APR-2000G Smart differential pressure
transmitter for non-aggressive gases
ü Programmable zero shift, range and damping ratio
ü Selectable linear or radical conversion characteristics
ü Standard Bell 202 communication (Hart protocol compatible)
ü Conversion error from 0.16%, digital compensation of additional errors
ü Exi
a
I/IICT6 spark proof
Application
Our APR-2000G transmitter is designed to measure pressure,
underpressure and differential pressure of non-corrosive
gases. Typical applications include the measurement of blast
pressure, chimney draughts or pressure/underpressure in
furnace chambers. The ability to select the radical conversion
characteristics enables the transmitter to be used in gas-flow
measurement systems using reducing pipes or other impeding
elements. The transmitter is built to withstand up to 35 kPa
overpressure. The housing of the electronic circuit is IP 65
rated.
Configuration, calibration
You can select the following settings of metrological parame-
ters:
♦
Pressure units for the active measurement range
♦
End-points of range, damping
♦
Radical conversion characteristics
♦
Inverted characteristics (output signal 20 ÷ 4 mA).
Ability to perform zero shift and calibration against pressure
standard.
Communication
Hart protocol with 4 ÷ 20 mA signal. Setting and calibration
through KAP-01 communicator unit, some Hart compatible
communicators or a PC through an RS-Hart interface and
Aplisens RAPORT-01 software. APR-2000G data transfer also
supports transmitter identification, as well as current readings
of pressure difference, output current and percentage of
measuring range.
Assembly
The economical version can be mounted on any stable con-
struction using the assembly fixture with
∅
9 opening. The
transmitter includes pipe stubs with terminals to connect to an
elastic
∅
6×1 impulse line. Where the pulse comes via a metal
pipe, we suggest the use of an M20×1.5 adapter for a
∅
6×1
fitting.
The transmitter with a C type connector should be mounted on
a 3- or 5-valve manifold. We recommend the use of our pre-as-
sembled transmitters with VM type valves (page 44).
Aplisens
KAP-01
Communicator
APR-2000G Industrial Version,
process
connector to mount together with a valve manifold
An example with
Electrical Connector
C type
PZ type
APR-2000G Economical Version,
process
connector, pipe stubs with terminal connecting to 6 pipe
An example with
Electrical Connector
PCV type
PD type
∅
range
from
100 Pa
Adapter for
valve manifold or
steel impulse lines
M20×1.5/ 6×1 adapter
∅
PCV pipe 6×1
∅
PZ
type
Terminal
Box
with
PG-1
1
Packing
Gland
and
earth
terminal;
IP
65
rated
Ingress
Protection
∅
51
130
∅
5...10
Cable
∅
51
∅
6...9 Cable
PD type
Electrical Connector
DIN 43650 with PG-11
Packing Gland;
IP 65 rated
Ingress Protection
34
105
50
4 ×
∅
9
28
54
M8×10
15 HM steel
weldable impulse
line connector
∅
12
∅
14
¼ NPT
APLISENS Sp. z o.o., ul. Morelowa 7
, tel. +4822 8140 777
fax +4822 8140 778, www.aplisens.com.pl, e-mail: aplisens@
.pl
, 03-192 Warszawa
aplisens.com
Version II/2002
Operating guidelines
The transmitter should be mounted in a vertical position. The impulse lines should be connected in such a way as to
ensure that any condensation flows off away from the device.
Where there is a significant difference in height between the place where the transmitter is mounted and the place where
the pulse is taken, the measurement may vary with the temperature of the impulse line. This effect can be minimized by
connecting a compensating pipe close to the impulse line, from the transmitter’s reference pipe stub to the height at
which the impulse is taken.
To prevent dust from entering the measuring cells, the impulse lines should be attached with care, with particular atten-
tion to the tightness of the connections between the impulse lines and the transmitter.
Measurement ranges
Maximum Range (MR)
Minimum Range
Zero Suppression Limit
Overpressure
Limit
Static Pressure
Limit
0...2500 Pa
100 Pa
0...2400 Pa
35 kPa
35 kPa
-700...700 Pa
100 Pa
-700...600 Pa
35 kPa
35 kPa
-2500...2500 Pa
500 Pa
-2500...2000 Pa
35 kPa
35 kPa
-10...10
kPa
2 kPa
-10...8
kPa
100 kPa
100 kPa
Metrological parameters
Maximum Range
0...2500 Pa
-700...700 Pa
-2500...2500 Pa
-10...10 kPa
Accuracy
≤
±0.16%
≤
±0.2%
≤
±0.2%
≤
±0.2%
Preset Range
0...100 Pa
-50...50 Pa
-250...250 Pa
-1...1 kPa
Accuracy
≤
±1%
≤
±1.6%
≤
±1%
≤
±1%
Thermal error
≤
±0.1% (MR) / 10°C
Thermal compensation range -10...70°C
max ±0.4% (MR) for the whole thermal compensation range
Damping of the sensing module 0.3 s
Additional electronic damping 0...30 s
Error related to changes of U
sup
0.002% (MR) / V
Electrical parameters
Power supply
10...30 V DC
Output signal
4...20 mA two wire transmission
Resistance required for communication 250...1100
Ω
Load resistance R [
U
V]
V
A
sup
Ω
]
[
.
.
≤
−
⋅
10
0 02
0 95
Operating conditions
Ambient temperature limit -25...85°C
Materials: case – 0H18N9 (304ss),
adapters: C – 316Ti, M20×1.5/
∅
6×1 – brass,
valve manifold – resistant steel 316ss
Example 1: APR-2000G transmitter / maximum range -700...700 Pa / terminal box / preset range -50...100 Pa / PCV type
process connector. Two additional M20×1.5/ 6×1 adapters.
∅
APR-2000G / -700 ÷ 700 Pa / PZ / -50 ÷ 100 Pa / PCV / + two M20×1.5/ 6×1 adapters
∅
Example 2: APR-2000G transmitter / maximum range 0...2500 Pa / connector / preset range 0...250 Pa / C type process
connector. Additional VM-3 three-valve manifold.
APR-2000G / 0 ÷ 2500 Pa / PD / 0 ÷ 250 Pa / C / + valve VM-3
1
2
3
4 ÷ 20 mA
e.g. Aplisens
ZL-24
+
–
Electrical diagram
Power
supply
250
< R < 1100
Ω
Ω
Connection to
the communicator
or interface
R – Total resistance of the current loop
Electrical connection of the transmitter
should be made with a twisted pair cable. It
is useful to have free wires for connection of
the communicator.
APR-2000G /___/__÷__/___/__÷__/___
Ordering procedure
Maximum range
Type of Electrical Connector PD, PZ
Process connector: PCV type or C type
End of preset range – in relation to 20 mA output
Start of preset range – in relation to 4 mA output
PD connector
Extra features: Ex