HEX control
File: HEX.doc
Last edition: 4 of March 2003
Author: Mikael Krantz
History: 96-02-13/MK First released version.
96-10-03/MK Updated to Menta 1.20
97-09-02/MK Updated to Menta 3.0
98-03-09/MK Unit corrected.
98-12-30/MK New filename
2003-03-04/MK Updated to Menta 4.0
Description
Heat exchanger (HEX) are controlled from the measured value and setpoint value for the supply air. By the "NormalControl" flag, it is possible to start and stop the controlling. By the "HEXMax" flag, it is possible to maximum the controlling signal. If both "NormalControl" flag and "HEXMax" are false the controller signal goes to minimum.
Inputs
(Real) SP supply temperature, °C.
(Real) Supply temperature, °C.
(Binary) Normal control
(Binary) HEX max
Outputs
(Real) HEX-control signal, %.
Parameters
(Real) HEXTravelTime 180 seconds
(Real) HEXITime 4 minutes
(Real) HEXPBand 25 °C
Public signals
(Real) HEXPBand
(Real) HEXITime
(Real) HEX