Supply control
File: Supply Control.doc
Last edition: 4 of March 2003
Author: Mikael Krantz
History: 96-02-13/MK First released version.
96-10-03/MK Updated to Menta 1.20
97-08-29/MK Updated to Menta 3.0.
98-12-30/MK New filename
2003-03-04/MK Updated to Menta 4.0
Description
Calculates "Cooling case" flag and actual setpoint for supply air controller. Switch over between heating and cooling case is interlocked until the control signal is equal to zero. If the "Cooling allowed" flag is false, the cooling case is blocked.
Inputs
(Real) SP cooling, °C
(Real) SP heating, °C
(Real) Supply temperature, °C
(Real) Control signal, %
(Binary) Cooling allowed flag
Outputs
(Real) SP supply temperature, °C
(Binary) Cooling case (00=heating, 1= cooling)
Parameters
Public signals
(Real) ActualSP
(Bin) CoolingCase