ZSP 41(1)

background image

APLISENS Sp. z o.o., ul. Morelowa 7

, tel. +4822 8140 777

fax +4822 8140 778, www.aplisens.com.pl, e-mail: aplisens@

.com.pl

, 03-192 Warszawa

aplisens

Version III/2002

ZSP-41

power supply/separator/signal converter

ü Full galvanic separation of circuits

(IN-OUT, IN-SUP, OUT-SUP)

ü Ability to select input and output signals
ü Ability to use input line to power a two-wire

transmitter

ü Casing can be fitted on a standard adapter

(TS35, TS32)

Applications and functions

The ZSP-41 provides galvanic separation of an input signal

(4 ÷ 20 mA, 0 ÷ 20 mA, 0 ÷ 10 V) and converts it, through a

separation system, into any standard output signal. An additional

input line may be connected to any two-wire transmitter to pro-

vide it with a 19 ÷ 24 V power supply.
The device is typically used to provide galvanic separation be-

tween measurement circuits installed on an object, and the main

section. This enables the effect of object-related interference in

the monitoring, control and recording systems of automatic de-

vices to be largely eliminated. The ability to alter the input and

output signals makes it easier to configure automatic systems

using apparatus based on differing standards.

Configuration, calibration

The user can use switches to configure input and output settings

for the following signals:

Input switches

Input

1

2 3

4

5

6

7

8

4...20 mA

– + – + + + + +

0...20 mA

– + – + +

– +

0...10 V

– + – +

Two-wire

transmitter

+

– +

– + + + +

Output switches

Output

1

2

3

4

4...20 mA

+

+

+ ON

0...20 mA

– OFF

0...10 V

+

+

Access to the switches is via openings in the side wall of the

casing.
Separators can be produced to support other input and output

signals.
Calibration is carried out using potentiometers. These are ac-

cessed through openings in the front plate of the separator.

View of front plate

Wiring diagram

(+)

(-)

3

2

1

ZSP-41

4

(+)

6

(-)

"0"

"S"

we

wy

5

(24V)

(GND)

U

IN

1

5

2

Ro

I

IN

+Ucc

+

_

+

_

6

3

4

+24V GND

22.5

79

85.5

background image

Version III/2002

APLISENS Sp. z o.o., ul. Morelowa 7

, tel. +4822 8140 777

fax +4822 8140 778, www.aplisens.com.pl, e-mail: aplisens@

.com.pl

, 03-192 Warszawa

aplisens

Technical parameters

Input parameters

Input signal (selected by switch)

0...20 mA, 4...20 mA

4...20 mA + converter power supply

0...10 V

Special versions: other input signals
Input resistance

50 k

(voltage input)

20

(current input)

Output parameters

Output signal (selected by switch)

0...20 mA, 4...20 mA

0...10 V

Special versions: other output signals
Load resistance

0...500

(current output)

1 k

(voltage output)

Galvanic separation

opto-electronic

Strength test parameters

1.5 kV AC, 50 Hz, 1 min

Dynamic characteristics

Transmission band

5 Hz (3 dB)

Conversion errors

Accuracy

±0.16%

Typically, the converter is set for the range 4...20 mA / 4...20 mA. Setting of a different range will lower the class of the converter to

0.25% (tuning is possible using trimmers accessible from the front plate).

Effect of temperature fluctuations

±0.1% / 10°C

Effect of load resistance fluctuations

±0.1% / 100

(for current output)

±0.1% (from 1 to 10 k

for voltage output)

Effect of serial interference 50 Hz

±0.1%

Effect of parallel interference 220 V

±0.1%

Effect of supply voltage fluctuations

±0.1%

Power supply

Supply voltage

24 V ± 20%

Supply current

100 mA

Conditions of normal use

Ambient temperature

5...60°C

Relative humidity

30...80%

Casing

Type

UEGM 22.5 (PHOENIX)

Ingress protection rating

IP 20

Weight

0.1 kg

Input signal

How to order

Output signal

Standard version:

Special version:

ZSP-41

ZSP-41 /___/___


Wyszukiwarka

Podobne podstrony:
ZSP 41
DTR ZSP 41 01
ZSP 41(1)
ZSP 41
41 etapy rozwoju dziecka
noj 41
(41) Leki zwiększające krzepliwość
analiza kosztow produkcji (41 str)
41 SWOT
41 Sterowanie
zwolnienie ZSP 13
Logistyka i Zarządzanie Łańcuchem dostaw Wykłady str 41
page 40 41
2002 04 41
ED 1999 1 41
1588 zyworodka endlera 41 l4id 16546
2005 03 41
41. Monitorowanie w Oddziale Intensywnej Terapii, Anestezjologia
Małżeństwo o jakim marzymy 29-41, DOKUMENTY NP KOŚCIOŁA ŚW I NIE TYLKO

więcej podobnych podstron