ca64adr mod e

background image

®

ADDRESSABLE

MODULE

CA-64 ADR-MOD

ca64adr_mod_e 11/05

1.

Module description

The CA-64 ADR-MOD module is a device intended for changing a typical alarm detector
(NO, NC) into an addressable detector. Such detectors work together with the CA-64 ADR
addressable zones expander. The module is suitable for installation inside the detector
housing (dimensions: 37/17/8mm).





Fig. 1. View of the module CA-64 ADR-MOD


Description of the cables:
white

- COM (common ground)

black

- INT (data – module bus)

blue

- NC/NO (detector signal input)

red

- +12V (module supply input)

2. Module operation

The common ground COM is connected to the input NC/NO (blue lead) via the detector
contacts (C,NC). Using digital transmission, the module informs the expander through the
lead INT (black color) of the status of expander contacts (closed/open). The expander, in
turn, interprets the received data and, depending on the preprogrammed settings, sends
information on the zone status to the control panel. The status of each detector contacts is
tested several times per second.

3. Connection of the module to the detector

Maximum distance between the CA-64 ADR expander and the detector is 1000m. The
detectors with modules should be supplied from the expander POW output. Detector supply
common ground, as well as signal and CA-64 ADR-MOD module supply common ground,
need to be connected to the expander with a separate leads (see Fig. 2 and 3).

3.1 Connection without tamper control
Detector TMP terminals should be connected to the separate tamper circuit. The given zone
detector configuration is to be programmed as NO or NC, according to the type of connected
detector.

white
black

blue

red

background image

SATEL

CA-64

ADR

MOD

2

Fig. 2. The example of connection without tamper circuit.

3.2 Connection with tamper control
Detector TMP terminals should be connected to module CA-64 ADR-MOD supply circuit. The
given zone detector configuration is to be programmed as 2EOL/NO or 2EOL/NC, according
to the type of connected detector.

Fig. 3. The example of connection with tamper control.

Note: Selecting the EOL line type is treated by the control panel as connecting the NC type

detector without tamper control.

Informations regarding CA-64 ADR-MOD module addressing and addressable zones
numbering in the alarm system are included in the CA-64 ADR manual.

SATEL sp. z o.o.

ul. Schuberta 79

80-172 Gdańsk

POLAND

tel. + 48 58 320 94 00

info@satel.pl

www.satel.pl

The latest EC declaration of
conformity and certificates are
available for downloading on
website www.satel.pl

CA-64 ADR

detector

white
black
blue
red

detector supply common ground

signal and module supply common ground

white
black
blue
red

detector

CA-64 ADR

detector supply common ground

signal and module supply common ground


Wyszukiwarka

Podobne podstrony:
ca64adr mod
ca64adr mod
ca64adr mod pl
Mała chirurgia II Sem IV MOD
W11 mod
sem mod imp(1)
W12 mod
mod części 15 07
P20 HH Mod
interna mod 1
Mod ryz lacz
10 2009 Twierdzenia mod n
Spr mod 2
lecture 15 Multivariate and mod Nieznany
mod 2007 8 FM
bb1 ep mod 9

więcej podobnych podstron