Cooling and HEX control in sequence
File: HEX Cool.doc
Last edition: 4 of March 2003
Author: Mikael Krantz
History: 96-02-13/MK First released version.
96-10-03/MK Updated to Menta 1.20
97-09-02/MK Updated to Menta 3.0
98-03-09/MK Unit corrected.
98-12-30/MK New filename
2003-03-04/MK Updated to Menta 4.0
Description
Cooling and HEX control in sequence, with separate P-band and I-times. If the flag for "Normal Control" is true, the main controller is activated, in other cases, the controller is set to closed valve and maximum HEX. The HEX can, however, be set to minimum be the "HEX min" flag. If the "Cooling allowed" flag is false, the cooling valve is forced to closed position. If the "HEX min" flag is true, the HEX is forced to min position, if the "HEX max" flag is true, the HEX is forced to max position.
Inputs
(Real) SP supply temperature, C
(Real) Supply temperature, C
(Binary) Normal control
(Binary) Cooling case flag
(Binary) HEX Min flag
(Binary) HEX max flag
Outputs
(Real) Cooling control signal 0 - 100%
(Real) HEX control signal 0 - 100%
Parameters
(Real) CoolingPBand 25 C
(Real) CoolingITime 4 minutes
(Real) HEXPBand 25 C
(Real) HEXITime 4 minutes
Public signals
(Real) Cooling
(Real) CoolingITime
(Real) CoolingPBand
(Real) HEX
(Real) HEXITime
(Real) HEXPBand