Rys. 7. Izolacja rejonów gięcia
VI. Mocowanie rur
Dla zapewnienia prawidłowej pracy rur ich mocowanie (podpory ślizgowe) winno mieć miejsce w określonych odstępach. I tak:
ROZSTAW PODPÓR [m] (rury poziome) PVC-C | |||||
Średn. rury |
Temperatura [°C] | ||||
[cal] |
20 |
40 |
60 |
80 |
90 |
;= 1/2” |
0.75 |
0.70 |
0.65 |
0.60 |
0.50 |
a: 3/4” |
0.85 |
0.80 |
0.70 |
0.65 |
0.55 |
o 1" |
0.90 |
0.85 |
0.75 |
0.70 |
0.60 |
to 11/4" |
1.00 |
0.95 |
0.85 |
0.75 |
0.65 |
{2 1 1/2" |
1.10 |
1.05 |
0.95 |
0.80 |
0.75 |
O 2" |
1.25 |
1.15 |
1.05 |
0.90 |
0.80 |
g 21/2" |
2.40 |
2.25 |
1.95 |
1.20 |
1.00 |
2.40 |
2.40 |
2.10 |
1.20 |
1.05 | |
2.40 |
2.70 |
2.25 |
1.35 |
1.10 |
ROZSTAW PODPÓR [m] (rury poziome) PVC-U SCH40 | |||
Średn. rury |
Temperatura [°C] | ||
[cal] |
20 |
40 |
60 |
1/2” |
1.10 |
1.05 |
0.9 |
3/4" |
1.25 |
1.10 |
1.0 |
1” |
1.45 |
1.25 |
1.1 |
1 1/4" |
1.60 |
1.40 |
1.2 |
1 1/2" |
1.65 |
1.60 |
1.35 |
2" |
1.90 |
1.70 |
1.5 |
21/2" |
2.20 |
1.90 |
1.65 |
3" |
2.40 |
2.10 |
1.8 |
4" |
2.80 |
2.40 |
2.1 |
6" |
3.30 |
3.00 |
2.5 |
8" |
3.60 |
3.45 |
3.0 |
Uchwyty metalowe z podkładką ściśliwą stosować tylko w przypadkach koniecznych, np. punkty stałe, mocowanie przyborów.
Uwaaa: Dla rur prowadzonych pionowo podane odległości można zwiększyć mnożąc je przez 1.3 dla temperatury do 60°C i przez 1.2 dla wyższej temperatury.
Przy montowaniu na rurze przyborów, baterii etc. należy zapewnić im niezależne podparcia.
Należy pamiętać, aby rury pionowe miały mocowanie przy każdym przejściu przez stropy oraz przy zmianie kierunku o 90°. Mocowania muszą uwzględnić ramię kompensujące.