POLITECHNIKA RZESZOWSKA
Wydział Elektrotechniki i Informatyki
Przesył energii elektrycznej
Badanie rozpływu mocy w liniach wysokiego napięcia dwustronnie zasilanych.
Kopczyk Władysław
Kępa Robert
3 ENDI
1.Sieć z jednym generatorem-rozpływ mocy.
Area 1 - Home
Number of Buses: 2
Total Load: 250,0 MW 80,0 MVAR
Total Generation: 0,0 MW 0,0 MVAR
Losses: 6,8 MW 19,3 MVAR
Actual Tie Line Flow: -256,8 MW To Area 2
Unserved Load: 0,0 MW
Interchange Error: -2,57
Tie Lines for Area 1 - Home
Area Bus Other Area Bus ID MW Leave MVR Leave MWLoss MVRLoss Meter |
---|
3 2 1 1 -119,5 -50,1 2,5 8,4 1 |
2 2 1 1 -137,3 -49,2 4,3 10,6 1 |
Bus Information for Area 1 - Home
Number Name Area kV Level LoadMW LoadMVR GenMW GenMVR Volt Angle Shunt |
---|
|
|
Load Information for Area 1 - Home
Bus ID Area Zone MW MVR |
---|
2 1 1 1 150 50 |
3 1 1 1 100 30 |
Generator Information for Area 1 - Home
Bus ID Area Zone MW MVR
Switched Shunt Information for Area 1 - Home
Bus Reg. Area Zone MVR
Transmission Line Information for Area 1 - Home
From To ID MVA % Loaded Loss-MW Loss-MVR Amps Tap |
---|
1 2 1 145,9 48,6 4,26 10,64 244,1 |
1 3 1 129,6 43,2 2,52 8,40 216,9 |
2 3 1 20,4 8,2 0,07 0,23 36,0 |
Area 2 - 2
Number of Buses: 1
Total Load: 0,0 MW 0,0 MVAR
Total Generation: 256,8 MW 99,3 MVAR
Losses: 0,0 MW 0,0 MVAR
Actual Tie Line Flow: 256,8 MW To Area 1
Unserved Load: 0,0 MW
Interchange Error: 2,57
Tie Lines for Area 2 - 2
Area Bus Other Area Bus ID MW Leave MVR Leave MWLoss MVRLoss Meter |
---|
1 1 3 1 119,5 50,1 2,5 8,4 1 |
1 1 2 1 137,3 49,2 4,3 10,6 1 |
Bus Information for Area 2 - 2
Number Name Area kV Level LoadMW LoadMVR GenMW GenMVR Volt Angle Shunt |
---|
1 1 2 345 0 0 257 99 1,0 0,0 0 |
Load Information for Area 2 - 2
Bus ID Area Zone MW MVR
Generator Information for Area 2 - 2
Bus ID Area Zone MW MVR
1 1 2 1 257 99
Switched Shunt Information for Area 2 - 2
Bus Reg. Area Zone MVR
Transmission Line Information for Area 2 - 2
From To ID MVA % Loaded Loss-MW Loss-MVR Amps Tap |
---|
1 2 1 145,9 48,6 4,26 10,64 244,1 |
1 3 1 129,6 43,2 2,52 8,40 216,9 |
Obliczenia parametrów sieci zamkniętej:
Parametry podłużne: $R_{l} = P\frac{U^{2}}{S^{2}}$ $X_{l} = Q\frac{U^{2}}{S^{2}}$
Nr linii Parametr |
1-2 | 1-3 | 2-3 |
---|---|---|---|
Rl |
25,78 Ω | 21,45 Ω | 22,09 Ω |
Xl |
71,38 Ω | 74,01 Ω | 81,8 Ω |
Szyna I : U1 = 1 • 345 kV = 345 kV
Szyna II: U2 = 0, 95 • 345 kV = 327, 75 kV
Szyna III: U3 = 0, 96 • 345 kV = 331, 2 kV
Numer linii | 1-2 | 1-3 | 2-3 |
---|---|---|---|
Spadek napięcia | 17,25 V | 13,8 V | 3,45 V |
Sprawność przesyłu mocy:
$\eta = \frac{P_{\text{odb.}}}{P_{\text{gen.}}}$ Pgen. = 257MW Podb. = 150 • 106 + 100 • 106 = 250 MW
$$\eta = \frac{250 \bullet 10^{6}}{257 \bullet 10^{6}} \bullet 100\% = 97,3\ \%$$
2.Dwa generatory-symulacja sieci.
Area 1 - Home
Number of Buses: 2
Total Load: 250,0 MW 80,0 MVAR
Total Generation: 60,0 MW 120,8 MVAR
Losses: 3,6 MW 10,5 MVAR
Actual Tie Line Flow: -193,6 MW To Area 2
Unserved Load: 0,0 MW
Interchange Error: -1,94
Tie Lines for Area 1 - Home
Area Bus Other Area Bus ID MW Leave MVR Leave MWLoss MVRLoss Meter |
---|
3 2 1 1 -99,8 -4,3 1,5 5,0 1 |
2 2 1 1 -93,9 34,6 2,0 5,0 1 |
Bus Information for Area 1 - Home
Number Name Area Level LoadMW LoadMVR GenMW GenMVR Volt Angle Shunt |
---|
2 2 1 345 150 50 60 121 1,00 -3,1 0 |
3 3 1 345 100 30 0 0 0,98 -2,9 0 |
Load Information for Area 1 - Home
Bus ID Area Zone MW MVR |
---|
2 1 1 1 150 50 |
3 1 1 1 100 30 |
Generator Information for Area 1 - Home
Bus ID Area Zone MW MVR |
---|
2 1 1 1 60 121 |
Switched Shunt Information for Area 1 - Home
Bus Reg. Area Zone MVR
Transmission Line Information for Area 1 - Home
From To ID MVA % Loaded Loss-MW Loss-MVR Amps Tap |
---|
1 2 1 100,1 33,3 2,00 5,00 167,4 |
1 3 1 99,9 33,3 1,50 4,99 167,1 |
2 3 1 31,3 20,8 0,15 0,49 52,3 |
Area 2 - 2
Number of Buses: 1
Total Load: 0,0 MW 0,0 MVAR
Total Generation: 193,6 MW -30,4 MVAR
Losses: 0,0 MW 0,0 MVAR
Actual Tie Line Flow: 193,6 MW To Area 1
Unserved Load: 0,0 MW
Interchange Error: 1,94
Tie Lines for Area 2 - 2
Area Bus Other Area Bus ID MW Leave MVR Leave MWLoss MVRLoss Meter |
---|
1 1 3 1 99,8 4,3 1,5 5,0 1 |
1 1 2 1 93,9 -34,6 2,0 5,0 1 |
Bus Information for Area 2 - 2
Number Name Area kV Level LoadMW LoadMVR GenMW GenMVR Volt Angle Shunt |
---|
1 1 2 345 0 0 194 -30 1,00 0,0 0 |
Load Information for Area 2 - 2
Bus ID Area Zone MW MVR
Generator Information for Area 2 - 2
Bus ID Area Zone MW MVR |
---|
1 1 2 1 194 -30 |
Switched Shunt Information for Area 2 - 2
Bus Reg. Area Zone MVR
Transmission Line Information for Area 2 - 2
From To ID MVA % Loaded Loss-MW Loss-MVR Amps Tap |
---|
1 2 1 100,0 33,3 2,00 5,00 167,4 |
1 3 1 99,9 33,3 1,50 4,99 167,1 |
Obliczenia parametrów sieci zasilanej z 2 generatorów
Parametry podłużne: $R_{l} = P\frac{U^{2}}{S^{2}}$ $X_{l} = Q\frac{U^{2}}{S^{2}}$
Nr linii Parametr |
1-2 | 1-3 | 2-3 |
---|---|---|---|
Rl |
25,93 Ω | 22,1 Ω | 19,98 Ω |
Xl |
71,24 Ω | 74,01 Ω | 72,3 Ω |
Szyna I : U1 = 1 • 345 kV = 345 kV
Szyna II: U2 = 1 • 345 kV = 345 kV
Szyna III: U3 = 0, 98 • 345 kV = 338, 1 kV
Numer linii | 1-2 | 1-3 | 2-3 |
---|---|---|---|
Spadek napięcia | 0 V | 6,9 V | 6,9 V |
Sprawność przesyłu mocy: $\mathbf{\ \eta =}\frac{\mathbf{P}_{\mathbf{\text{odb.}}}}{\mathbf{P}_{\mathbf{\text{gen.}}}}$
Pgen. = 197 • 106 + 60 • 106 = 257MW Podb. = 100 • 106 + 150 • 106 = 250 MW
$$\eta = \frac{250 \bullet 10^{6}}{257 \bullet 10^{6}} \bullet 100\% = 97,3\ \%$$
3. Układ otwarty-schemat.
WNIOSKI:
Na podstawie tego ćwiczenia, mamy możliwość porównać dwie sieci-jedną zasilaną z jednego generatora i drugą-zasilaną dwoma generatorami. Przy zasilaniu dwoma generatorami mamy większe bezpieczeństwo i pewność zasilania, a obliczone parametry klarują się na podobnym poziomie. W przypadku zasilania z dwóch generatorów spadki napięcia były mniejsze niż w momencie zasilania jednym generatorem.
Sieć zamknięta jest lepsza od sieci otwartej. Na schemacie sieci otwartej widać, że linia przesyłowa 1-3 jest przeciążona i z tego względu nie może pracować zbyt długo. Taki stan nazywamy stanem awaryjnym.