APR-2000G Smart differential pressure

transmitter for non-aggressive gases

ü Programmable zero shift, range and damping ratio

ü Selectable linear or radical conversion characteristics

ü Standard Bell 202 communication (Hart protocol compatible)

ü Conversion error from 0.16%, digital compensation of additional errors

ü Exi

a

I/IICT6 spark proof

Application

Our APR-2000G transmitter is designed to measure pressure,

underpressure and differential pressure of non-corrosive

gases. Typical applications include the measurement of blast

pressure, chimney draughts or pressure/underpressure in

furnace chambers. The ability to select the radical conversion

characteristics enables the transmitter to be used in gas-flow

measurement systems using reducing pipes or other impeding

elements. The transmitter is built to withstand up to 35 kPa

overpressure. The housing of the electronic circuit is IP 65

rated.

Configuration, calibration

You can select the following settings of metrological parame-

ters:

Pressure units for the active measurement range

End-points of range, damping

Radical conversion characteristics

Inverted characteristics (output signal 20 ÷ 4 mA).

Ability to perform zero shift and calibration against pressure

standard.

Communication

Hart protocol with 4 ÷ 20 mA signal. Setting and calibration

through KAP-01 communicator unit, some Hart compatible

communicators or a PC through an RS-Hart interface and

Aplisens RAPORT-01 software. APR-2000G data transfer also

supports transmitter identification, as well as current readings

of pressure difference, output current and percentage of

measuring range.

Assembly

The economical version can be mounted on any stable con-

struction using the assembly fixture with

9 opening. The

transmitter includes pipe stubs with terminals to connect to an

elastic

6×1 impulse line. Where the pulse comes via a metal

pipe, we suggest the use of an M20×1.5 adapter for a

6×1

fitting.
The transmitter with a C type connector should be mounted on

a 3- or 5-valve manifold. We recommend the use of our pre-as-

sembled transmitters with VM type valves (page 44).

Aplisens

KAP-01

Communicator

APR-2000G Industrial Version,

process

connector to mount together with a valve manifold

An example with

Electrical Connector

C type

PZ type

APR-2000G Economical Version,

process

connector, pipe stubs with terminal connecting to 6 pipe

An example with

Electrical Connector

PCV type

PD type

range

from

100 Pa

Adapter for

valve manifold or

steel impulse lines

M20×1.5/ 6×1 adapter

PCV pipe 6×1

PZ

type

Terminal

Box

with

PG-1

1

Packing

Gland

and

earth

terminal;

IP

65

rated

Ingress

Protection

51

130

5...10

Cable

51

6...9 Cable

PD type

Electrical Connector

DIN 43650 with PG-11

Packing Gland;

IP 65 rated

Ingress Protection

34

105

50

4 ×

9

28

54

M8×10

15 HM steel

weldable impulse

line connector

12

14

¼ NPT

background image

APLISENS Sp. z o.o., ul. Morelowa 7

, tel. +4822 8140 777

fax +4822 8140 778, www.aplisens.com.pl, e-mail: aplisens@

.pl

, 03-192 Warszawa

aplisens.com

Version II/2002

Operating guidelines

The transmitter should be mounted in a vertical position. The impulse lines should be connected in such a way as to

ensure that any condensation flows off away from the device.
Where there is a significant difference in height between the place where the transmitter is mounted and the place where

the pulse is taken, the measurement may vary with the temperature of the impulse line. This effect can be minimized by

connecting a compensating pipe close to the impulse line, from the transmitter’s reference pipe stub to the height at

which the impulse is taken.
To prevent dust from entering the measuring cells, the impulse lines should be attached with care, with particular atten-

tion to the tightness of the connections between the impulse lines and the transmitter.

Measurement ranges

Maximum Range (MR)

Minimum Range

Zero Suppression Limit

Overpressure

Limit

Static Pressure

Limit

0...2500 Pa

100 Pa

0...2400 Pa

35 kPa

35 kPa

-700...700 Pa

100 Pa

-700...600 Pa

35 kPa

35 kPa

-2500...2500 Pa

500 Pa

-2500...2000 Pa

35 kPa

35 kPa

-10...10

kPa

2 kPa

-10...8

kPa

100 kPa

100 kPa

Metrological parameters

Maximum Range

0...2500 Pa

-700...700 Pa

-2500...2500 Pa

-10...10 kPa

Accuracy

±0.16%

±0.2%

±0.2%

±0.2%

Preset Range

0...100 Pa

-50...50 Pa

-250...250 Pa

-1...1 kPa

Accuracy

±1%

±1.6%

±1%

±1%

Thermal error

±0.1% (MR) / 10°C

Thermal compensation range -10...70°C

max ±0.4% (MR) for the whole thermal compensation range

Damping of the sensing module 0.3 s

Additional electronic damping 0...30 s

Error related to changes of U

sup

0.002% (MR) / V

Electrical parameters

Power supply

10...30 V DC

Output signal

4...20 mA two wire transmission

Resistance required for communication 250...1100

Load resistance R [

U

V]

V

A

sup

]

[

.

.

10

0 02

0 95

Operating conditions

Ambient temperature limit -25...85°C
Materials: case – 0H18N9 (304ss),

adapters: C – 316Ti, M20×1.5/

6×1 – brass,

valve manifold – resistant steel 316ss

Example 1: APR-2000G transmitter / maximum range -700...700 Pa / terminal box / preset range -50...100 Pa / PCV type

process connector. Two additional M20×1.5/ 6×1 adapters.

APR-2000G / -700 ÷ 700 Pa / PZ / -50 ÷ 100 Pa / PCV / + two M20×1.5/ 6×1 adapters

Example 2: APR-2000G transmitter / maximum range 0...2500 Pa / connector / preset range 0...250 Pa / C type process

connector. Additional VM-3 three-valve manifold.

APR-2000G / 0 ÷ 2500 Pa / PD / 0 ÷ 250 Pa / C / + valve VM-3

1

2

3

4 ÷ 20 mA

e.g. Aplisens

ZL-24

+

Electrical diagram

Power

supply

250

< R < 1100

Connection to

the communicator

or interface

R – Total resistance of the current loop

Electrical connection of the transmitter

should be made with a twisted pair cable. It

is useful to have free wires for connection of

the communicator.

APR-2000G /___/__÷__/___/__÷__/___

Ordering procedure

Maximum range

Type of Electrical Connector PD, PZ

Process connector: PCV type or C type

End of preset range – in relation to 20 mA output

Start of preset range – in relation to 4 mA output

PD connector

Extra features: Ex


Wyszukiwarka

Podobne podstrony:
APR 2000G(1)
APR 2000G
APR 2000G
APR 2000(1)
APR 2000
Int Apr
badanie temperaturowej zale˝no—ci oporu pŕťprzewodnika
Gurus on Leadership apr 2005
APR 2000Y
Int Apr
Andromeda Spaceways Inflight Magazine [Mar Apr 06] Issue"
Kwasy karboksylowe Apr 2009(1)
CSR Big Amp Test 3 Mar Apr 1989
DTR.APR...01, Instrukcje, aplisens, dtr
LQ12S08 15 Apr 97
egrid apr id 151011 Nieznany
APR-2200, Instrukcje, aplisens,

więcej podobnych podstron