HYDRO-WENTPOM |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
SPRAWOZDANIE Z POMIARÓW POZIOMU HAŁASU |
WYWOŁANEGO PRACĄ INSTALACJI WENTYLACJI |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
OBIEKT: |
Silwer Screem |
|
|
|
ul. Górczewska 124 |
|
|
|
Warszawa |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
ZAKRES POMIARÓW: |
POMIAR POZIOMU HAŁASU OD INSTALACJI WENTYLACJI |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
PODSTAWA POMIARÓW: |
POLSKA NORMA PN-87/B-02151/02, PN-87/B-02156 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
POMIARY I OPRACOWANIE WYNIKÓW: |
Michał Mazur & Jacek Wosiński |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Warszawa 10-11 grudzień 2004 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1.Zakres pomiarów |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Pomiary wykonano zgodnie z normą PN-87/B-02156; mierzono poziom dźwięku A-LA, który ze względu na stały i ciągły w czasie charakter hałasu odpowiada tzw. równoważnemu poziomowi dźwięku A. |
|
|
|
|
|
|
|
|
|
2.Przyrząd pomiarowy |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Pomiary wykonano przyrządem do pomiaru hałasu model ,,NL-32'' firmy RION wyposażony w wyświetlacz ciekłokrystaliczny o dokładności odczytu 0,1 dB. Miernik kl.1. |
|
|
|
|
|
|
|
|
|
3. Warunki pomiarowe |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Pomiary wykonano w godzinach nocnych 23.30-05.30, włączając i wyłączając wszystkie urządzenia wentylacyjne. Instalacja przed pomiarami została wyregulowana. |
|
|
|
|
|
|
|
|
|
4.Punkty pomiarowe |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Pomiarów dokonano w salach kinowych holu i barach. W pomieszczeniach wyznaczono, co najmniej cztery punkty pomiarowe. Mikrofon umieszczono na wysokości 1.5 m od podłogi, oraz w odległości nie mniejszej niż 1m od ściany i 1.5 m od okien. Drzwi i okna w czasie pomiarów były zamknięte. |
|
|
|
|
|
|
|
|
|
5.Wyniki pomiarów |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Zgodnie z normą PN-87/B-02156, określany poziom dźwięku A,(LA) należy obliczyć w dB według wzoru: |
|
|
|
|
|
|
|
|
|
LA=L+K1+K2 |
|
|
|
|
|
|
|
|
|
w którym: |
|
|
|
|
|
|
|
|
L- zmierzony średni poziom dźwięków w dB, |
|
K1-poprawka uwzględniająca wpływ tła akustycznego, |
|
K2-poprawka uwzględniająca chłonnosć akustyczną pomieszczenia nie umeblowanego |
|
|
|
Ltło- tło akustyczne |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
PROTOKÓŁ Nr 1 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
POMIARÓW HAŁASÓW |
URZĄDZEŃ WENTYLACYJNYCH |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
MIEJSCE BADAŃ: |
|
Sala kinowa Nr 1 |
|
|
|
|
|
|
|
|
|
DATA BADAŃ: |
|
10-11 grudzień 2004r. |
|
|
|
|
|
|
|
|
|
CEL POMIARÓW: |
|
Pomiary odbiorcze urządzeń wentylacyjnych |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
OPIS BADANEGO URZĄDZENIA WENTYLACYJNEGO: Wentylacja nawiewno-wyciągowa |
OPIS WARUNKÓW BADAŃ |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Szkic pomieszczenia z lokalizacją punktów pomiarowych. |
|
|
|
|
|
|
|
|
|
Charakterystyka pomieszczenia: |
Sala kinowa. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
METODA POMIAROWA: |
|
w polu rozproszenia |
|
|
|
|
|
|
|
|
|
|
|
|
|
APARATURA POMIAROWA: |
|
Sonometr cyfrowy |
|
|
|
|
|
|
Typ: RION NL-32 |
|
|
|
|
|
|
Nr. : 00940952 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
WYNIKI POMIARÓW |
|
|
|
|
|
|
|
|
|
Punkt |
Poziom dźwięku A dB |
Pomiarowy |
L1w |
L1 tła |
L2w |
L2 tła |
L3w |
L3 tła |
Lśr w |
Lśr tła |
1 |
29.9 |
29.6 |
29.8 |
29.1 |
29.9 |
29.9 |
29.9 |
29.5 |
2 |
29.1 |
24.9 |
29.7 |
25.4 |
28.9 |
25.3 |
29.2 |
25.2 |
3 |
30 |
26.8 |
30 |
26.3 |
29.9 |
26.7 |
30.0 |
26.6 |
4 |
29.5 |
25.4 |
29.1 |
25.1 |
29.5 |
24.9 |
29.4 |
25.1 |
5 |
29.2 |
25.1 |
29.6 |
25.7 |
29.5 |
25.4 |
29.4 |
25.4 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
OCENA POZIOMU HAŁASU INSTALACJI WENTYLACJI |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Wartość zmierzona |
Lśr |
Lmax |
29.6 |
30.0 |
Wartość dopuszczalna |
30.0 |
30.0 |
|
|
|
Wartość średnia poziomu nie przekracza wartości dopuszczalne. |
|
|
|
UWAGA |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
UWAGI : |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Metoda pomiaru zgodna z PN-67/B-02156 ,,Akustyka budowlana. Metody kontroli poziomu dźwięku A w pomieszczeniach budynku". |
Ocena wykonana zgodnie z PN-87/B-02151/02 ,, Akustyka budowlana. Ochrona przed hałasem w budynku. Dopuszczalne wartości poziomu dźwięków w pomieszczeniach". |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Pomiary wkonał: |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Michał Mazur |
|
|
|
|
|
|