Cooling pump with manoeuvre alarm
File: Pump With Alarm.doc
Last edition: 2003-03-04
Author: Désirée Ilvemo/Mikael Krantz
History: 97-09-15/MK First released version.
98-03-09/MK Corrected unit.
98-12-29/MK New file name
2003-03-04/MK Updated to Menta 4.0
Description
The cooling pump is stopped if the valve has been closed longer time than the number of minutes given in "TimeBeforePumpStops". The pump is exercised for two minutes every Monday at noon.
Inputs
(Real) Control signal, 0-100%.
(Bin) Running indication pump.
Outputs
(Binary) Pump order
Parameters
(Real) TimeBeforePumpStops 10 minutes.
Public signals
(Real) TimeBeforePumpStops
(Bin) PumpAlarm