Badanie układu V.
- schemat układu
tabela pomiarów
zasilanie 30 kV
Lp |
UR |
US |
UT |
URS |
UST |
UTR |
||||||
- |
1 |
2 |
1 |
2 |
1 |
2 |
1 |
2 |
1 |
2 |
1 |
2 |
|
V |
V |
V |
V |
V |
V |
V |
V |
V |
V |
V |
V |
1 |
139 |
10 |
135 |
32 |
135 |
32 |
243 |
61 |
238 |
57 |
238 |
59 |
2 |
0 |
0 |
119 |
19 |
115 |
19 |
120 |
29 |
236 |
57 |
114 |
25 |
3 |
135 |
49 |
135 |
49 |
134 |
41 |
1 |
0 |
237 |
57 |
237 |
57 |
4 |
138 |
2 |
135 |
25 |
134 |
32 |
242 |
0 |
238 |
57 |
238 |
9 |
5 |
138 |
72 |
134 |
27 |
134 |
32 |
241 |
58 |
237 |
56 |
238 |
108 |
6 |
0 |
85 |
256 |
130 |
240 |
126 |
261 |
56 |
238 |
57 |
240 |
60 |
Zasilanie 110kV
Lp |
UR |
US |
UT |
URS |
UST |
UTR |
||||||
- |
1 |
2 |
1 |
2 |
1 |
2 |
1 |
2 |
1 |
2 |
1 |
2 |
|
V |
V |
V |
V |
V |
V |
V |
V |
V |
V |
V |
V |
1 |
134 |
9 |
131 |
31 |
130 |
30 |
237 |
57 |
231 |
56 |
232 |
60 |
2 |
4 |
21 |
130 |
40 |
131 |
40 |
139 |
34 |
231 |
56 |
132 |
31 |
3 |
131 |
48 |
130 |
47 |
131 |
41 |
0 |
0 |
231 |
56 |
231 |
56 |
4 |
134 |
2 |
130 |
26 |
131 |
31 |
232 |
0 |
231 |
95 |
236 |
9 |
5 |
134 |
71 |
130 |
27 |
131 |
30 |
236 |
57 |
231 |
56 |
232 |
99 |
6 |
0 |
23 |
129 |
40 |
135 |
43 |
133 |
32 |
231 |
56 |
136 |
32 |
|
|
2. Badanie układu gwiazdowego.
- schemat układu
tabela pomiarów
zasilanie 30kV
Lp |
UR |
US |
UT |
URS |
UST |
UTR |
||||||
- |
1 |
2 |
1 |
2 |
1 |
2 |
1 |
2 |
1 |
2 |
1 |
2 |
|
V |
V |
V |
V |
V |
V |
V |
V |
V |
V |
V |
V |
1 |
138 |
34 |
136 |
32 |
134 |
32 |
242 |
61 |
238 |
57 |
238 |
58 |
2 |
0 |
0 |
118 |
28 |
115 |
27 |
115 |
28 |
236 |
58 |
115 |
27 |
3 |
0 |
0 |
135 |
32 |
135 |
32 |
139 |
34 |
238 |
58 |
135 |
32 |
4 |
138 |
0 |
135 |
32 |
133 |
32 |
244 |
4 |
238 |
58 |
237 |
8 |
5 |
138 |
32 |
136 |
32 |
134 |
32 |
240 |
33 |
238 |
58 |
238 |
31 |
6 |
0 |
0 |
255 |
61 |
240 |
59 |
260 |
56 |
239 |
57 |
239 |
67 |
Zasilanie 110kV
Lp |
UR |
US |
UT |
URS |
UST |
UTR |
||||||
- |
1 |
2 |
1 |
2 |
1 |
2 |
1 |
2 |
1 |
2 |
1 |
2 |
|
V |
V |
V |
V |
V |
V |
V |
V |
V |
V |
V |
V |
1 |
133 |
33 |
130 |
30 |
130 |
30 |
235 |
60 |
231 |
56 |
230 |
57 |
2 |
0 |
0 |
130 |
30 |
130 |
31 |
130 |
30 |
230 |
56 |
130 |
30 |
3 |
0 |
0 |
130 |
30 |
130 |
30 |
133 |
32 |
231 |
56 |
131 |
30 |
4 |
133 |
0 |
130 |
30 |
130 |
30 |
235 |
0 |
231 |
56 |
230 |
8 |
5 |
131 |
31 |
130 |
30 |
130 |
30 |
230 |
31 |
230 |
56 |
230 |
30 |
6 |
0 |
0 |
128 |
30 |
135 |
32 |
133 |
33 |
231 |
56 |
135 |
32 |
Układ gwiazdowy z uzwojeniem wtórnym połączonym w otwarty trójkąt.
schemat układu
- tabela pomiarów
zasilanie 30kV
Lp |
UR |
US |
UT |
URS |
UST |
UTR |
||||||
- |
1 |
2 |
1 |
2 |
1 |
2 |
1 |
2 |
1 |
2 |
1 |
2 |
|
V |
V |
V |
V |
V |
V |
V |
V |
V |
V |
V |
V |
1 |
137 |
7 |
137 |
6 |
135 |
5 |
240 |
4 |
238 |
5 |
238 |
6 |
2 |
0 |
6 |
115 |
5 |
116 |
2 |
115 |
5 |
235 |
5 |
116 |
6 |
3 |
140 |
7 |
134 |
6 |
138 |
4 |
246 |
4 |
237 |
5 |
244 |
6 |
4 |
138 |
3 |
135 |
5 |
136 |
3 |
240 |
1 |
237 |
4 |
237 |
3 |
5 |
1 |
34 |
250 |
32 |
239 |
27 |
255 |
5 |
237 |
5 |
238 |
6 |
6 |
0 |
18 |
176 |
16 |
139 |
13 |
182 |
14 |
237 |
5 |
138 |
6 |
Zasilanie 110kV
Lp |
UR |
US |
UT |
URS |
UST |
UTR |
||||||
- |
1 |
2 |
1 |
2 |
1 |
2 |
1 |
2 |
1 |
2 |
1 |
2 |
|
V |
V |
V |
V |
V |
V |
V |
V |
V |
V |
V |
V |
1 |
134 |
7 |
130 |
6 |
131 |
4 |
235 |
6 |
230 |
5 |
230 |
4 |
2 |
141 |
6 |
136 |
6 |
128 |
3 |
264 |
4 |
231 |
5 |
234 |
6 |
3 |
131 |
7 |
129 |
6 |
130 |
4 |
236 |
6 |
232 |
5 |
223 |
4 |
4 |
134 |
3 |
130 |
5 |
131 |
3 |
230 |
1 |
226 |
4 |
234 |
3 |
5 |
0 |
11 |
130 |
10 |
136 |
7 |
133 |
5 |
230 |
5 |
135 |
6 |
6 |
0 |
9 |
129 |
8 |
121 |
5 |
132 |
5 |
233 |
6 |
122 |
7 |
Przeprowadzone pomiary:
Praca normalna.
zanik napięcia w fazie R.
Przepalenie wkładki bezpiecznikowej po stronie pierwotnej w fazie R.
Przepalenie wkładki bezpiecznikowej po stronie wtórnej w fazie R.
Błędne połączenie przekładnika.
Zwarcie doziemne fazy R.
4. Wykresy
- do układu V
- do układu gwiazdowego
strona pierwotna strona wtórna
5.Wnioski.
Układ V tworzy się z dwóch jednofazowych przekładników, pozwala na odwzorowanie trójkąta napięć międzyprzewodowych. Układ może być realizowany w sieciach z nie uziemionym punktem zerowym transformatora zasilającego. Stosuje się w urządzeniach na napięcie do 30 kV do zasilania watomierzy i liczników trójfazowych.
Układy gwiazdowe w zależności od sposobu pracy sieci, mogą być z punktem zerowym uzwojeń pierwotnych przekładników napięciowych, uziemionym lub izolowanym. W sieciach na 110 kV i wyższych stosowane są układy z punktem gwiazdowym uzwojeń pierwotnych uziemionych.
Układ gwiazdowy przekładników z uzwojeniem wtórnym połączonym w otwarty trójkąt stosujemy do pomiaru składowej zerowej napięcia przy doziemieniu. Układ otwartego trójkąta jest często stosowany jako dodatkowe uzwojenie stront wtórnej.