HEX Thermal efficiency with supply sensor
File: HEX Efficiency Supply.doc
Last edition: 2003-03-04
Author: Mikael Krantz
History: 96-02-14/MK First released version.
96-09-30/MK Updated to Menta 1.20
Alarm block has new name and text.
Pri added on alarms.
97-08-27/MK Updated to Menta 3.0
98-12-21/MK New filename
2003-03-04/MK Updated to Menta 4.0
Description
t2 - t1
Formula: -------
t3 - t1
where t1 = Supply temperature before HEX.
t2 = Supply temperature after HEX
t3 = Return temperature before HEX
t4 = return temperature after HEX
Efficiency calculation for Heat exchanger with use of an supply air temperature sensor placed after the heat exchanger. The efficiency is calculated as a value between 0 and 100%. An alarm is set if the efficiency is to low while the HEX control is above a set limit. If the numerator or the denominator are below 2°C, or if the running signal is false, the calculation output is zero, and the alarm interlocked.
Inputs
(Real) Inlet temperature
(Real) Outlet temperature
(Real) Outdoor temperature
(Real) HEX Control signal, 0-100%.
(Binary) Running signal
Outputs
(Real) Thermal efficiency 0-100%
(Binary) Low alarm thermal efficiency
Parameters
(Real) EfficiencyLimit 40%
(Real) HEXControlLimit 90%
Public signals
(Real) EfficiencyLimit
(Real) HEXEfficiency
(Real) HEXControlLimit
(Binary) HEXAlarm