1500-9000)
2210
(580-2980)
1800
2350
4500
8650
(1700-10600)
2380
(540-3010)
20+35+35
1580
2760
2760
7100
(1500-8850)
2210
(580-2940)
1900
3350
3350
8600
(1700-10400)
2380
(540-3000)
20+35+50
1370
2400
3420
7190
(1500-9000)
2220
(580-2980)
1660
2900
4140
8700
(1700-10500)
2390
(540-3020)
25+25+25
2350
2350
2400
7100
(1500-9000)
2200
(580-2980)
2820
2820
2860
8500
(1700-10500)
2330
(540-3000)
25+25+35
2200
2200
2830
7230
(1500-9000)
2250
(580-2970)
2500
2500
3700
8700
(1700-10500)
2380
(540-3000)
25+25+50
1810
1810
3630
7250
(1500-9000)
2260
(580-2990)
2150
2150
4400
8700
(1700-10700)
2400
(540-3010)
25+35+35
1950
2650
2650
7250
(1500-9000)
2260
(580-2970)
2400
3150
3150
8700
(1700-10500)
2380
(540-3000)
25+35+50
1660
2230
3370
7260
(1500-9000)
2280
(580-2990)
2020
2760
4020
8800
(1700-10700)
2410
(540-3020)
26+26+26
2365
2365
2370
7100
(1500-9000)
2200
(580-2980)
2840
2830
2830
8500
(1700-10500)
2330
(540-3000)
26+26+35
2160
2160
2910
7230
(1500-9000)
2250
(580-2970)
2600
2600
3500
8700
(1700-10500)
2380
(540-3000)
26+26+50
1850
1850
3550
7250
(1500-9000)
2260
(580-2990)
2220
2220
4260
8700
(1700-10700)
2400
(540-3010)
26+35+35
1950
2650
2650
7250
(1500-9000)
2260
(580-2970)
2400
3150
3150
8700
(1700-10500)
2380
(540-3000)
26+35+50
1700
2300
3280
7280
(1500-9000)
2270
(580-2990)
2060
2780
3960
8800
(1700-10700)
2410
(540-3020)
35+35+35
2410
2410
2410
7230
(1500-9000)
2270
(580-2980)
2850
2850
2850
8550
(2000-10500)
2340
(610-3000)
26 SERVICE MANUAL FOR CMV
5 . 1 . 4 C M V - V 8 0 W C 3 A Q C o m b i n a t i o n s ( b a s e d o n s p l i t i n d o o r u n i t s )
Data For Outdoor Unit CMV-V80WC3AQ Combinations
(Based on Split indoor units)
Cooling
Heating
RoomA RoomB RoomC RoomD
Total
Capacity
Power
Input
RoomA
RoomB
RoomC RoomD
Total
Capacity
Power
Input
Indoor Units
Combinations
[W]
[W]
[W]
[W]
[W]
[W]
[W]
[W]
[W]
[W]
[W]
[W]
20
*
*
*
2000
2000
(1800-2960)
720
(710-1050)
*
*
*
2800
2800
(2000-3300)
930
(910-1050)
26
*
*
*
2600
2600
(1800-3700)
785
(710-1200)
*
*
*
3200
3200
(2000-3700)
970
(910-1170)
35
*
*
*
3500
3500
(1800-4300)
1050
(710-1400)
*
*
*
4300
4300
(2000-5200)
1210
(910-1630)
50
*
*
*
5000
5000
(1800-5900)
1530
(710-1890)
*
*
*
6000
6000
(2200-6800)
1660
(890-1920)
20+20
*
*
2175
2175
4350
(1800-5800)
1350
(710-1890)
*
*
2850
2850
5700
(2000-6700)
1580
(910-1950)
20+26
*
*
2000
2600
4600
(1800-5800)
1430
(710-1900)
*
*
2520
3280
5800
(2000-7000)
1610
(910-1950)
20+35
*
*
2000
3500
5500
(1800-6300)
1700
(710-2050)
*
*
2220
3880
6100
(2000-8000)
1690
(910-2270)
20+50
*
*
1970
4930
6900
(1800-8500)
2150
(710-2950)
*
*
2370
5930
8300
(2000-8500)
2250
(910-2400)
26+26
*
*
2600
2600
5200
(1800-6000)
1510
(710-1920)
*
*
3000
3000
6000
(2000-7000)
1580
(910-1990)
26+35
*
*
2590
3490
6080
(1800-6800)
1840
(710-2200)
*
*
2680
3600
6280
(2000-8200)
1680
(910-2260)
26+50
*
*
2390
4610
7000
(1800-8600)
2170
(710-3020)
*
*
2900
5590
8490
(2000-8900)
2210
(910-2400)
35+35
*
*
3430
3430
6860
(1800-8450)
2130
(710-2880)
*
*
4040
4040
8080
(2000-8500)
1920
(910-2340)
35+50
*
*
2910
4160
7070
(1800-8700)
2180
(710-3050)
*
*
3570
5110
8680
(2000-8900)
2240
(910-2480)
20+20+20
*
2130
2130
2140
6400
(1800-8600)
2000
(710-3050)
*
2780
2780
2790
8350
(2000-8900)
2300
(910-2600)
20+20+26
*
2000
2000
2600
6600
(1800-8600)
2050
(710-3040)
*
2545
2545
3310
8400
(2000-8900)
2290
(910-2600)
20+20+35
*
1890
1890
3320
7100
(1800-8600)
2200
(710-3050)
*
2255
2255
3940
8450
(2000-8900)
2290
(910-2600)
20+20+50
*
1620
1620
4060
7300
(1800-8900)
2280
(710-3080)
*
1900
1900
4750
8550
(2000-9200)
2280
(910-2650)
20+26+26
*
1960
2545
2545
7050
(1800-8600)
2200
(710-3030)
*
2330
3035
3035
8400
(2000-9000)
2280
(910-2550)
20+26+35
*
1800
2340
3160
7300
(1800-8700)
2270
(710-3040)
*
2110
2745
3695
8550
(2000-9000)
2270
(910-2530)
20+26+50
*
1520
1980
3800
7300
(1800-8900)
2280
(710-3100)
*
1800
2340
4510
8650
(2000-9700)
2250
(910-2650)
20+35+35
*
1620
2840
2840
7300
(1800-8800)
2280
(710-3080)
*
1910
3345
3345
8600
(2000-8900)
2260
(910-2620)
20+35+50
*
1410
2470
3520
7400
(1800-9000)
2300
(710-3090)
*
1660
2900
4140
8700
(2000-9700)
2250
(910-2670)
26+26+26
*
2400
2400
2400
7200
(1800-9000)
2250
(710-3160)
*
2940
2940
2940
8820
(2000-9200)
2250
(850-2580)
26+26+35
*
2200
2200
2970
7370
(1800-9000)
2260
(710-3160)
*
2640
2640
3550
8830
(2000-9300)
2250
(850-2580)
26+26+50
*
1905
1905
3670
7480
(1800-9100)
2300
(710-3180)
*
2260
2260
4350
8870
(2000-9800)
2270
(850-2650)
26+35+35
*
2010
2705
2705
7420
(1800-9000)
2290
(710-3160)
*
2400
3225
3225
8850
(2000-9350)
2260
(850-2610)
26+35+50
*
1840
2480
3540
7860
(1800-9100)
2320
(710-3190)
*
2080
2805
4005
8890
(2000-9800)
2280
(850-2660)
35+35+35
*
2570
2570
2570
7710
(1800-9040)
2300
(710-3200)
*
2960
2960
2970
8890
(2000-10200)
2270
(850-2780)
35+35+50
*
2305
2305
3290
7900
(1800-9100)
2330
(710-3190)
*
2595
2595
3710
8900
(2000-10200)
2280
(850-2780)
20+20+20+20
1920
1920
1920
1920
7680
(1800-9300)
2400
(710-3290)
2300
2300
2300
2300
9200
(2000-10600)
2550
(850-3100)
20+20+20+26
1800
1800
1800
2350
7750
(1800-9300)
2420
(710-3290)
2160
2160
2160
2820
9300
(2000-10700)
2530
(850-3100)
27 SERVICE MANUAL FOR CMV
20+20+20+35
1650
1650
1650
6190
7840
(1800-9300)
2440
(710-3290)
1970
1970
1970
3440
9350
(2000-10700)
2530
(850-3100)
20+20+20+50
1430
1430
1430
3590
7880
(1800-9350)
2460
(710-3300)
1720
1720
1720
4290
9450
(2000-11000)
2520
(850-3050)
20+20+26+26
1700
1700
2215
2215
7830
(1800-9300)
2440
(710-3290)
2075
2075
2700
2700
9550
(2000-11000)
2500
(850-3050)
20+20+26+35
1565
1565
2030
2740
7900
(1800-9300)
2460
(710-3290)
1905
1905
2480
3340
9630
(2000-11000)
2500
(850-3050)
20+20+25+50
1390
1390
1740
3480
8000
(1800-9350)
2490
(710-3300)
1690
1690
2105
4215
9700
(2000-11000)
2490
(850-3050)
20+20+35+35
1450
1450
2550
2550
8000
(1800-9300)
2480
(710-3290)
1760
1760
3080
3080
9680
(2000-11000)
2500
(850-3050)
20+20+35+50
1310
1310
2240
3240
8100
(1800-9400)
2520
(710-3300)
1560
1560
2720
3890
9730
(2000-11000)
2490
(850-3050)
20+26+26+26
1600
2100
2100
2100
7900
(1800-9400)
2460
(710-3290)
1970
2560
2560
2560
9650
(2000-11000)
2490
(850-3050)
20+26+26+35
1480
1935
1935
2600
7950
(1800-9400)
2480
(710-3290)
1810
2350
2350
3170
9680
(2000-11000)
2490
(850-3050)
20+26+26+50
1300
1725
1725
3300
8050
(1800-9400)
2510
(710-3300)
1585
2070
2070
3975
9700
(2000-11000)
2480
(850-3050)
20+26+35+35
1380
1790
2400
2400
7970
(1800-9400)
2490
(710-3290)
1670
2170
2925
2925
9690
(2000-11000)
2470
(850-3050)
20+26+35+50
1230
1600
2150
3080
8060
(1800-9400)
2510
(710-3350)
1480
1925
2590
3705
9700
(2000-11000)
2470
(850-3050)
20+35+35+35
1310
2250
2250
2250
8020
(1800-9400)
2490
(710-3350)
1555
2715
2715
2715
9700
(2000-11000)
2460
(850-3050)
25+25+25+25
2000
2000
2000
2000
8000
(1800-9400)
2450
(710-3350)
2400
2400
2400
2400
9600
(2000-11000)
2400
(910-3050)
25+25+25+35
1870
1870
1870
2490
8100
(1800-9400)
2470
(710-3350)
2195
2195
2195
3065
9650
(2000-11000)
2400
(910-3050)
25+25+25+50
1610
1610
1610
3280
8110
(1800-9400)
2480
(710-3350)
1950
1950
1950
3930
9780
(2000-11000)
2460
(910-3050)
25+25+35+35
1720
1720
2340
2340
8120
(1800-9400)
2460
(710-3350)
2065
2065
2800
2800
9730
(2000-11000)
2440
(910-3050)
25+25+35+50
1520
1520
2040
3020
8100
(1800-9400)
2480
(710-3350)
1800
1800
2430
3750
9780
(2000-11000)
2460
(910-3050)
25+35+35+35
1620
2160
2160
2160
8110
(1800-9400)
2480
(710-3350)
1930
2600
2600
2600
9730
(2000-11000)
2450
(910-3050)
35+35+35+35
2030
2030
2030
2030
8120
(1800-9400)
2490
(710-3350)
2425
2425
2425
2425
9700
(2000-11000)
2470
(910-3050)
5.2 Indoor Units Data
5.2.1 Indoor Units Capacity For 2.5KW
Capacity
Model
CMVS-25V3A-A38A
CMVS-25V3A-A38B
CMVS-25V3A-A48A
CMVS-25V3A-A69A
CMVS-25V3A-A46A
CMV-V25G3A/A67
CMV-V25G3A/A78
CMV-V25G3A/A27
2.5KW
CMV-V25G3A/A77
28 SERVICE MANUAL FOR CMV
5.2.1.1
Cooling Capacity (KW)---Run Model (Unit A,B,C or D),230V,Indoor fan at
high speed
INDOOR ENTERING AIR DB/WB TEMPERATURE [
0
C]
OUTDOOR
ENTERING AIR DB
TEMPERATURE
[
0
C] DATA
22/15
24/17
27/19
29/21
32/23
TC
80 - 110 % of nominal
-10 - 20
SC
80 - 105 % of nominal
(protection range)
PI
25 - 50 % of nominal
TC 2.42 2.57 2.73 2.89 3.05
25
SC 1.72 1.75 1.79 1.82 1.86
PI 0.58 0.59 0.60 0.61 0.62
TC 2.30 2.46 2.62 2.77 2.93
30
SC 1.67 1.71 1.74 1.78 1.81
PI 0.65 0.66 0.67 0.68 0.69
TC 2.18 2.34 2.50 2.66 2.82
35
SC 1.63 1.66 1.70 1.74 1.77
PI 0.71 0.72 0.74 0.75 0.76
TC 2.07 2.23 2.38 2.54 2.70
40
SC 1.59 1.62 1.66 1.69 1.73
PI 0.78 0.79 0.80 0.81 0.82
TC 1.93 2.09 2.24 2.40 2.56
46
SC 1.53 1.57 1.60 1.64 1.67
PI 0.86 0.87 0.88 0.89 0.91
L E G E N D
TC – Total Cooling Capacity, kW
SC – Sensible Capacity, Kw
PI – Power Input, kW
WB – Wet Bulb Temp., (
o
C)
DB – Dry Bulb Temp., (
o
C)
ID – Indoor
OD – Outdoor
29 SERVICE MANUAL FOR CMV
5.2.1.2
Heating Capacity (KW)---Run Model (Unit A,B,C or D),230V,Indoor fan at
high speed
ID COIL ENTERING AIR DB TEMPERATURE [
0
C]
OD COIL
ENTERING
AIR DB/WB
TEM PERATU RE
[
0
C]
DATA 15
20
25
-15/-16
TC
1.92 1.77 1.65
PI 0.49
0.54
0.59
-10/-12
TC 2.13
1.98
1.86
PI
0.59 0.64 0.70
-7/-8
TC 2.28
2.16
2.01
PI
0.67
0.72
0.77
-1/-2
TC 2.37
2.25
2.10
PI
0.71 0.75 0.80
2/1
TC
2.43 2.28 2.16
PI
0.73
0.78
0.83
7/6
TC
3.12 3.00 2.88
PI
0.77 0.82 0.87
10/9
TC
3.30 3.18 3.03
PI
0.82
0.87
0.92
15/12
TC
3.48 3.36 3.21
PI
0.86
0.90
0.96
15-24
TC
85 - 105 % of nominal
(Protection Range)
PI
80 - 120 % of nominal
5.2.1.3 Capacity
Correction
Factors
Cooling Capacity Ratio Vs. Outdoor Temperature
Cooling Capacity Correction Factor
0
0.2
0.4
0.6
0.8
1
1.2
1.4
25
30
35
40
45
Outdoor Temperature (deg C)
Capacity Ratio
32/23
29/27
27/19
24/17
22/15
30 SERVICE MANUAL FOR CMV
Heating Capacity Ratio Vs. Outdoor Temperature
Heating Capacity Correction Factor
0
0.2
0.4
0.6
0.8
1
1.2
1.4
-15
-10
-5
0
5
10
15
20
Outdoor Temperature (deg C)
Capacity Ratio
15
20
25
5.2.2 Indoor Units Capacity For 3.5KW
5.2.2 Indoor
Units
Capac
ity For
3.5KW
Capacity
Model
CMVS-35V3A-A38A
CMVS-35V3A-A38B
CMVS-35V3A-A48A
CMVS-35V3A-A69A
CMVS-35V3A-A46A
CMV-V35G3A/A67
CMV-V35G3A/A78
CMV-V35G3A/A27
3.5KW
CMV-V35G3A/A77
31 SERVICE MANUAL FOR CMV
5.2.2.1
Cooling Capacity (KW)---Run Model (Unit A,B,C or D),230V,Indoor fan at
high speed
INDOOR ENTERING AIR DB/WB TEMPERATURE [
0
C]
OUTDOOR
ENTERING AIR DB
TEMPERATURE
[
0
C] DATA
22/15
24/17
27/19
29/21
32/23
TC
80 - 110 % of nominal
-10 - 20
SC
80 - 105 % of nominal
(protection range)
PI
25 - 50 % of nominal
TC
3.40
3.61
3.82
4.06
4.27
25
SC
3.03
3.09
3.15
3.21
3.27
PI
0.86
0.87
0.89
0.90
0.93
TC
3.22
3.43
3.68
3.89
4.10
30
SC
2.94
3.00
3.09
3.15
3.21
PI
0.96
0.97
0.99
1.00
1.02
TC
3.05
3.29
3.50
3.71
3.96
35
SC
2.88
2.94
3.00
3.06
3.12
PI
1.06
1.08
1.09
1.11
1.12
TC
2.91
3.12
3.33
3.57
3.78
40
SC
2.79
2.85
2.91
3.00
3.06
PI
1.16
1.18
1.19
1.21
1.22
TC
2.70
2.91
3.15
3.36
3.57
46
SC
2.70
2.76
2.82
2.88
2.97
PI
1.28
1.30
1.31
1.33
1.34
5.2.2.2
Heating Capacity (KW)---Run Model (Unit A,B,C or D),230V,Indoor fan at
high speed
ID COIL ENTERING AIR DB TEMPERATURE [
0
C]
OD COIL
ENTERING
AIR DB/WB
TEM PERATU RE
[
0
C]
DATA 15
20
25
-15/-16
TC
2.56
2.36
2.20
PI
0.67
0.73
0.80
-10/-12
TC
2.84
2.64
2.48
PI
0.80
0.87
0.94
-7/-8
TC
3.04
2.88
2.68
PI
0.91
0.98
1.04
-1/-2
TC
3.16
3.00
2.80
PI
0.95
1.02
1.09
2/1
TC
3.24
3.04
2.88
PI
0.99
1.05
1.12
7/6
TC
4.16
4.00
3.84
PI
1.04
1.11
1.18
10/9
TC
4.40
4.24
4.04
PI
1.11
1.18
1.24
15/12
TC
4.64
4.48
4.28
PI
1.17
1.23
1.30
15~24
TC
85 - 105 % of nominal
(Protection Range)
PI
80 - 120 % of nominal
32 SERVICE MANUAL FOR CMV
5.2.2.3 Capacity
Correction
Factors
Cooling Capacity Ratio Vs. Outdoor Temperature
Cooling Capacity Correction Factor
0
0.2
0.4
0.6
0.8
1
1.2
1.4
25
30
35
40
45
Outdoor Temperature (deg C)
Capacity Ratio
32/23
29/27
27/19
24/17
22/15
Heating Capacity Ratio Vs. Outdoor Temperature
Heating Capacity Correction Factor
0
0.2
0.4
0.6
0.8
1
1.2
1.4
-15
-10
-5
0
5
10
15
20
Outdoor Temperature (deg C)
Capacity Ratio
15
20
25
5.2.3 Indoor Units Capacity For 5.0KW
Capacity
Model
CMV-V50G3A/H38A
CMVS-50V3A-N46A
CMVS-50V3A-N17A
CMV-V50G3A/H27
CMV-V50G3A/H69
CMV-V50G3A/H48
5.0KW
CMV-V50G3A/H77
33 SERVICE MANUAL FOR CMV
5.2.3.1 Cooling Capacity (KW)---Run Model (Unit A,B,C or D),230V,Indoor fan at high
speed
INDOOR ENTERING AIR DB/WB TEMPERATURE [
0
C]
OUTDOOR
ENTERING AIR DB
TEMPERATURE
[
0
C] DATA
22/15
24/17
27/19
29/21
32/23
TC
80 - 110 % of nominal
-10 - 20
SC
80 - 105 % of nominal
(protection range)
PI
25 - 50 % of nominal
TC
4.85
5.15
5.45
5.80
6.10
25
SC
4.55
4.64
4.73
4.82
4.91
PI
1.23
1.25
1.28
1.29
1.33
TC
4.60
4.90
5.25
5.55
5.85
30
SC
4.41
4.50
4.64
4.73
4.82
PI
1.37
1.39
1.42
1.44
1.47
TC
4.35
4.70
5.00
5.30
5.65
35
SC
4.32
4.41
4.50
4.59
4.68
PI
1.51
1.54
1.56
1.59
1.61
TC
4.15
4.45
4.75
5.10
5.40
40
SC
4.19
4.28
4.37
4.50
4.59
PI
1.65
1.68
1.70
1.73
1.75
TC
3.85
4.15
4.50
4.80
5.10
46
SC
4.05
4.14
4.23
4.32
4.46
PI
1.83
1.86
1.87
1.90
1.92
5.2.3.2 Heating Capacity (KW)---Run Model (Unit A,B,C or D),230V,Indoor fan at
high speed
ID COIL ENTERING AIR DB TEMPERATURE [
0
C]
OD COIL
ENTERING
AIR DB/WB
TEM PERATU RE
[
0
C]
DATA 15
20
25
-15/-16
TC
3.71
3.42
3.19
PI
0.97
1.06
1.16
-10/-12
TC
4.12
3.83
3.60
PI
1.16
1.26
1.37
-7/-8
TC
4.41
4.18
3.89
PI
1.32
1.42
1.51
-1/-2
TC
4.58
4.35
4.06
PI
1.38
1.48
1.58
2/1
TC
4.70
4.41
4.18
PI
1.43
1.53
1.63
7/6
TC
6.03
5.80
5.57
PI
1.51
1.61
1.71
10/9
TC
6.38
6.15
5.86
PI
1.61
1.71
1.80
15/12
TC
6.73
6.50
6.21
PI
1.69
1.79
1.88
15-24
TC
85 - 105 % of nominal
(Protection Range)
PI
80 - 120 % of nominal
34 SERVICE MANUAL FOR CMV
5.2.3.3 Capacity
Correction
Factors
Cooling Capacity Ratio Vs. Outdoor Temperature
Cooling Capacity Correction Factor
0
0.2
0.4
0.6
0.8
1
1.2
1.4
25
30
35
40
45
Outdoor Temperature (deg C)
Capacity Ratio
32/23
29/27
27/19
24/17
22/15
Heating Capacity Ratio Vs. Outdoor Temperature
Heating Capacity Correction Factor
0
0.2
0.4
0.6
0.8
1
1.2
1.4
-15
-10
-5
0
5
10
15
20
Outdoor Temperature (deg C)
Capacity Ratio
15
20
25
5.2.4
Indoor Units Capacity For 2.0KW
Capacity
Model
2.0KW
CMV-V20G3A/G38A
35 SERVICE MANUAL FOR CMV
5.2.4.1
Cooling Capacity (KW)---Run Model (Unit A,B,C or D),230V,Indoor fan at
high speed
INDOOR ENTERING AIR DB/WB TEMPERATURE [
0
C]
OUTDOOR
ENTERING AIR DB
TEMPERATURE
[
0
C] DATA
22/15
24/17
27/19
29/21
32/23
TC
80 - 110 % of nominal
SC
80 - 105 % of nominal
-10 - 20
(protection range)
PI
25 - 50 % of nominal
TC
1.94
2.06
2.18
2.32
2.44
SC
1.72
1.75
1.79
1.82
1.85
25
PI
0.49
0.50
0.51
0.51
0.53
TC
1.84
1.96
2.10
2.22
2.34
SC
1.67
1.70
1.75
1.79
1.82
30
PI
0.55
0.55
0.56
0.57
0.58
TC
1.74
1.88
2.00
2.12
2.26
SC
1.63
1.67
1.70
1.73
1.77
35
PI
0.60
0.61
0.62
0.63
0.64
TC
1.66
1.78
1.90
2.04
2.16
SC
1.58
1.62
1.65
1.70
1.73
40
PI
0.66
0.67
0.68
0.69
0.69
TC
1.54
1.66
1.80
1.92
2.04
SC
1.53
1.56
1.60
1.63
1.68
46
PI
0.73
0.74
0.74
0.76
0.76
5.2.4.2
Heating Capacity (KW)---Run Model (Unit A,B,C or D),230V,Indoor fan at
high speed
ID COIL ENTERING AIR DB TEMPERATURE [
0
C]
OD COIL
ENTERING
AIR DB/WB
TEM PERATU RE
[
0
C]
DATA 15
20
25
-15/-16
TC
1.54
1.42
1.32
PI
0.40
0.44
0.48
-10/-12
TC
1.70
1.58
1.49
PI
0.48
0.52
0.57
-7/-8
TC
1.82
1.73
1.61
PI
0.55
0.59
0.63
-1/-2
TC
1.90
1.80
1.68
PI
0.58
0.62
0.66
2/1
TC
1.94
1.82
1.73
PI
0.60
0.64
0.68
7/6
TC
2.50
2.40
2.30
PI
0.63
0.67
0.71
10/9
TC
2.64
2.54
2.42
PI
0.67
0.71
0.75
15/12
TC
2.78
2.69
2.57
PI
0.70
0.74
0.78
15~24
TC
85 - 105 % of nominal
(Protection Range)
PI
80 - 120 % of nominal
36 SERVICE MANUAL FOR CMV
5.2.4.3 Capacity
Correction
Factors
Cooling Capacity Ratio Vs. Outdoor Temperature
Cooling Capacity Correction Factor
0
0.2
0.4
0.6
0.8
1
1.2
1.4
25
30
35
40
45
Outdoor Temperature (deg C)
Capacity Ratio
32/23
29/27
27/19
24/17
22/15
Heating Capacity Ratio Vs. Outdoor Temperature
Heating Capacity Correction Factor
0
0.2
0.4
0.6
0.8
1
1.2
1.4
-15
-10
-5
0
5
10
15
20
Outdoor Temperature (deg C)
Capacity Ratio
15
20
25
37 SERVICE MANUAL FOR CMV
5.3 Capacity Correction Factor Due to Tubing Length (One Way)
5.3.1 Indoor units Model
CMVS-25V3A-A38A
CMVS-35V3A-A38A
CMV-V20G3A/G38A
CMV-V50G3A/H38A
CMVS-25V3A-A38B
CMVS-35V3A-A38B
CMVS-25V3A-A48A
CMVS-35V3A-A48A
CMVS-25V3A-A69A
CMVS-35V3A-A69A
CMVS-25V3A-A46A
CMVS-35V3A-A46A
CMV-V25G3A/A27
CMV-V35G3A/A27
CMV-V25G3A/A77
CMV-V35G3A/A77
CMV-V25G3A/M85
CMV-V35G3A/M85
CMVS-50V3A-N46A
CMVS-50V3A-N17A
CMV-V25G3A/A67
CMV-V35G3A/A67
CMV-V25G3A/A78
CMV-V35G3A/A78
CMV-V50G3A/H27
CMV-V50G3A/H69
CMV-V50G3A/H48
CMV-V50G3A/H77
5.3.1.1 Cooling
5.3.1.2 Heating
38 SERVICE MANUAL FOR CMV
6. Pressure Curve
6.1 Model
CMV-50V3A-E2
CMV-71V3A-T CMV-V80WC3AQ
CMV-V40H13AD
6.1.1 Cooling--------------Test Model
6.1.2 Heating-----------Test Model
39 SERVICE MANUAL FOR CMV
7 . E L E C T R I C A L
D A T A
Model
CMV-50V3A-E2
Power Supply
1 PH, 220-240 VAC, 50Hz
Connected to
Outdoor
Maximum Current
11 A
Inrush Current
35A
Starting Current
1A
Circuit breaker
20A
Power supply wiring - No. x cross section
1 X 3 X 2.5 mm
2
Interconnecting cable - No. x cross section
2 X 4 X 1 mm
2
Model
CMV-71V3A-T
Power Supply
1 PH, 220-240 VAC, 50Hz
Connected to
Outdoor
Maximum Current
16A
Inrush Current
35A
Starting Current
2A
Circuit breaker
20A
Power supply wiring - No. x cross section
1 X 3 X 2.5 mm
2
Interconnecting cable - No. x cross section
3X 4 X 1 mm
2
Model
CMV-V80WC3AQ
Power Supply
1 PH, 220-240 VAC, 50Hz
Connected to
Outdoor
Maximum Current
16A
Inrush Current
35A
Starting Current
2A
Circuit breaker
20A
Power supply wiring - No. x cross section
1 X 3 X 2.5 mm
2
Interconnecting cable - No. x cross section
3X 4 X 1 mm
2
Model
CMV-V40H13AD
Power Supply
1 PH, 220-240 VAC, 50Hz
Connected to
Outdoor
Maximum Current
8 A
Inrush Current
35A
Starting Current
1A
Circuit breaker
20A
Power supply wiring - No. x cross section
1 X 3 X1.5 mm
2
Interconnecting cable - No. x cross section
2 X 4 X 1 mm
2
Note:
Inrush current is the current when power is up. (charging the DC capacitors at outdoor unit
controller).
Starting current is the current when starting the compressor
NOTE
Power wiring cord should comply with local lows and electrical regulations
requirements.
40 SERVICE MANUAL FOR CMV
8 . W I R I N G
D I A G R A M S
8 . 1 C M V - 5 0 V 3 A - E 2
C M V - V 4 0 H 1 3 A D
CN13
CN12
CN1
CN6
SW
SC
N
2
.5
-2
P
C
N
15
V
H
3
.9
6
-4P
CN7
CN8
WH
RD
RD
COM
953-1A-12DB
NO
CN5
P
U
V
W
N
BR
BK
BL
CN9
RD
BR
BK
RD
OR
YL
BK
YL
OR
RD
BR
RD
WH
IA
1
IA
2
IA
3
IA
4
CN1
BK
WH
To compressor
temperature protector
RD
WH
EARTH
AC-N
AC-L
WB1021B8004
MBZ102B120
3
VB109B3118
BL
RD
AC-L
AC-N
L
2
N
WH
RD
ZB102B9108
COMPRESSOR
BL
RD
N
N
A
S
A
L
B
N
B
S
B
L
A
BR
BL
BK
HI
N
ME
D
LOW
F
o
u
r-p
o
sitio
n
Va
lv
e
Expansion Valve:B Expansion Valve:A
1
2
1
5
L
1
p
AC-N
AC-L
AC-L1
AC-N1
AC-N1
AC-N
AC-L
BK
BK
BK
WH
CN10
L
3
2
BK
WH
1
BR
BR
BK
WH
P
N
BK
UF-1330A
Y/G
BL
RD
RD
BL
HT225-15-L8-H2
CN1
SB
SA
AC-L
AC-N
reactor
AC-L1
T3
T1
T2
T4
simulant quantity input:
IA4: inspiration temperature
IA3:condensator midpiont
temperature
IA2:outside temperature
IA1:exhaust temperature
others:
Y/G
Y/G
WH
GR
RD
RD
GR
ZB102B9108:PFC board
WB1021B8004:filter board
VB109B3118:IPM board
MBZ102B1203:mainboard
HT225-15-L8-H2:filter
WIRE COLOUR:
BL(BLUE),BK(BLACK),
BR(BROWN),RD(RED),
GR(GREEN),YL(YELLOW),
Y/G(YELLOW/GREEN),
WH(WHITE),OR(ORANGE)
YL
BK
BL
WH
8 . 2 C M V - V 8 0 W C 3 A
W i r i n g D i a g r a m
41 SERVICE MANUAL FOR CMV
8 . 3 C M V - 7 1 V 3 A - T
W i r i n g D i a g r a m
8 . 4 C M V - 5 0 V 3 A - E 2 C M V - V 4 0 H 1 3 A D
I n d o o r - O u t d o o r W i r i n g D i a g r a m
42 SERVICE MANUAL FOR CMV
8 . 5 C M V - 7 1 V 3 A - T I n d o o r - O u t d o o r W i r i n g D i a g r a m
8 . 6 C M V - V 8 0 W C 3 A Q I n d o o r - O u t d o o r W i r i n g D i a g r a m
43 SERVICE MANUAL FOR CMV
9. REFRIGERATION
DIAGRAMS
9 . 1 C M V - 5 0 V 3 A - E 2 R e f r i g e r a t i o n D i a g r a m
9 . 2 C M V - 7 1 V 3 A - T R e f r i g e r a t i o n D i a g r a m
44 SERVICE MANUAL FOR CMV
9 . 3 C M V - V 8 0 W C 3 A Q R e f r i g e r a t i o n D i a g r a m
9 . 4 C M V - V 4 0 H 1 3 A D R e f r i g e r a t i o n D i a g r a m
45 SERVICE MANUAL FOR CMV
1 0 . T U B I N G C O N N E C T I O N S
When the outdoor unit is installed above the indoor unit an oil trap is required every 5m along the suction line at
the lowest point of the riser. Incase the indoor unit is installed above the outdoor, no trap is required
T U B E ( I n c h )
T O R Q U E ( N m )
¼ ” ~ ” ½ ” ~ ” ¾ ”
F l a r e N u t s
11-13
40-45
60-65 70-75
80-85
V a l v e C a p
13-20
13-20
18-25 18-25
40-50
Service Port Cap
11-13 11-13 11-13 11-13 11-13
1.
Valve Protection Cap-end
2.
Refrigerant Valve Port (use Allen wrench to open/close)
3.
Valve Protection Cap
4. Refrigerant
Valve
5.
Service Port Cap
6. Flare
Nut
7.
Unit Back Side
8. Copper
Tube
46 SERVICE MANUAL FOR CMV
1 1 . C O N T R O L S Y S T E M
Function of Inverter indoor unit
一、summary
1. This control is use for DC Multi-Spilt air conditioners.
2. Power of indoor unit supply is 220-240V/50Hz, voltage range is 170V~270V.
3. Control precision of indoor temperature is ±1℃.
4. Indoor fan motor is PG motor.
5. Control accord with :
GB5956-91《safe requirement of air conditioner》
GB7725-2004《air conditioner》;GB3797-87《control equipment of electrical
equipment》
Vibrancy test:frequency 50Hz,acceleration 2.5g
PCB ought to accord with GB4588.1 and GB4588.2
Electromagnetism compatibility ought to accord with relate standard of nation.
二.Base parameter
1. Use condition:ambient temperature -15℃~85℃, relative humidity =30-95%.
2. Receive distance of remote:<10m
3. Angle of remote:<120 degree
4. Control precision of temperature: ±1℃
5. Speed precision of indoor fan motor: ±10RPM
6. Time precision: <0.1%
三.Major function of control
1. Remote
Turn on/off
Mode select
auto
cooling
dehumidify
heating
ventilation
Indoor fan speed select
manual mode: high, middle, low speed
auto mode: accord difference of indoor room temp. and set temp. automatic select.
Temperature setting
Cooling: 16℃――32℃, default is 25℃
Heating : 16℃――32℃, default is 25℃
Dehumidify: default is 25℃ and it can’t adjust.
Auto: default is 25℃ and it can’t adjust.
Ventilation: 16℃――32℃, default is 25℃
Sleeping
It can set or cancel 24HR sleep .
Timer on or timer off
Timer can set 24HR on or off.
47 SERVICE MANUAL FOR CMV
Air flower control.
Turbo running
Hold key
2. Main PCB board
five running modes
Auto, cooling, heating, dehumidify, ventilation.
Timer function
Indoor temperature detect.
Indoor coil temperature detect.
Indoor fan speed control
cooling: turbo/high speed/middle speed/low speed/ lower speed
heating: turbo/high speed/middle speed/low speed/ lower speed
Indicate lamp
green—running indicate
yellow—timer indicate
red—turbo running
green—economic running
Indoor temperature control
Coil pipe of indoor unit overheat protection
Coil pipe of indoor unit anti frost protection
Sleep
Swing
Anti cold air in heating mode
Indoor fan motor protection
Fault display
PG motor speed:
5.0KW:
mode
higher
high
middle
low
lower
Cooling
speed
1350
1250
950
850
750
Heating
speed
1350
1250
950
850
750
3.5KW:
mode
higher
high
middle
low
lower
Cooling
speed
1350
1250
950
850
750
Heating
speed
1350
1250
950
850
750
2.5KW
mode
higher
high
middle
low
lower
Cooling
speed
1250
1150
950
850
750
Heating
speed
1250
1150
950
850
750
48 SERVICE MANUAL FOR CMV
2.0KW:
mode
higher
high
middle
low
lower
Cooling
speed
1250
1150
950
850
750
Heating
speed
1250
1150
950
850
750
四、operating mode
Air conditioner have four operating mode: auto, cooling, dehumidify, heating.
1.Cooling(ΔT=Troom temp.-Tset temp.)
range of set temp. 16℃~32℃;
compressor running as below figure:
compressor
on
CONT 5 MIN
off
-1ºC +1ºC ΔT
It require outdoor unit to reduce power if indoor room temp. continuous less than
set temp. for 5 minutes.
Air blow function:indoor blower fan continuous running 20 seconds at low speed
after air conditioner turn off in cooling mode. if the flap is swing, shutdown the
flap after turn off indoor blower fan.
Indoor blower fan can select one of four speed.
Fan speed is determined by the difference of room temp. and set temp. in auto wind.
speed
high
middle
low
1ºC 3ºC 5ºC ΔT
It have anti freeze protection of indoor coil ,fan motor fault protection, sensor
fault protection, unit abnormal protection in cooling mode.
2.Dehumidify:(ΔT=Troom temp.-Tset temp.)
range of set temp.: default is 25℃ and it can’t change.
The indoor blower fan is running at low speed for thirty seconds after air
conditioner shutdown in dehumidify mode.
The indoor blower fan is running at low speed and it can’t change.
Air conditioner haven’t turbo and economic function in dehumidify mode.
Flap position: flap at 85 degree position and it can’t change.
It require indoor unit to reduce power if indoor room temp. continuous less than
or equal to 15 degree for 5 minutes, when room temp. is more than or equal to 17
degree, it add the power of indoor unit.
3.Heating(ΔT=Troom temp.-Tset temp.)
Range of set temp. 16℃~32℃;
Compressor running as below figure.
49 SERVICE MANUAL FOR CMV
compressor
on
CONT 5 MIN
off
-4℃
-2℃
ΔT
It require outdoor unit to reduce power if indoor room temp. continuous more than
set temp. for 5 minutes.
Indoor blower fan continuous running for 30 seconds at current speed after indoor
unit reduce power.
Indoor blower fan can select one of four speed.
Fan speed is determined by the difference of room temp. and set temp. in auto
wind.(but anti cold wind is prior)
speed
high
middle
low
0ºC 2ºC 3ºC 5ºC ΔT
Anti cold wind:
When air conditioner first power on or change mode, indoor blower fan didn’t running. When
the coil pipe temp. of indoor unit is more than 30℃,start turnning on indoor blower
fan(lower speed).if the coil pipe temp. of indoor unit drop to less than or equal
to 25℃,it shutdown indoor blower fan.
Heat wind control:
If coil pipe temp. of indoor unit is more than or equal to 32℃, indoor blower fan is
running at set speed.
If coil pipe temp. of indoor unit is less than 32℃, indoor blower fan is running as below
figure.
speed
set speed
lower
turn off
25℃ 30℃ 32℃ coil pipe temp.
Note:①When Tp≤30℃,flap is open at 85°and is running at lower speed, when Tp
≥32℃, it is running at set speed and flap revert to prior state.
②If Tp≤25℃,turn off indoor blower fan.
Defrost control
Indoor blower fan turn off when it enter defrost.
Clear quantity of heat
Turn off air conditioner in heating mode, if the coil pipe temp. of indoor unit
is more than 40℃, indoor blower fan is running at low speed. If the coil pipe
temp. of indoor unit is less than or equal to 40℃ or turn off air conditioner
over 2 minutes, It shutdown indoor blower fan.
4. Auto mode
set temp. is 25℃ and it can’t change;
Press emergency key in waiting state or select auto mode by remote, air
conditioner enter auto mode and set temp. is 25℃.
Indoor blower fan is running for 20 seconds at lower speed after select auto
50 SERVICE MANUAL FOR CMV
mode, the running lamp is light, it select correspond running mode accord to room
temp.:
room temp. >26℃, select cooling mode.
room temp. <21℃, select heating mode.
21ºC≤room temp.≤26ºC,select ventilation mode.
When the running mode has confirmed, it can’t change, if it reenter auto mode,
it select running mode again accord to room temp..
When the mode of auto select is clash with other indoor unit running mode:
If it auto select is cooling mode and other indoor unit is running heating mode, then it select
ventilation mode.
If it auto select is heating mode, but other indoor unit is running cooling mode, display error of
mode clash.
if it select is ventilation mode, then it running is ventilation.
5.Ventilation
1) Range of set temp.:16℃-32℃.
2) Indoor blower fan is operate same as cooling mode.
3) Flap is operate same as cooling mode.
4) Indoor unit no power require in ventilation mode.
6. Timer and sleep
timer
Remote can set 1-24 hours timer on or timer off.
Air conditioner is running .
If set timer off, air conditioner is continuous running and display timer time, when timer time is
end, it shutdown air conditioner.
air conditioner is shutdown .
If set timer on, air conditioner at waiting state, it display timer time. when timer time is end, it
turn on air conditioner.
when it set timer , the timer lamp is light and display set temp.
sleep
If set sleep, the sleep lamp is light, set temp. and fan speed can be adjust.
Timer and sleep can set together, which time is end then perform this function.
7. Air flow control
Define:flap full open angle is 0°, and full close angle is 125°。
Power on, flap run to full close position.
Full open
Full close
Fixed
51 SERVICE MANUAL FOR CMV
Turn off air conditioner, flap run to full close position.
Turn on air conditioner, flap first run to full open position, then run to correspond position.
Fixed wind:
If turn on air conditioner and set fixed wind at first power on, flap first run to full open
position then stop at 40°position.
If change to fixed wind from swing wind or natural wind, the flap stop at current position
and store the position.
Swing wind:
Flap start position is 20°.
Flap is running between 20°and 85°.
Natural wind is swing two cycle and stop 15 seconds, flap is stop at current
position at that moment.
Flap stop at 85°at anti cold wind or defrost procedure in heating mode.
Flap stop at 85°in first 20 seconds of auto mode.
Flap is drive by step motor.
8. Turbo function
Turbo is use in cooling /heating/ventilation mode, the indoor blower fan is running
at super speed.
(1) enter condition: press turbo key of remote.
(2)end condition:
① running time more than or equal to 15 minutes.
② press turbo key of remote again.
(3) all restrict and protect condition are active in turbo running.
(4) return to prior state after end turbo running.
五、Protection
1. Prevent frost of indoor coil pipe (cooling and dehumidify mode)
When the temp. of middle coil pipe is less than or equal to 0℃, indoor blower
fan is running at high speed, if the temp. less than or equal to -1℃ for 5 minutes,
it turn off compressor, when the temp. more than or equal to 7℃, it exit
protection.
2. Overheat of indoor coil pipe(heating mode)
When the temp. of middle coil pipe more than or equal to 57℃, indoor blower fan
is running at high speed, if the temp. more than or equal to 65℃ , it turn off
outdoor unit, when the temp. less than or equal to 54℃, it exit protection.
3. Indoor fan motor fault(only PG motor)
If no feedback signal continuous 30 seconds during PG motor running, it turn off
air conditioner and display fan motor error.
4. Communicate fault
If it can’t receive correct signals after air conditioner has run for 60 seconds,
it turn off air conditioner and display communicate error.
5.Indoor sensor fault
When indoor sensor cut off or short, it shutdown air conditioner and display sensor
error.
6. When outdoor unit is fault, indoor unit only display fault.
六、Other function
Emergency key
Press emergency key after power on, air conditioner select auto mode, auto fan speed, natural wind,
it set temp. is 25℃. If press emergency key again, air conditioner is shutdown.
52 SERVICE MANUAL FOR CMV
七、Sound indication
1. The buzzer will sound when air conditioner turn on , turn off, power on or receive remote signal.
八、Display
1.After turn on air conditioner, mode clash display
d1
and timer lamp flash (light
one second, extinguish one second), defrost display
dF
, the running lamp flash (light
one second, extinguish one second)indicate anti cold wind ,when air conditioner is
normal running , the running lamp is light.
2.Set timer or sleep , the yellow lamp is light.
3.Outdoor unit and indoor unit fault display:
Fault display of indoor unit:
fault
display
Communicate fault
F1
Fan motor fault
F4
Room temp. sensor fault
F2
Temp. sensor of coil pipe outlet fault
F3
Temp. sensor of coil pipe entrance
fault
F3
Temp. sensor of coil pipe middle
fault
F3
Fault display of outdoor unit:
fault
display
Transducer module protection
P2
Over current
P3
Discharge temperature of
compressor overheat, ambient
temperature overheat
P4
DC voltage of outdoor unit abnormal
P7
Leakage or reverse valve fault
P8
Outdoor sensor fault
F6
Compressor drive fault
FC
Function of Dual DC Inverter Type
一. System Frame Drawing
R
everse Valve(Current in cooling condition
)
Condenser of Outdoor Unit
Temperature of the Middle of Outdoor Coils
Temperature of Exhaust
Expansion Valve 1 Expansion Valve 2
Temperature of suction
M M
Compressor
Liquid Tank
T11 T12 T13
Evaporator 1 of Indoor Unit
Ambient Temperature of Indoor 1
Ambient Temperature of Outdoor T21 T22 T23
Evaporator 2 of Indoor Unit
Ambient Temperature of Indoor 2
Diagram 1
53 SERVICE MANUAL FOR CMV
二.Major Performance Index
a) Voltage of Power Supply: AC220V ±15%;
b) Power of Controller: ≤15W;
c) Output of Three-phase Frequency Conversion:
Wire Voltage: 70V∽180V; Power: ≤5KW; Frequency: 10Hz∽120Hz;
d) Precision of Temperature Control:±1℃;
e) Applicable Environment:
Temperature:-20∽55℃,Relative Humidity: ≤90%RH (No dew);
f) Conservation Environment:
Temperature:-25∽70℃,Relative Humidity: ≤95%RH (No dew);
g) Executive Standard: GB/T7725-2004 & GB4706.32-2000.
三.Input & Output of Outdoor Controller
1.
Outputs of one three-phase Frequency Conversion, two relays, one indicator led and one
communication signal:
1) Controlling the three-phase output of compressor
2) Controlling the output of outdoor motor
3) Controlling the output of 4-way valve
4) Controlling the output of communication signals of indoor unit
5) Controlling the output of expansion valve
2. Inputs of five analogue inputs (the temperature measuring points distributing as Diagram 1, all
the analogues go through digital filter for disposal), and two switch signals and two
communication signals:
a) Signal input of outdoor ambient temperature
b) Signal input of median temperature of outdoor coil
c) Signal input of discharge temperature of compressor
d) Signal input of suction temperature of compressor
e) Signal input of power supply voltage
f) over-heat protection signal of compressor
g) communication signal of indoor unit 1
h) communication signal of indoor unit 2
i) protection signal of outdoor IPM module
四. Operation in Cooling Mode
Control of Expansion Valve in Cooling Mode
1. Reset of Expansion Valve
In the first time ,the expansion valves in all channels shall be shut down 600 steps, then the
expansion valve corresponding to the indoor unit in normal communications with the outdoor unit
shall be opened to standby mode steps. If accomplished, the outdoor unit shall be on standby mode,
until the turn-on the indoor unit.
2. Adjustment of Expansion Valve
1) Setting of Basic Step
After the confirmation of the turn-on order of cooling mode, the expansion valve of the
relevant indoor unit shall be set to the basic step and the other to zero step.
2) Adjustment of Expansion Valve according to the difference in temperature between the inlet
and outlet of evaporator
54 SERVICE MANUAL FOR CMV
During the first ten minutes of cooling mode, the expansion valve of the indoor unit at the
request of cooling shall be set to the basic step. Ten minutes later, the expansion valve step and
its adjust cycle shall be adjusted according to the difference in temperature between the inlet
and outlet of evaporator.
Control of compressor’s frequency:
1.Range of compressor’s frequency:Fmin~Fmax (Fmin:the lowest frequency, Fmax:the highest
frequency)
2.Frequency decrease protection of compressor: frequency decrease protection is
prior during frequency adjustment of compressor (Frequency decrease protection
have: high temperature of compressor discharge, high temperature of outdoor coil
pipe, high temperature of indoor coil pipe, low temperature of compressor suction,
over current)
Control of fan motor in cooling mode:
1.The fan motor of outdoor unit is ahead run 20 seconds before compressor turn on.;
2.After compressor turn off, the fan motor of outdoor unit delay 30 seconds.
3. The fan motor speed of outdoor unit as below table in normal running, it has 20 seconds delay
after speed change.
Speed table of outdoor fan motor
indoor unit
capacity
outdoor ambient
<2hp
≥
2hp
≥
3hp
cooling Speed
grade
T<19℃
low low
middle
19℃≤T<27℃
low middle high
T≥27℃
middle high high
compressor
outdoor FM
20s 30s 30s
figure 3
五
.Operation in Dehumidify Mode
Dehumidify mode is same as cooling mode.
六
.Operation in heating Mode
Adjustment of Expansion Valve:
1.Reset of Expansion Valve
In the first time,the expansion valves in two channels shall be shut down 600 steps, then the
expansion valve corresponding to the indoor unit in normal communications with the outdoor unit
55 SERVICE MANUAL FOR CMV
shall be opened to standby mode steps. If accomplished, the outdoor unit shall be on standby mode,
until the turn-on the indoor unit.
2.Adjustment of Expansion Valve
1) Setting of Basic Step
After the confirmation of the turn-on order in heating mode, the expansion valve of the
relevant indoor unit shall be set to the basic step.
2) Adjustment of Expansion Valve according to the difference in temperature between the inlet
and outlet of evaporator
During the first ten minutes of heating mode, the expansion valve of the indoor unit shall be
set to the basic step and can’t adjust. Ten minutes later, the expansion valve step and its adjust
cycle shall be adjusted according to the difference in temperature between the inlet and outlet
of evaporator.
Control of compressor’s frequency
Range of compressor’s frequency:Fmin~Fmax (Fmin:the lowest frequency, Fmax:the highest
frequency)
Control of fan motor in heating mode:(figure 5)
1. The fan motor of outdoor unit is ahead run 20 seconds before compressor turn on.
2. After compressor turn off, the fan motor of outdoor unit delay 30 seconds.
3. The fan motor speed of outdoor unit as below table in normal running, it has 20 seconds delay
after speed change.
4. The control of outdoor fan motor as figure 6 during defrost process.
Speed table of outdoor fan motor
indoor unit
capacity
outdoor ambient
<2hp
≥2hp
≥3hp
heating Speed
grade
T≥20℃
low low
middle
12℃≤T<20℃
low middle high
T<12℃
middle high high
Control of reverse valve(figure 5)
1. The reverse valve is ahead run 20 seconds before compressor turn on.
2. After compressor turn off, the reverse valve delay 60 seconds shutdown.
3. The control of reverse valve as figure 6 during defrost process.
compressor
outdoor FM
reverse valve
20s 30s 30s
figure 5
七.Defrost of heating mode(figure 6)
1. Defrost start condition
If outdoor ambient is more than or equal to 16℃,it can’t defrost. When the time of
defrost interval is end , outdoor coil pipe temp. and outdoor ambient temp.
continuous meet all conditions for 5 minutes, it enter defrost process:
1) If outdoor ambient temp. less than or equal to 0℃,when T
盘
≤0.8T
环
+a℃(a is a adjust
constant), it enter defrost process.
56 SERVICE MANUAL FOR CMV
2) If outdoor ambient temp. more than 0℃ and less than or equal to 15℃,when T
盘
≤ 0.2 T
环
+a℃, it enter defrost process.
3) If outdoor temp. sensor is failure, when outdoor coil temp. T
盘
≤+a℃, it enter defrost
process.
4) If coil temp. sensor of outdoor unit is failure, when defrost interval time is end, it enter defrost,
the time of defrost is four minutes.
5) During the first ten minutes of outdoor running in heating mode, the time is clear and it judge
whether outdoor coil pipe temp. and outdoor ambient temp. satisfy defrost condition, if the
frequency of compressor is 25HZ and satisfy defrost condition, then if enter defrost process.
After end defrost process or over 10 minutes it return normal running.
2. Defrost end condition
1) T
盘
≥b℃(b is a adjust constant)or defrost time more than or equal to c minutes
(c is a adjust constant),it exit defrost process.
2) When outdoor coil pipe sensor is failure, defrost time is four minutes, it exit defrost process
after four minutes.
3. Interval time of defrost
1) Defrost interval time restriction: Max 120 minutes, Min 25 minutes.
2) The first frost interval time is 0 minute after heating.
3) The second defrost interval time is base on 60 minutes, it adjust according to below table.
4) Form second time, defrost interval time adjustment as below table.
Interval time(Td)
change
Td <2 minutes
Last interval time add 5
minutes
3 minutes≥Td≥2
minutes
Same as last interval time
≥4 minutes
Last interval time reduce 5
minutes
4. Time sequence of defrost process(figure 6).
57 SERVICE MANUAL FOR CMV
八.Control of oil return circle
1. Oil return circle period
When air conditioner has run for 10 minutes or accumulate time T
msro
is end, it execute oil return
circle once.
2.
When compressor is running to oil return circle, the indoor unit which have communication
is return oil, expand valve is open fully and compressor’s frequency increase more than 3/5
of max frequency for 90 seconds, the expand valve of indoor unit which no communication is
close.
九. Operation mode control of outdoor unit(dehumidify、cooling or heating)
The indoor unit can require cooling mode and dehumidify mode together, but it can’t require cooling mode
or dehumidify with heating mode together, the outdoor unit operate state is decided by the indoor unit which is
applied first.
十.Protect function:
1. Delay protection of compressor
The compressor can’t run after it stop within 3 minutes.
2. Fault protection of module
The air conditioner stop running immediately and display error code if the module
is fault.
3. Protection of communicate fault
The control of outdoor unit can connect with all indoor units, when it power on,
it sent data to each indoor unit continuously, if it receive a correct data from
correspond indoor unit, then the indoor unit is exist. when the control of outdoor
unit didn’t receive communication data from indoor unit which is exist within 30
seconds, it will display communication fault. If all communication channels are
failure, air conditioner will shutdown and display fault code.
4. Leakage or reverse valve fault
The air conditioner shutdown immediately when meet one of below conditions.
1) Heating: coil pipe temp. of outdoor unit can’t decrease 3 degree within setting
time and coil pipe temp. of indoor unit can’t increase 3 degree all along.
2) Cooling: coil pipe temp. of outdoor unit can’t increase 3 degree within setting
time and coil pipe temp. of indoor unit can’t decrease 3 degree all along.
5. High temp. protection of compressor discharge
1) The protection don’t effect if the temp. sensor of compressor discharge fault.
2) The air conditioner stop running immediately and display error code when the
temp. of compressor discharge more than Tsd.
3) The compressor decrease frequency until the temp. of compressor discharge less
than 99℃ if the temp. of compressor discharge more than 95℃. The compressor resume
normal frequency when the temp. of compressor discharge less than 90℃.
6. Temperature switch protection of compressor
The air conditioner will shutdown immediately and display fault code if the temp.
switch of compressor switch off.
7. High temp. protection of middle coil pipe of condenser
1) The protection don’t effect if the temp. sensor of middle coil pipe fault.
2) The compressor decrease frequency until the temp. of middle coil pipe less than
58 ℃.if the temp. of middle coil pipe more than 57℃..
3) It resume normal frequency when the temp. of middle coil pipe less than 56℃..
58 SERVICE MANUAL FOR CMV
8. High temp. protection of indoor coil pipe
1) The compressor decrease frequency until the temp. of indoor coil pipe more than
(Tsce-2) if the temp. of indoor coil pipe less than (Tsce-2)in cooling mode.
The compressor decrease frequency until the temp. of indoor coil pipe less than
(Tsce+2) if the temp. of indoor coil pipe more than (Tsce+2) in heating mode.
2) It resume normal frequency when the temp. of indoor coil pipe less than Tsce(cooling mode)
or less than Tshe(heating mode).
9. Low temp. protection of compressor suction
1) The protection don’t effect if the temp. sensor of compressor suction fault or compressor
don’t run or in heating mode..
2) The compressor decrease frequency until the temp. of compress suction more than
Tss if the temp. of compressor suction less than Tss. It resume normal frequency when the
temp. of compressor suction more than (Tss+2).
10.Fault protection of outdoor sensor
The air conditioner is running at the frequency of less than (3/5)*Fmax and display fault code
if the temp. sensor of compressor discharge fault, or the temp. sensor of outdoor middle
coil pipe fault, or the temp. sensor of compressor suction fault, or the temp. sensor
of outdoor ambient fault.
11.High temp. of ambient
1) The protection don’t effect if the temp. sensor of outdoor ambient fault.
2) The air conditioner stop running immediately and display error code if outdoor
ambient temp. more than 55℃or less than -20℃.
12. Over current protection of compressor
1) The air conditioner stop running immediately and display error code when input
current more than or equal to Imax.
2) The compressor decrease 2Hz per 3 seconds until input current less than or equal
to (Imax-13) when the input current more than (Imax-13).
2)The compressor decrease 1Hz per 3 seconds until input current less than or equal
to (Imax-16) when the input current more than (Imax-16).
3) It resume normal frequency when the input current less than or equal to (Imax-20).
13.DC voltage of wire protection
1) The air conditioner stop running and display DC voltage abnormal when it less
than 260V.
2)The compressor decrease frequency and display FA6 when DC voltage less than 285V.
3) The air conditioner resume normal running when DC voltage more than 290V.
十一、Outdoor unit fault of indoor unit display
fault
display
Transducer module protection
P2
Over current
P3
Discharge temperature of
compressor overheat, ambient
temperature overheat
P4
DC voltage of outdoor unit abnormal
P7
Leakage or reverse valve fault
P8
Outdoor sensor fault
F6
Compressor drive fault
FC
59 SERVICE MANUAL FOR CMV
12. TROUBLESHOOTING
WARNING!!!
When Power Up – the whole outdoor unit controller, including the wiring, is under HIGH
VOLTAGE!!!
Never open the Outdoor unit before turning off the Power!!!
When turned off, the system is still charged (400V)!!!
It takes about 3 Min. to discharge the system.
Touching the controller before discharging may cause an electrical shock!!!
For safe handling of the controller please refer to section 1.6 below.
1.1 Air Conditioner Failures and Corrective Actions
F1:
1,Communicate wire cut off ,loose or wrong wiring---check wires
2,Communication interfere---check wires connection with circuit diagram.(earth line must be
wired)。
F2:
1,Temp. sensor of indoor room short or cut off.---change sensor
F3:
1,Temp. sensor of indoor coil pipe outlet short or cut off.---change sensor.
2,Temp. sensor of indoor coil pipe entrance short or cut off.---change sensor.
3,Temp. sensor of indoor coil pipe middle short or cut off.---change sensor.
F4:
1,PG motor fault.---change motor. PG.
2,Fixed screw loose.---fix cross flow fan.
3,Communication interfere. (earth wire can’t with communicate wire in same cable)---check cable.
F6:
1,Temp. sensor of discharge short or cut off.---change sensor.
2,Temp. sensor of suction short or cut off.---change sensor.
3,Temp. sensor of condenser middle short or cut off.---change sensor.
P2:(auto-restart)
1,over current protection of inverter module.
2,over voltage protection of inverter module.
3,high temp. protection of inverter module.
P3:
1,over load (outdoor ambient temp. more high).
2,Voltage over low.
60 SERVICE MANUAL FOR CMV
P4:
1: discharge temp. too high.---maybe leak refrigerant, add refrigerant.
2:outdoor ambient temp. too high, if (T<-20,T>55), it will alarm.
3:temp. switch of compressor cut off.。
4:Communication interfere. (earth wire can’t with communicate wire in same cable)---check cable.
P7:
1,PFC board fault.---change PFC board.
2,Communication of main board and PFC board fault.---check wires of main board and PFC board.
P8:
1,Less refrigerant.---add refrigerant.
2,Coil pipe sensor can’t contact with coil pipe.
3,4-way valve fault.---change 4-way vavle fault.
61 SERVICE MANUAL FOR CMV
1 3 . E X P L O D E D V I E W S A N D S P A R E P A R T S L I S T S
13.1 outdoor unit :CMV-50V3A-E2
NO. description
name
number
1
前网罩
front grill
1
2
前面板
front panel
1
3
风叶
fan 1
4
室外电机
motor 1
5
电机支架组件 motor bracket assemble
1
6
左护网
left grill
1
7
左侧立柱
left pole
1
8
顶盖板
top cover
1
9
背网
rear grill
1
10
冷凝器
condenser 1
11
四通阀
4-way valve
1
12
消音器
muffle 1
13
过滤器
filter 1
14
控制器
controllor 1
62 SERVICE MANUAL FOR CMV
15
电控盒盖
control box cover
1
16
电控盒
electrical control box
1
17
A机DN8截止阀
DN8 valve for A unit
1
18
A机DN4截止阀
DN4 valve for A unit
1
19
B机DN8截止阀
DN8 valve for B unit
1
20
B机DN4截止阀
DN4 valve for B unit
1
21
阀座板
valve installation plate
1
22
大抽手
handle 1
23
右侧板
right panel
1
24
电子膨胀阀
expand valve
2
25
压缩机
compressor 1
26
压缩机胶垫
compressor pad
1
27
中隔板
partition board
1
28
底盘组件
base assemble
1
13.2 outdoor unit :CMV-71V3A-T
63 SERVICE MANUAL FOR CMV
NO. description
name
number
NO.
description name
number
1
顶盖
top cover
1
15
单接头 DN8 sigle tie-in DN8
3
2
冷凝器
condenser 1
16
单接头 DN4 sigle tie-in DN4
4
3
电机支架
motor bracket
1
17
单接头 DN10
sigle tie-in
DN10 1
4
中隔板
partition board
1
18
电子膨胀阀
expand valve
3
5
汽液分离器
gas and liquid
segregator 1
19
右前面板
right front panel
1
6
干燥过滤器
filter 1
20
储液罐
store pot
1
7
油汽分离头
器
gas and oil segregator
1
21
压缩机
compressor 1
8
后板
rear panel
1
22
四通阀
reverse valve
1
9
电控组件
electrical control
assemble 1
23
底盘
base 1
10
阀座板
valve installation plate
1
24
前面板
front panel
1
11
低压阀
low pressure valve
1
25
网罩
grill 1
12
维修板
repair plate
1
26
风叶
fan 1
13
抽手
handle 2
27
电机
motor 1
14
高压阀
high pressure valve
1
13.2 outdoor unit :CMV-V80WC3AQ
64 SERVICE MANUAL FOR CMV
NO. description
name
number
NO.
description name
number
1
顶盖
top cover
1
15
单接头 DN8 sigle tie-in DN8
3
2
冷凝器
condenser 1
16
单接头 DN4 sigle tie-in DN4
4
3
电机支架
motor bracket
1
17
单接头 DN10
sigle tie-in
DN10 1
4
中隔板
partition board
1
18
电子膨胀阀
expand valve
3
5
汽液分离器
gas and liquid
segregator
1 19 右前面板
right front panel
1
6
干燥过滤器
filter 1
20
储液罐
store pot
1
7
油汽分离头
器
gas and oil segregator
1
21
压缩机
compressor 1
8
后板
rear panel
1
22
四通阀
reverse valve
1
9
电控组件
electrical control
assemble
1 23 底盘
base 1
10
阀座板
valve installation plate
1
24
前面板
front panel
1
11
低压阀
low pressure valve
1
25
网罩
grill 1
12
维修板
repair plate
1
26
风叶
fan 1
13
抽手
handle 2
27
电机
motor 1
14
高压阀
high pressure valve
1
13.2 outdoor unit :CMV-V40H13AD
65 SERVICE MANUAL FOR CMV
NO. description
name
number
1
前网罩
Front Grill
1
2
面 板
Front Plate
1
3
轴流风轮
Axial flow fan
1
4
电 机
Motor
1
5
电机支架
Motor support
1
6
冷凝器
Condenser
1
7
顶盖板
Top panel
1
8
电器盒
Electric box
1
9
背网
Rear Grill
1
10
右侧板
Right panel
1
11
抽手
handle
1
12
阀座板
Valve installation plate
1
13
A 机 DN4 阀
DN4 valve
1
14
A 机 DN8 阀
DN8 valve
1
15
B 机 DN4 阀
DN4 valve
1
16
B 机 DN8 阀
DN8 valve
1
17
毛细管组件 Capillary Assy
1
18
电子膨胀阀 Electronic expansion valve
2
19
四通阀组件 Four-way valve assembly
1
20
汽液分离器 Steam liquid segregator
1
21
压缩机
Compressor
1
22
中隔板
Partition board
1
23
底盘
Base
1
66 SERVICE MANUAL FOR CMV
APPENDIX A
APPENDIX A
INSTALLATION AND OPERATION MANUAL
I N S T A L L A T I O N M A N U A L C M V
67 SERVICE MANUAL FOR CMV
F o r e w o r d
This instruction Manual is the universal-purpose version for the models of separate wall-mounted
air conditioners manufactured by our Co. The appearance of the units that you purchase might be
s l i g h t l y d i f f e r e n t from the ones described in the Manual, but it does not affect your proper
operations and usage.
Please read carefully the sections corresponding to the specific model you choose, and keep the
Manual properly so as to facilitate your reference at later time.
I M P O R T A N T !
P l e a s e R e a d B e f o r e S t a r t i n g
This air conditioning system meets strict safety and operating standards.
As the installer or service person, it is an important part of your job to install or service the system
so it operates safely and efficiently.
For safe installation and trouble-free operation, you must:
? Carefully read this instruction booklet before beginning.
?
Follow each installation or repair step exactly as shown.
?
Observe all local, state, and national electrical codes.
? Pay close attention to all danger, warning, and caution notices given in this manual. WARNING:
This symbol refers to a hazard or unsafe practice which can result in severe personal injury or
death.
CAUTION: This symbol refers to a hazard or unsafe practice which can result in personal injury
and the potential for product or property damage.
CONTENTS
LOCATION OF OUTDOOR UNIT
1
ELECTRICAL CONNECTION BETWEEN INDOOR AND OUTDOOR UNIT
3
INSTALLATION/SERVICE TOOLS (ONLY FOR R410A PRODUCT)
7
REFRIGERANT TUBING
9
FINAL TASKS
11
NOTE: This manual is for Multi split applications only.
For indoor units installation please refer to the installation manual
supplied within the indoor unit package.
68 SERVICE MANUAL FOR CMV
1 LOCATION OF OUTDOOR UNIT
Select the location considering the following:
O U T D O O R U N I T
1 .The location must allow easy servicing and provide good air circulation as shown in fig2.
2.The unit may be suspended from a wall by a bracked(Optional)or located in a free standing
position on the floor(preferably slightly elevated).
3.If the unit is suspended , ensure that the bracket is firmly connected and the wall is strong
enough to withstand vibrations.
4.Unit location should not disturb neighbours with noise or exhaust air stream.
5.Place the mounting pads under the unit legs.
6.Refer to figure 2 for allowed installation distances.
.
Fig 1
2 ELECTRICAL CONNECTION BETWEEN
OUTDOOR AND INDOOR UNIT
ELECTRICAL REQUIREMENTS
Electrical wiring and connections should be made by qualified electricians and in accordance
with local electrical codes and regulation.The air conditioner units must be grounded. The air
conditioner units must be connected to an adequate power outlet from a separate branch
circuit protected by a time delay circuit breaker,as specified on unit's nameplate. Voltage
should not vary beyond ± 10% of the rated voltage.
1 .Remove the power supply cable that is connected to the indoor unit!
2.To connect the indoor units to the outdoor units,use the following electrical cables.
Electrical connections:
Power input cable: 1 group 3 wiresX2.5mm
2
cable between indoor and
outdoor units:
1 group 4 wiresX 1.0mm
2
see Fig 6.7.8.9.10 for detail .
3.Prepare the cable ends for the power input and for the cables between outdoor and indoor
units as shown in figure 3a and 3b respectively.
4.Connect the cable ends to the terminals of the indoor and outdoor units , as show in fig4, figs.
Please select corresponding connection according to the different indoor units. 5.Secure the
multiple wire power cable with the cable clamps.
•Power input cable
70 SERVICE MANUAL FOR CMV
71 SERVICE MANUAL FOR CMV
3 INSTALLATION/SERVICE TOOLS(QNLY
FOR R410A PRODUCT)
C A U T I O N
New Refrigerant Air Conditioner Installation
This air conditioner adopts the new HFC refrigerant (R410A) which does not destroy ozone layer.
R410A refrigerant is approx . 1.6 times of refigerant R22. Accompanied with the adoption of the
new refrigerant , the refrigeration machine oil has also been changed.
Therefore,during installation work, be sure that water , dust , former refrigerant , or refrigeration
machine oil does not enter into the new type refrigerant R410A air conditioner circuit.The system
must not be left open to the atmosphere for any reason for any period of time as the systems oil
quickly absorbs moisture and will contaminate and damage the system.
A refrigerant liquid line drier is recommended.
To prevent mixing of refrigerant or refrigerating machine oil ,the sizes of conneting sections of
charging port on main unit and installation tools are different from those used for the conventional
refrigerant units. Accordingly,special tools are required for the new refrigerant (R410A) units,
For connecting pipes use new and clean piping materials with high pressure f i t t i n g made for
R410A only, so that water and/or dust does not enter.Moreover, do not use the existing piping
because there are some problems w i t h presure f i t t i n g s and possible i m p u r i t i e s in e x i s t i n g
piping .
Changes in the product and components
In air conditioners using R410A ,in order to prevent any other refrigerant from being accedentally
charged .the service port diameter size of the outdoor unit control valve (3 way valve) has been
changed. (1/2 UFN 20 threads per inch)
• In order to increase the pressure resisting strength of the refrigerant piping ,flare processing
diameter and opposing flare nuts sizes have been changed.( fot copper pipes with nomensions
1/2 and 5/8)
New tools for R410A
Nes tools for R410A
Applicable to R22 model
Chages
Gauge manifold
x
As the working pressure is high ,it is impossible
to measure the working pressure using
conventional gauges . In order to prevent
any other refrigerant from being charged ,
the port diameters have been changed.
Charge hose
x
In order to increase pessure resisting strength.
hose materials and port sizes have been changed(
to 1 /2 UNF 20 threads per inch).
When puchasing a charge hose,be sure to confirm
the port size.
Electronic balance for
refrigerant charging
As working pressure is. high and gasification
speed is fat ,it is difficult to read the indicated
value by means of charging cylinder ,as air
bubbles occur.
Torque wrench
(nominal dia.1/2,5/8)
x
The size of opposing flare nuts have been
increased ,incidentally,a common wrench is
used for nominal diameters 1/4 and 3/8.
72 SERVICE MANUAL FOR CMV
Flare tool
(clutch type)
0
By incressing the clamp bar'receiving hole
size , strength of spring in the tool has been
improved.
Gauge for projection
adjustment
_
Used when flare is made by using conventional
flare tool.
Vacuum pump adapter 0
Connected to conventional vacuum pump,it is
necessary to use an adapter to prevent vacuum
pump oil from flowing back into the charge
hose ,
The charge hose connecting part has two
ports-one for conventional refrigerant (7/16
UNF 20 theads per inch )and one for R41 OA ,if
Gas leakage detector
x
Exclusive for HFC refrigerant
• I n c i d e n t a l l y , t h e " r e f r i g e r a n t cylinder"comes w i t h the r e f r i g e r a n t designation(R410A)and
protector coating in the U.S's ARI specified rose color (Ari color code; PMS 507).
•Also the "charge port and packing for refrigerant cylinder"requires 1/2 UNF 20 theads per inch
corresponding to the charge pOse's port size.
4 REFRIGERANT TUBING
CONNECT THE INDOOR TO THE OUTDOOR UNIT
The indoor unit contains a small quantity of nitrogen.Do not unscrew the nuts from the unit until
you are ready to
connect the tubing.The outdoor unit is supplied
with suffcient refrigerant charge(R410A). Refer
to outdoor unit nameplate.
To prevent crushing,bend tubes using a bending
tool.
NOTE:Use refrigeration R410Atype copper
tubing only.
1.Open the valve cover.
2.Use tubing diameter that corresponds to the
tubing diameter of the indoor and outdoor units.
Note that the liquid and suction tubes have
different diameters.(See tube size,torque
tightening table.)
3.Place flares nuts on tube ends before preparing
them with a flaring tool.Use the flare nuts that
are mounted on the supplied outdoor and indoor
units.
4.Connect the all ends of the tubing to the
indoor and outdoor units.Notice the sign . All
ends should correspond one by one.
5.Insulate each tube separately,and their
unions,with at least 6mm thick of
insulation .Wrap the refrigerant tubing,drain
hose and electric cables together with a vinyl tape (UV protected).
73 SERVICE MANUAL FOR CMV
Caution!
When unscrewing the
valve caps, do not stand
in front of them or the
spindles at any time,as
the system is under
pressure.
Fig 11
1.INDOOR UNIT
2.Liquid tube(small dia.) 3.Suction
tube(large dia.) 4. Plugs
5.Flare nuts
6.Tubing between units 7.Suction
tube
8.Liquid tube
9.OUTDOOR UNIT
10.FIare nuts
11 .Suction valve(larger) 12.Liquid
valve(smal)
NOTE:1.For unit use connectionsA,B and D
2.For large indoor unit of 5.0KW Use the
lower connection(unit D) and use the
3/8"-1/2"transition( supplied)
3.The electric control channel must match
the tube channel.
TUBE SIZE
TORQUE
Liquid line 1/4"
1 5 - 2 0 N.M.
Suction line 3/8"
3 0 - 3 5 N.M.
Suction line 1/2"
5 0 - 5 4 N.M.
Suction line 5/8"
7 5 - 7 8 N.M.
Fig 13 To prevent refrigerant
leakage,coat the flared
surface with
refrigeration oil
Fig 14
1.Suction valve
2.Service port
3.Liquid valve
EVACUATION OF THE REFRIGERATION TUBES AND THE INDOOR UNIT
After connecting the unions of the indoor and outdoor units,evacuate the air from the
tubes and indoor unit as follows:
Tightening torques
of unions and
valve caops:
74 SERVICE MANUAL FOR CMV
1.Connect the charging hoses with a push pin to the low and high sides of the charging
set and the service ports of the suction and liquid valves.
Be sure to connect the end of the charging hose with the push pin to the service
ports. 2.Connect the center hose of the charging set to a vacuum pump.
3.Open Fully the low and high pressure sides of the manifold gauge valves.
4.Turn on the vacuum pump.Perform evacuating for at least 30 minutes and than confirm
that the needle in the gauge moves from 0 MPa(Ocm Hg) t 0 - 0 . 1 MPa(-76cm Hg).
5.Close the valves of the low and high sides of the charging set and turn off the vacuum
pump. After few m i n u t e s , i f the gauge needle has moved,there is a leak which must be
found and repaired before moving to the next stage.
6.Disconnect the charging hose from the vacuum pump and from the service ports of the
suction and liquid valves.
7.Tighten the service port caps of suction and liquid valves.
8.Remove the valve caps from all valves,and open them using a hexagonal Allen
wrench, 9.Securely tighten the caps onto all of the valves.
10.Check for gas leaks from all the connecting p os i t io n . Tes t w i t h electronic leak
detector or with a sponge immersed in soapy water for bubbles.
1 .Charging set
5.Cap
9.Liquid valve
2.Vacuum pump
6.Suction valve
10.INDOOR UNIT
3.OUTDOOR UNIT
7.Service valve
1 1.Suction flare connection
4.Service valve
8.Cap
12.Liquid flare connection
75 SERVICE MANUAL FOR CMV
5 FINAL TASKS
1 .Check all valve caps and ensure that they had tightened properly.Close the valve
cover. 2.Fill gaps on the wall between hole sides and tubing with sealer.
3.Attach wiring and tubing to the wall with clamps where necessary.
4.Operate the unit for no less than 5 minutes at heating or cooling
mode. 5.Explain filter removal,cleaning and installation.
6.Operate the air conditioner together with the customer and explain all
functions. 7.Give the operating and installation manuals to the customer