FLOW M3


Calculate power from difference temperature and water flow in m3/h

File: flow_m3.doc

Last edition: 2003-03-11

Author: Mikael Krantz

History: 96-02-14/MK First released version.

96-09-30/MK Updated to Menta 1.20

97-05-21/MK Updated to Menta 3.0

2003-03-11/MK Updated to Menta 4.0

Description

Calculates power in kW from a difference temperature and water flow given in m3/h.

Formula: (TSupply - TReturn) * Water flow * 1.0 * 4.18 / 3.6

Heating coefficient for water 20 - 100 °C = 4.18 kJ/kg*K

Scale factor from m3/h to l/s = 1 / 3.6

Density for water = 1.0 kg/l

Inputs

(Real) Supply temperature (°C)

(Real) Return temperature (°C)

(Real) Water flow (m3/h)

Outputs

(Real) Actual power (kW)

Parameters

Public signals

(Real) Power