Heating and HEX control in sequence
File: Heat HEX.doc
Last edition: 4 of March 2003
Author: Mikael Krantz
History: 96-02-13/MK First released version.
96-10-03/MK Updated to Menta 1.20
97-09-02/MK Updated to Menta 3.0
98-03-09/MK Unit corrected.
98-12-30/MK New filename
2003-03-04/MK Updated to Menta 4.0
Description
Heating and HEX control in sequence, with separate P-band and I-times. If the flag for "Normal Control" is true, the main controller is activated, in other cases, the controller is set to closed valve and maximum HEX. The HEX can, however, be set to minimum by the "HEX min" flag. If the "Heating allowed" flag is false, the heating valve is closed. If the "HEX max" flag is true, the HEX is forced to max, if the "HEX min" flag is true, the HEX is forced to min. During this cases, the controlling is moved over to the heating valve.
Inputs
(Real) SP supply temperature, °C
(Real) Supply temperature, °C
(Binary) Normal control
(Binary) Heating allowed flag
(Binary) HEX Min flag
(Binary) HEX max flag
Outputs
(Real) HEX control signal 0 - 100%
(Real) Heat control signal 0 - 100%
Parameters
(Real) HeatingPBand 25 °C
(Real) HeatingITime 4 minutes
(Real) HEXPBand 25 °C
(Real) HEXITime 4 minutes
Public signals
(Real) Heating
(Real) HeatingPBand
(Real) HeatingITime
(Real) HEX
(Real) HEXPBand
(Real) HEXITime