Water flow in m3
File: flow_m3.doc
Last edition: 2003-03-11
Author: Mikael Krantz
History: 98-01-05/MK First released version.
98-03-09/MK Corrected unit.
2003-03-11/MK Updated to Menta 4.0
Description
Calculates water flow in m3 during last day and last month from a pulse counter.
Note that the scalefactor shall be given in pulse/m3.
Inputs
(Real) Water flow pulses
Outputs
(Real) Water flow last day, m3.
(Real) Water flow last month, m3.
Parameters
(Real) Water flow Scale factor 1 pulse/m3
Public signals
(Real) WaterflowCount
(Real) WaterflowLastDay
(Real) WaterflowLastMonth
(Real) WaterflowSCF
(Real) WaterflowThisMonth