Pump control
File: Pump Cut Off.doc
Last edition: 2003-03-04
Author: Mikael Krantz
History: 96-02-13/MK First released version.
96-10-02/MK Updated to Menta 1.20
97-08-29/MK Updated to Menta 3.0
98-12-29/MK New file name
2003-03-04/MK Updated to Menta 4.0
Description
The pump is stopped (Cut off) if the outdoor temp during summer period exceeds a "CutOff" set limit. There is also a hysteresis of 1.5°C before the pump restart. During Cut off, the pump is exercised at noon on a daily basis. During winter period, the pump runs continuously.
Inputs
(Real) Outdoor temperature, °C
(Binary) Summer flag
Outputs
(Binary) Pump control flag
Parameters
(Real) CutOffLimit 17 °C
Public signals
(Binary) PumpOrder
(Binary) PumpCutOff
(Real) CutOffLimit