Experiment 2 8


Experiment 2-8

Single-Phase Full-Controlled AC Voltage Controller

OBJECTIVE

  1. To understand the differences between the single-phase full-controlled ac voltage controller and the single-phase semi-controlled ac voltage controller.

  2. To understand the characteristics of single-phase full-controlled ac voltage controller.

  3. To measure the voltage and current of single-phase full-controlled ac voltage controller.

  4. To verify characteristics of single-phase full-controlled ac voltage controller.

DISCUSSION

Compared with the single-phase semi-controlled (or halt-wave) ac voltage controller, both the positive and negative cycles of output voltage waveform of the single-phase full controlled (or full-wave) ac voltage controller are symmetrical and variable. To achieve these function two SCRs (inverse parallel operation) are employed in the single-phase semi-controlled ac voltage controller.

Figure 2-8-1 shows the circuit and waveforms of single-phase semi-controlled (full- wave) ac voltage controller with purely resistive load. During the positive half cycle of Vi, Q2 is reverse-biased and tuned off, Q1 is triggered and conducts at. t=. , in the interval. ≤. t≤. , Vi is connected to the load through Q1, and the output voltage is variable; during the negative cycle of Vi,Q1 is reverse-biased and turned off, Q2 is triggered to conduct at . t=. +. , in the interval . +. ≤. t≤2. , Vi is connected to load through Q2, and the output voltage is also variable. Triggering angle. can be varied from 0° to 180°, the corresponding voltage waveform is shown in Figure 2-8-1 (b). The triggering pulses of thyristors Q1 and Q2 must be isolated from each other, usually two pulse transformers are used to couple the triggering signals to the gates; otherwise, short circuit may occur. Since the pulse width of gate triggering signal is usually 20μs approximately, the required pulse transformer is quite small in size.

Figure 2-8-1 Circuit and waveforms of single-phase semi-controlled ac voltage controller with purely resistive load

In the single-phase semi-controlled ac voltage controller with a purely resistive load, input current li and output current lo are equal. As can be seen from Figure 2-8-1 (b), The input current of single-phase semi-controlled ac voltage controller is alternating symmetrical and has no dc component.

If Vi(rms) is the rms input voltage, by varying the SCR triggering angle . from 0° to 180°, the rms output voltage v . (rms) of single-phase semi-controlled ac voltage controller with purely resistive load can be varied from 0 to Vi(rms) . When . =0°, the output voltage waveform is identical to that of a single-phase full-wave diode rectifier, therefore V0°(rms) = Vi(rms) . When . = 180°, there is no output waveform; that is, V180°(rms)=0V. In the same way, the rms input current I . (rms) can be varied from 0 to Ii(rms), where Ii(rms) = Vi(rms) /R. The power delivered to load P. will vary from 0 to Pi and Pi = Vi(rms) x Ii(rms).

If V . (rms) is the rms value of ac output voltage of single-phase full-controlled ac voltage controller at firing angle . , 0x01 graphic
is the peak value of ac input voltage, thus

0x08 graphic

(2-8-2)

If I . (rms) is the rms value of ac current (this value is equal to the rms values of li and lo) of single-phase full-controlled ac voltage controller at firing angle . , IQ1(. ) and IQ2(. ) are the rms value of ac currents flowing through SCR Q1 and SRC Q2, respectively. Since positive and negative half cycles are symmetric, therefore I Q1(. ) are equal. Thus

0x08 graphic

(2-8-2)

Figure 2-8-2 shows he circuit and waveforms of single-phase full-controlled ac voltage controller with inductive to load. During the positive cycle of Vi, Q1 is fired to conduct at . t=. , Vi is applied to the load circuit through Q1 during the interval . ≤. t≤. . During the negative half cycle of Vi, due to the inductive load, Q1 continues to conduct until it reaches the angle . ; Q2 conducts at . t=. +. , in the . +. ≤. t≤2. interval, Vi is connected to load through Q2. During the next positive half cycle of Vi, Q2 continues to conduct until the angle 2. +. is reached.

Assume that the conduction angle of thyristor is. , impedance angle of load is ϕ, thus . =. -. , 0x01 graphic
. As can be seen from the waveforms in Figure 2-8-2(b), the conduction angle . cannot be larger than 180° and the triggering angle . cannot be less than ϕ; Otherwise, only one of the two thyristors can conduct in a complete cycle. For example, if Q1 is now conducting, gating signal IG2 cannot make Q2 conduct, therefore input current and load current are asymmertic and has dc component. There are two solutions: one is to extend the width of triggering pulse (continuous pulse) but a bigger pulse transformer is requited; the other is the use of high-frequency carrier gating signal (of pulse train). The second solution is more popular.

Figure 2-8-2 Circuit and waveforms of the single-phase full-controlled ac voltage controller with inductive load

EQUIPMENT REQUIRED

  1. PE-5340-3A Isolating Transformer x1

  2. PE-5310-5B Fuse set x1

  3. PE-5310-5C Thyristor Set x1

  4. PE-5310-3A R.M.S Meter x1

  5. PE-5310-2B Differential Amplifier x1

  6. PE-5310-3C Resistor Load Unit x1

  7. PE-5310-3E Inductive Load Unit x1

  8. PE-5310-2C Current Transducer x1

  9. PE-5310-1A DC Power Supply x1

  10. PE-5310-2A Reference Variable Generator x1

  11. PE-5310-2D 3ϕ Phase Angle Controller x1

  12. Digital Storage Oscilloscope (DSO) x1

  13. Connecting Wires and Bridging Plugs

PROCEDURE

  1. Put modules PE05310-1A, PE-5310-2A, PE-5310-2D, and PE-5310-5C in Experimental Frame. Place DSO, PE-5310-3C and PE-5340-3A modules on workbench. Complete the connections of Figure 2-8-3 using bridging plugs (curved lines) and connecting wires.

  1. This ac voltage controller operates from a single-phase 220V and the load circuit is a 200. resistor connected in series with a 200 mH inductor. On Reference Variable Generator module, set the Vc Range selector switch to 0~+10V position, and set the V control knob to its 0% position. On 3ϕ Phase Angle Controller module, select Single Pulse output (down position), set . min = 0° and . max=180°. The triggering angle can be varied from 0° to 180° by turning the V control knob of Reference Variable Generator.

Figure 2-8-3 Wiring diagram for single-phase full-controlled ac voltage controller experiment

  1. Short out the load inductor by placing a connecting wire directly across the inductor terminals . This makes a purely resistive load circuit. Turn the V control knob of Reference Variable Generator to read triggering angle . =60° from the 7-segment display on 3ϕ Phase Angle Controller module. Set the V Range selector switches of Differential Amplifiers Ch. A and Ch.C to 500V. Use DSO to measure the ac input voltage (CH1) and the load voltage (CH2) waveforms of ac voltage controller as shown in Figure 2-8-4. Practice a variety of triggering angles . and observe the changes in load voltage waveform.

Figure 2-8-4 Measured input voltage (CH1) and load voltage (CH2) waveforms of dingle-phase full-controlled ac voltage controller with purely resistive load

  1. Place the AC+DC/AC and RMS/AV selector switches of RMS meter in AC+DC and RMS positions, respectively. Adjust the V control knob of Reference Variable Generator to read triggering angle . =90° from the 7-segment display on 3ϕ Phase Angle Controller module. Measure the rms load current (equal to input current) value I. (rms) = _____A. Using the RMS Meter, measure the rms value of SCR Q1 current IQ1(.) = _____A., and the rms value of SCR Q2 current IQ2(. )= _____A. Does the result meet Eq. (2-8-2)? _____

  1. Remain the settings of RMS Meter in Step 4 uncharged. Set each of SCR triggering angles . indicated in Table 2-8-1, measure and record the corresponding rms voltage of the ac voltage controller.

Table 2-8-1 Measured V. Values of single-phase full-controlled ac voltage controller with purely resistive load.

  1. Using recorded values of V .(rms) in Table 2-8-1, calculate and record the ratio of

V .(rms)/Vi(rms) for each value of . , where Vi(rms) is the V .(rms) at . =0°.

Plot the V .(rms)/Vi(rms) versus. curve in Figure 2-8-5.

Figure 2-8-5 V .(rms) / Vi(rms) vs. . curve of single-phase full-controlled ac voltage controller with purely resistive load

  1. When the triggering angle . =90°, use Eq. (2-8-1) to calculate V90°(rms)=_____ Vi(rms) and V90°(rms)/ Vi(rms) =_____. Are the calculated values equal to the recorded values in table 2-8-1? _____

  1. Recover the load inductor by removing the connecting wire from inductor terminals. This modifies the purely resistive load to an inductive load. Repeat step 3 to measure the ac input voltage (CH1) and the load voltage (CH2) wave forms of ac voltage controller when . =60° and record the results in Figure 2-8-6.

Note: With inductive load, Single Pulse trigging is unsuitable when . <ϕ. Select Pulse Train output (up position) from 3ϕ Phase Angle Controller module.

CH1:

DIF AMP V Range:___

VOLTS/DIV:___

SEC/DIV: ___

CH2:

DIF AMP V Range:___

VOLTS/DIV:___

SEC/DIV:___

Figure 2-8-6 Measured input voltage (CH1) and load voltage (CH2) waveforms of

single-phase full-controlled ac voltage controller with inductive load .

  1. Remain the load circuit and settings of triggering angles in Step 8 uncharged. Modify the connections of Figure 2-8-3 to measure the ac input voltage (CH1) and the load current (CH2) via Current Transducer module, and record the results in Figure 2-8-7.

CH1:

DIF AMP V Range:___

VOLTS/DIV:___

SEC/DIV: ___

CH2:

DIF AMP V Range:___

Current Transducer

I Range: ___

VOLTS/DIV:___

SEC/DIV:___

Figure 2-8-7 Measured input voltage (CH1) and load current (CH2) waveforms of

single-phase full-controlled ac voltage controller with inductive load .

COMPUTER SIMULATION

  1. Run TINAPro. In Schematic Editor window, complete the simulation circuit as shown in Figure 2-8-8. Set input voltage source Vi as Sine wave, Amplitude to 311V, Frequency to 60Hz.

Figure 2-7-8 Simulation circuit of single-phase full-controlled ac voltage controller

  1. In Signal Editor dialog, select General wave and create the triggering pulses VG as reffering to Figure 2-4-9. Set Amplitude to 10V (A1=10V, A2=0V), Period to 16.67ms (T2=1ms, T6=15.67ms). set the triggering angle of SCR Q1 to 60° (TS=2.78ms), the triggering angle of SCR Q2 to 240° (TS=11.1ms). Once completed, click OK.

  1. Modyfi the load to a purely resistive circuit by setting inductance L to 0H. Run Analysis/Transient. In Transient Analysis dialog, set Stop display to 33.3ms and check the Draw excitation box. Once completed, click OK. The TR result is shown in Figure 2-8-9. Is there agreement between the TR result and your measured result of Figure

2-8-4? _________

Figure 2-8-9 TR result of single-phase full-controlled ac voltage controller with purely resistive load

  1. Modify the inductance L to 200mH to construct an inductive load . Repeat Step 3 to run Analysis/Transient and obtain the TR result as shown in Figure 2-8-10. Is there good agreement between the TR result and your measured results of Figures 2-8-6 and 2-8-7? ________

Figure 2-7-10 TR result of single-phase full-controlled ac voltage controller with inductive load

0x01 graphic

0x01 graphic



Wyszukiwarka

Podobne podstrony:
EXPERIENTIAL
Experimental avascular osteonecrosis
ExperimentsClass3Handouts
Interruption of the blood supply of femoral head an experimental study on the pathogenesis of Legg C
34 453 476 Creep of HSS Part I Experimental Investigations
French Experience S02E08
French Experience S02E02
On Programming Psychedelic Experiences
Experience bramy Manual
Das TFH CAN Bus Experimentalsystem
a Mat inf. dz.wykl 11 , 1 „Równowaga przeżywania"(EB=Experience Balance)
Linux 2000 DVB T Experiments
2010 experimental solutions
05?rly Experiences Pink
a Mat inf. dz.wykl 9 , 1 „Równowaga przeżywania"(EB=Experience Balance)
a Mat inf. dz.wykl 14, 1 „Równowaga przeżywania"(EB=Experience Balance)
3 etap 2010 experimental solutions
3 etap 2011 experimental solutions
DYWD Becoming The Irresistible Experienced Man
Experiences with a compound method2

więcej podobnych podstron