Micrologic
Control units 2.0 and 5.0

Low Voltage Products

User manual

We do more with electricity.

<< Back

background image

Micrologic 2.0, 5.0

Schneider Electric

1

Discovering your control unit

2

Identifying your control unit

2

Overview of functions

4

Setting your control unit

6

Setting procedure

6

Setting the Micrologic 2.0 control unit

7

Setting the Micrologic 5.0 control unit

8

Testing the control unit

9

Technical appendix

10

Tripping curves

10

Changing the long-time rating plug

11

Thermal memory

12

Micrologic
Control units 2.0 and 5.0

background image

Micrologic 2.0, 5.0

Schneider Electric

2

Discovering your
control unit

E51266B

E51450A

All Compact NS800-3200 and Masterpact
NT and NW circuit breakers are equipped
with a Micrologic control unit that can be
changed on site.
Control units are designed to protect
power circuits and connected loads.

Identifying your control unit
Designations

E51352A

X: type of protection

c

2 for basic protection

c

5 for selective protection

c

6 for selective + earth-fault protection

c

7 for selective + earth-leakage protection.

Y: version number
Identification of the control-unit generation.
"0" signifies the first generation.

Z: type of measurement

c

A for "ammeter"

c

P for "power meter"

c

H for "harmonic meter"

c

no indication = no measurements.

Micrologic 2.0: basic protection

Long time + Instantaneous

Micrologic 5.0: selective protection

Long time + Short time + Instantaneous

E51353A

E51354A

0

Ir

Isd

I

t

0

Ir

I

t

Ii

Isd

Micrologic 2.0 A

Y

X

Z

Micrologic 2.0

.4

.5

.6

.7

.8

.9

.95
.98

1

x Ir

2

2.5

3

4

5

6

8

10

1.5

setting

Isd

.5

1

2

4

8

12

16
20

instantaneous

long time

alarm

Ir

tr
(s)

x In

at 6 Ir

24

Micrologic 5.0

setting

delay

short time

I i

tsd
(s)

long time

alarm

x In

3

4

6

8

10

12
15

off

2

.4

.5

.6

.7

.8

.9

.95
.98

1

Ir

x In

x Ir

2

2.5

3

4

5

6
8

10

Isd

1.5

.5

1

2

4

8

12

16
20

tr
(s)

at 6 Ir

24

on

I

2

t

.

2

.

3

.

4

.

4

.

1

.

2

.

3

.

1

0

instantaneous

background image

Micrologic 2.0, 5.0

Schneider Electric

3

1

top fastener

2

bottom fastener

3

protective cover

4

cover opening point

5

lead-seal fixture for protective cover

6

long-time rating plug

7

screw for long-time rating plug

8

connection with circuit breaker

Presentation

E51355A

E51356A

E51357A

Adjustment dials

9

long-time current setting Ir

10

long-time tripping delay tr

11

short-time pickup Isd

12

short-time tripping delay tsd

13

instantaneous pick-up Isd

14

instantaneous pick-up Ii

15

LED indicating an overload

16

test connector

Micr

olog

ic 2.0

.4

.5

.6

.7

.8 .9

.95
.98

1

.5

1

2

4

8 12

16
20

24

long

time

alarm

Ir

tr
(s)

x In

@

6 Ir

10

1

5

3

7

6

4

2

8

Micrologic 5.0

setting

delay

short time

long time

alarm

4

.4

.5

.6

.7

.8

.9

.95
.98

1

Ir

x In

.5

1

2

4

8

12

16
20

tr

(s)

at 6 Ir

24

I i

x In

3

6

8

10

12
15

off

2

tsd

(s)

on

I

2

t

.

2

.

3

.

4

.

4

.

1

.

2

.

3

.

1

0

off

x Ir

2

2.5

3

4

5

6
8

10

Isd

1.5

Micrologic 2.0

.98

instantaneous

long time

alarm

.5

1

2

4

8

12

16
20

tr

(s)

at 6 Ir

24

.4

.5

.6

.7

.8

.9

.95

1

Ir

x In

x Ir

2

2.5

3

4

5

6
8

10

1.5

setting

Isd

9

10

13

9

10

7

15

5

16

7

15

5

16

11

12

14

instantaneous

background image

Micrologic 2.0, 5.0

Schneider Electric

4

Discovering your
control unit

Protection settings

Depending on the type of installation, it is possible to set the tripping curve of your
control unit using the parameters presented below.

Thermal memory
The thermal memory continuously accounts for the amount of heat in the cables,
both before and after tripping, whatever the value of the current (presence of an
overload or not). The thermal memory optimises the long-time protection function
of the circuit breaker by taking into account the temperature rise in the cables.
The thermal memory assumes a cable cooling time of approximately 15 minutes.

Long-time current setting Ir and standard tripping delay tr

E51358A

E51360A

Overview of functions
Current protection

Micrologic 2.0

1. current setting Ir
(long time)
2. tripping delay tr
(long time) for 6 x Ir
3. pick-up Isd
(instantaneous)

1. current setting Ir (long time)
2. tripping delay tr (long time) for 6 x Ir
3. pick-up Isd (short time)
4. tripping delay tsd (short time)
5. pick-up Ii (instantaneous)

Micrologic 5.0

E51359A

Micrologic control unit

2.0 and 5.0

current setting

Ir = In x …(*)

0.4

0.5

0.6

0.7

0.8

0.9

0.95

0.98

1

tripping between 1.05 and 1.20 x Ir

other ranges or disable by changing rating plug

time delay (s)

tr at 1.5 x Ir

12.5

25

50

100

200

300

400

500

600

accuracy 0 to -20%

tr at 6 x Ir

0.5

1

2

4

8

12

16

20

24

tr at 7.2 x Ir

0.34

0.69

1.38

2.7

5.5

8.3

11

13.8

16.6

* In: circuit breaker rating

Setting accuracy of the Ir setting may be enhanced by using a different long-time
rating plug.
See the technical appendix "Changing the long-time rating plug".

E51361A

This LED signals that the long-time current setting Ir
has been overrun.

0

Ir

Isd

I

t

1

2

3

1

2

3

4

5

0

Ir

Isd

I

t

Ii

I

2

t off

I

2

t on

x Ir

2

2.5

3

4

5

6

8

10

1.5

setting

Isd

instantaneous

long time

alarm

tr

(s)

.4

.5

.6

.7

.8

.9

.95
.98

1

Ir

x In

.5

1

2

4

8

12

16
20

at 6 Ir

24

.4

.5

.6

.7

.8

.9

.95
.98

1

delay

short time

I i

tsd

(s)

on

I

2

t

.

2

.

3

.

4

.

4

.

1

.

2

.

3

.

1

0

off

long time

alarm

Ir

x In

.5

1

2

4

8

12

16
20

tr

(s)

at 6 Ir

24

setting

x Ir

2

2.5

3 4 5

6

8

10

Isd

1.5

x In

3

4

6 8 10

12

15

off

2

instantaneous

Long-time protection

The long-time protection function protects cables (phases and neutral) against
overloads. This function is based on true rms measurements.

Overload LED

background image

Micrologic 2.0, 5.0

Schneider Electric

5

Short-time protection

c

the short-time protection function protects the distribution system against

impedant short-circuits.

c

the short-time tripping delay can be used to ensure discrimination with

a downstream circuit breaker.

c

this function carries out true rms measurements.

c

the I

2

t ON and I

2

t OFF options enhance discrimination with downstream

protection devices.

c

use of I

2

t curves with short-time protection:

v

I

2

t OFF selected: the protection function implements a constant time curve;

v

I

2

t ON selected: the protection function implements an I

2

t inverse-time curve up to

10 Ir. Above 10 Ir, the time curve is constant.

Short-time pick-up Isd and tripping delay tsd

Micrologic control unit

2.0 and 5.0

pick-up accuracy

±

10%

Isd = Ir x …

1.5

2

2.5

3

4

5

6

8

10

time delay (ms) at 10 x Ir

settings

I

2

t OFF

0

0.1

0.2

0.3

0.4

I

2

t ON or I

2

t OFF

I

2

t ON

0.1

0.2

0.3

0.4

tsd (max resettable time)

20

80

140

230

350

tsd (max break time)

80

140

200

320

500

Instantaneous protection

c

the instantaneous-protection function protects the distribution system

against solid short-circuits. Contrary to the short-time protection function,
the tripping delay for instantaneous protection is not adjustable.
The tripping order is sent to the circuit breaker as soon as current exceeds
the set value, with a fixed time delay of 20 milliseconds.

c

this function carries out true rms measurements.

Instantaneous pick-up Isd

Micrologic control unit

2.0

pick-up accuracy

±

10 %

Isd = Ir x …

1.5

2

2.5

3

4

5

6

8

10

Instantaneous pick-up Ii

Micrologic control unit

5.0

pick-up accuracy

±

10 %

li = In x … (*)

2

3

4

6

8

10

12

15

OFF

* In: circuit-breaker rating

Protection of the fourth pole on four-pole circuit breakers

Protection of the neutral conductor depends on the distribution system.
There are three possibilities:

Type of neutral

Description

Neutral unprotected

The distribution system does not require protection
of the neutral conductor.

Neutral protection

The cross-sectional area of the neutral conductor is half

at 0.5 In

that of the phase conductors.

c

the long-time current setting Ir for the neutral is equal

to half the setting value

c

the short-time pick-up Isd for the neutral is equal

to half the setting value

c

the instantaneous pick-up Isd (Micrologic 2.0)

for the neutral is equal to half the setting value

c

the instantaneous pick-up Ii (Micrologic 5.0)

for the neutral is equal to the setting value

Neutral protection at In

The cross-sectional area of the neutral conductor is equal
to that of the phase conductors.

c

the long-time current setting Ir for the neutral is equal

to the setting value

c

the short-time pick-up Isd for the neutral is equal

to the setting value

c

the instantaneous pick-ups Isd and Ii for the neutral

are equal to the setting value

background image

Micrologic 2.0, 5.0

Schneider Electric

6

Selecting the type of neutral protection

On four-pole circuit breakers, it is possible to select the type of neutral protection
using the three-position switch:

Setting
your control unit

Setting procedure

E51383A

Setting procedure

Using the adjustment dials

E51363A

E51364A

E51365A

Open the protective
cover.

Select the desired
setting.

Close the protective
cover and, if necessary,
install a lead seal to
protect the settings.

Micr

olog

ic 2.0

1

Micr

olog

ic 2.0

2

Micr

olog

ic 2.0

3

4P 3D

3D+N/2

4P 4D

c

neutral unprotected

(4P 3D);

c

neutral protection

at 0.5 In (3D + N/2);

c

neutral protection

at In (4P 4D).

background image

Micrologic 2.0, 5.0

Schneider Electric

7

E51366A

Setting the Micrologic 2.0
control unit

The rating of the circuit breaker in this example is 2000 A.

Set the threshold values

E60365A

E51368A

Set the tripping delay

E60366A

E51370A

In = 2000 A

Ir = 0.7 x In = 1400 A

Isd = 3 x Ir = 4200 A

alarm

x Ir

2

2.5

3 4 5

6

8

10

1.5

setting

Isd

instantaneous

.4

.5

.6

.7

.8

.9

.95
.98

1

long time

Ir

x In

0

I

t

Ir

Isd

long time

alarm

.5

1

2

4

8

12

16
20

tr

(s)

at 6 Ir

24

tr = 1 second

0

I

t

tr

1

In =

200

0 A

In = 2000 A

See pages 4 and 5 for information
on the available settings.

background image

Micrologic 2.0, 5.0

Schneider Electric

8

Setting
your control unit

Setting the Micrologic 5.0
control unit

Set the threshold values

E60367A

E51372A

E60368A

E51375A

E51373A

Set the tripping delay

E51376A

In = 2000 A

Ir = 0.7 x In = 1400 A

Ii = 3 x In = 6000 A

Isd = 2 x Ir = 2800 A

.4

.5

.6

.7

.8

.9

.95

.98

1

setting

short time

I i

x Ir

2

2.5

3

4 5

6

8

10

Isd

1.5

long time

alarm

Ir

x In

x In

3

4

6

8 10

12

15

off

2

instantaneous

Ir

Isd

Ii

0

I

t

Ir

Isd

Ii

0

I

t

tr = 1 second

tsd = 0.2 seconds

short time

long time

alarm

.5

1

2

4

8 12

16

20

tr

(s)

at 6 Ir

24

delay

tsd

(s)

on

I

2

t

.

2

.

3

.

4

.

4

.

1

.

2

.

3

.

1

0

I

2

t on

I

2

t off

tr

tsd

0

I

t

tr

tsd

0

I

t

See pages 4 and 5 for information
on the available settings.

I

2

t ON curve

I

2

t OFF curve

I

2

t

ON curve

I

2

t

OFF curve

background image

Micrologic 2.0, 5.0

Schneider Electric

9

See the user manual
for the portable test kit.

To test the control unit, connect the portable test kit via the test connector

E51363A

E51377A

Testing the control unit

Micr

olog

ic 2.0

1

Micr

olog

ic 2.0

2

Micr

olog

ic 2.0

2

background image

Micrologic 2.0, 5.0

Schneider Electric

10

Technical appendix

Tripping curves

Long-time and instantaneous protection - Micrologic 2.0

E60369A

.5 .7

1

2

3 4 5

7 10

20 30

50 70 100

200 300

I / Ir

10 000

5 000

2 000

1 000

500

200

100

50

20

10

5

2

1

.5

.2

.1

.05

.02

.01

.005

.002
.001

t(s)

tr = 0.5…24 s

Isd = 1.5…10 x Ir

Ir = 0.4…1 x In

Long-time, short-time and instantaneous
protection - Micrologic 5.0

E60370A

0

0.4

0.3

0.2
0.1

t(s)

.5 .7

1

2

3 4 5

7 10

20

3

5

7 10

20 30

10 000

5 000

2 000

1 000

500

200

100

50

20

10

5

2

1

.5

.2

.1

.05

.02

.01

.005

.002
.001

x In

tr = 0.5…24 s

Isd = 1.5…10 x Ir

Ir = 0.4…1 x In

Ii = 2…15 x In . OFF (1)

I

2

t OFF

x Ir

0.4

0.3

0.2
0. 1

I

2

t ON

0

background image

Micrologic 2.0, 5.0

Schneider Electric

11

Caution.
Following any modifications
to the long-time rating plug,
all control-unit protection parameters
must be checked.

Changing the long-time
rating plug

Select the long-time rating plug

A number of setting ranges for the long-time current setting are available on
Micrologic 2.0 and 5.0 control units by changing the long-time rating plug.
The available rating plugs are listed below:

Part number

Setting range for the Ir value

33542

standard

0.4 to 1 x Ir

33543

low setting

0.4 to 0.8 x Ir

33544

high setting

0.8 to 1 x Ir

33545

without long-time protection

Change the long-time rating plug

Proceed in the following manner.

2. Open the protective
cover of the control unit.

3. Completely remove the long-
time rating plug screw.

E51483A

E51484A

4. Snap out the rating plug.

5. Clip in the new rating plug.

E51485A

E51486A

6. Refit the screw for the
long-time rating plug.

7. Check and/or modify the
control-unit settings

.4

.5

.6

.7

.8 .9

.95
.98

1

long

time

alarm

Ir

x In

.5

1

2

4

8 12

16
20

tr

(s)

@ 6

Ir

24

.4

.5

.6

.7

.8 .9

.95
.98

1

long

time

alarm

Ir

x In

.5

1

2

4

8 12

16
20

tr

(s)

@ 6

Ir

24

1. Open the circuit breaker.

If no long-time rating plug is installed,
the control unit continues to operate
under the following downgraded
conditions:

c

the long-time current setting Ir is 0.4,

whatever the position of the
adjustment dial;

c

the long-time tripping delay tr

corresponds to the value indicated
by the adjustment dial.

background image

Micrologic 2.0, 5.0

Schneider Electric

12

Thermal memory

Thermal memory

The thermal memory is a means to simulate temperature rise and cooling caused
by changes in the flow of current in the conductors.

These changes may be caused by:

c

repetitive motor starting;

c

loads fluctuating near the protection settings;

c

repeated circuit-breaker closing on a fault.

Control units without a thermal memory (contrary to bimetal strip thermal
protection) do not react to the above types of overloads because they do not
last long enough to cause tripping.
However, each overload produces a temperature rise and the cumulative effect
can lead to dangerous overheating.

Control units with a thermal memory record the temperature rise caused
by each overload. Even very short overloads produce a temperature rise
that is stored in the memory.
This information stored in the thermal memory reduces the tripping time.

Micrologic control units and thermal memory

All Micrologic control units are equipped as standard with a thermal memory.

c

for all protection functions, prior to tripping, the temperature-rise and cooling time

constants are equal and depend on the tripping delay in question:

v

if the tripping delay is short, the time constant is low;

v

if the tripping delay is long, the time constant is high.

c

for long-time protection, following tripping, the cooling curve is simulated

by the control unit. Closing of the circuit breaker prior to the end of the time
constant (approximately 15 minutes) reduces the tripping time indicated
in the tripping curves.

Technical appendix

background image

Schneider Electric Industries SA

Designed by: HeadLines
Printed by:

As standards, specifications and designs develop from time, always ask for confirmation of the
information given in this publication.

5, rue Nadar
92506 Rueil-Malmaison Cedex
France
Tel: +33 (0)1 41 29 82 00
Fax:+33 (0)1 47 51 80 20

http://www.schneiderelectric.com

04443722AA-A

11-99

This document has been printed on ecological paper.


Document Outline


Wyszukiwarka

Podobne podstrony:
05 MICROLOGIC 5 0P 7 0P MANUAL
05 MICROLOGIC 2 0A 7 0A MANUAL
05 INSTRUCTION MANUAL COUPLING M8090901A
JobEditorNX Manual EN 05
podrecznik 2 18 03 05
regul praw stan wyjątk 05
05 Badanie diagnostyczneid 5649 ppt
Podstawy zarządzania wykład rozdział 05
05 Odwzorowanie podstawowych obiektów rysunkowych
05 Instrukcje warunkoweid 5533 ppt
05 K5Z7
05 GEOLOGIA jezior iatr morza
05 IG 4id 5703 ppt
05 xml domid 5979 ppt

więcej podobnych podstron