Load protection
Motor starter protection
P25M
DB1
16619
DBxxxxxx
DBxxxxxx
DBxxxxxx
Country approval pictograms
(1)
IEC 60947-2 and IEC 60947-4-1 (in combination)
They protect single-phase or three-phase motors with manual local control.
This protection includes:
isolation
manual or remote control
short-circuit protection (magnetic)
overload protection (thermal
Breaking capacity to IEC 60947-2
Voltage (V)
230...240
400...415
440
500
690
Rating (A) Icu
Ics
Icu
Ics
Icu
Ics
Icu
Ics
Icu
Ics
kA
%
kA
%
kA
%
kA
%
kA
%
0.16 to 1.6
Unlimited
2.5
3
75
4
3
75
6.3
50
100
50
100
3
75
10
15
100
10
100
3
75
14
15
50
8
50
6
75
3
75
18
15
50
8
50
6
75
3
75
23
50
100
15
40
6
50
4
75
3
75
25
50
100
15
40
6
50
4
75
3
75
The limiting unit increases the breaking capacity up to 100 kA at 415 V.
b
b
b
b
Catalogue numbers
Motor characteristics
P25M circuit breaker
Type
Standardised power (kW) of three-phase 50/60 Hz motors in category AC3
Rating In
(A)
Setting
Cat. no.
Width in
9 mm
modules
Voltage (V AC)
230
400
415
440
500
690
3P
1
2
3
4
5
6
-
-
-
-
-
-
0.16
0.1-0.16
21100
5
-
-
-
-
-
-
0.25
0.16-0.25
21101
5
-
-
-
-
-
-
0.40
0.25-0.40
21102
5
-
-
-
-
-
0.37
0.63
0.40-0.63
21103
5
-
-
-
0.37
0.37
0.55
1.0
0.63-1
21104
5
-
0.37
-
0.55
0.75
1.1
1.6
1-1.6
21105
5
0.37
0.75
1.1
1.1
1.1
1.5
2.5
1.6-2.5
21106
5
0.75
1.5
1.5
1.5
2.2
3
4.0
2.5-4
21107
5
1.1
2.2
2.2
3
3.7
4
6.3
4-6.3
21108
5
2.2
4
4
4
5;5
7.5
10
6-10
21109
5
3
5.5
5.5
7.5
9
11
14
9-14
21110
5
4
7.5
9
9
10
15
18
13-18
21111
5
5.5
9
11
11
11
18.5
23
17-23
21112
5
5.5
11
11
11
15
22
25
20-25
21113
5
Limiting unit
Type
Rating In
(A)
Cat. no.
Width in 9 mm
modules
3P
63
21115
5
045666_SE
E12648C
PG131075_SE
CM901026E.indd
version: 1.0
3
Load protection
Motor starter protection
P25M
Technical data
Electrical characteristics
Operating voltage (Ue)
690 V AC
Insulation voltage (Ui)
690 V
Rated impulse withstand voltage (Uimp)
6 kV
Endurance (O-C)
Electrical AC3
100,000 cycles
Thermal trip unit
Sensitive to missing phase
Settings
Factory < settings range
Simultaneously on the front face
On current drawn in nominal operation
Ratings (In)
0.16 to 25 A adjustable
Temperature
compensation
-20°C to +40 °C in an enclosure
Magnetic trip unit
12 x the In rating (±20 %)
Other characteristics
Padlocking device on the front face
Tropicalisation
Treatment 2 (relative humidity 95 % at 55 °C)
Operating temperature
-20 ...+60 °C
Storage temperature
-40 ...+80 °C
Weight (g)
P25M
260
Limiting unit
130
Connection
P25M
Limiting unit
DB125904
PZ2
5.5 mm
Tightening
torque
Terminal clamps
With insulated
connector
Tunnel terminals
Rigid Cu
Flexible Cu
Flexible Cu
Flexible or rigid Cu
1.7 M.m.
2 x 1 ... 6 mm
2
2 x 1.5 ... 6 mm
2
1 x 25 mm
2
or 2 x 10 mm
2
DB1
18767
Mounted on 35 mm DIN rail.
DB126273
0...90°
0...30°
DB122932
Degrees of protection.
DB126274
Dimensions (mm)
010-0100
DB126275
013-0100
Circuit breaker
Limiting unit only
Insulating enclosure
IP20
IP40
CM901026E.indd
version: 1.0
4
Load protection
Motor starter protection
P25M
Electrical auxiliaries
The electrical auxiliaries allow remote tripping or position or fault indication of the
PM25 circuit breakers.
Connection
Cables
Rigid
min.
Flexible
max.
Flexible
with ferrule
2 x 1 mm
2
2 x 2.5 mm
2
2 x 1.5 mm
2
Catalogue numbers
Trip units
Type
Control voltage
(V AC)
Width in 9 mm
modules
Cat. no.
1 MX shunt release
Controls circuit breaker tripping and opening
C1 C2
u>
220...240
2
21127
380...415
2
21128
2 MN undervoltage release
Controls circuit breaker tripping and opening
when its supply voltage decreases (between 70 and 35 %)
D1 D2
u<
220...240
2
21129
380...415
2
21130
Auxiliary contacts
Type
Breaking capacity
Width in 9 mm
modules
Cat. no.
3 Contacts de position
O + F
O to indicate the "closed contact" position, idle
F to indicate the "open contact" position, idle
31
32
43
44
3 A at 240 V AC
1
21117
2 A at 415 V AC
F + F
O to indicate the "closed contact" position, idle
F to indicate the "open contact" position, idle
43
44
33
34
3 A at 240 V AC
1
21116
2 A at 415 V AC
4 Position and fault tripping indication contacts
F + SD.F
SD.F to indicate the closed contact fault
53
54
97
98
SD.F 0,3 A at 240 V AC
1
21118
F
3 A at 240 V AC
2 A at 415 V AC
O + SD.F
SD.F to indicate the closed contact fault
51
52
97
98
SD.F 0,3 A at 240 V AC
1
21119
O
3 A at 240 V AC
2 A at 415 V AC
F + SD.O
SD.O to indicate the open contact fault
95
96
53
54
SD.O 0,3 A at 240 V AC
1
21120
F
3 A at 240 V AC
2 A at 415 V AC
O + SD.O
SD.O to indicate the closed contact fault
95
96
51
52
SD.O 0,3 A at 240 V AC
1
21121
O
3 A at 240 V AC
2 A at 415 V AC
1
3
4
2
or
MN
MX
SD
OF
P25M
18 mm max.
CM901026E.indd
version: 1.0
5
Load protection
Motor starter protection
P25M
Accessories
4
6
5
3
1
Accessories make it easier to integrate the circuit breakers and extend their use.
Catalogue numbers
Type
Cat. no.
1 Comb busbars
54 mm
63 A maxi
Test
M E R
L IN
G E R
IN
m u
l t i 9
P 2 5
M
6 6 0
V
AC3-
IEC29
2-1
0 . OFF
Test
M E R
L IN
G E R
IN
m u
l t i 9
P 2 5
M
6 6 0
V
AC3-
IEC29
2-1
0 . OFF
Test
M E R
L IN
G E R
IN
m u
l t i 9
P 2 5
M
6 6 0
V
AC3-
IEC29
2-1
0 . OFF
M E
R L I
N G
E R
I N
M E
R L
I N G
E R
I N
2 P25M feeders
21145
4 P25M feeders
21146
Protection end-piece
21448
2 Downstream terminal block
Test
M E R
L IN
G E R
IN
m u
l t i 9
P 2 5
M
6 6 0
V
AC3-
IEC29
2-1
0 . OFF
Test
M E R
L IN
G E R
IN
m u
l t i 9
P 2 5
M
6 6 0
V
AC3-
IEC29
2-1
0 . OFF
Test
M E R
L IN
G E R
IN
m u
l t i 9
P 2 5
M
6 6 0
V
AC3-
IEC29
2-1
0 . OFF
M E
R L I
N G
E R
I N
M E
R L
I N G
E R
I N
L1
1
3
I
>>
L2
I
>>
5
L3
L1
1
3 L2
L3
I
>>
5
I>
>
I>
>
I>
>
Ii660V
- 50/60
Hz
25 mm²
21144
3 Insulated connector
25 mm²
Test
M E R
L IN
G E R
IN
m u
l t i 9
P 2 5
M
6 6 0
V
AC3-
IEC29
2-1
0 . OFF
Test
M E R
L IN
G E R
IN
m u
l t i 9
P 2 5
M
6 6 0
V
AC3-
IEC29
2-1
0 . OFF
Test
M E R
L IN
G E R
IN
m u
l t i 9
P 2 5
M
6 6 0
V
AC3-
IEC29
2-1
0 . OFF
Test
M E R
L IN
G E R
IN
m u
l t i 9
P 2 5
M
6 6 0
V
AC3-
IEC29
2-1
0 . OFF
1L1
3L2
5L3
21147
4 Clip-on terminal markers
see module CM907003E
5 Insulating enclosure
Individual installation of a P25M circuit breaker with an auxiliary contact block and trip unit.
Double insulation i and sealed to IP55.
L = 93, H = 147, P = 100 (mm)
21133
6 Neon indicator light
230-240 V AC
green
21140
red
21142
400-415 V AC
green
21141
red
21143
2
CM901026E.indd
version: 1.0
6
Load protection
Motor starter protection
P25M
Practical advice
Choice of motor supply cable cross-section
The motor starting current and permissible voltage drop must be taken into
account when choosing the cross-section.
The cable must accept a current at least equal, when used continuously, to the
sum of In + Id/3 where:
In: rated current,
Id: starting current (4 to 8 In), depending on the motors.
Voltage drop
The voltage drop permitted between the source and the motor concerned is 5% for
public distribution networks and 8 % for subscriber or transformer substations.
If the torque of the machine to be driven is low at startup, simply check the voltage
drop for the rated current of the motor.
If the startup torque is high (grain crushers, goods lift, etc.), check the voltage drop
for the starting current.
Protection of the motor supply line
All circuits and motors must be protected against overloads and short-circuits.
Connecting the circuit breaker for use with a single-
phase motor
Two circuit breaker poles must be connected in series.
1
2
3
4
5
6
b
b
v
v
b
b
b
b
b