06 VIP300 MANUAL

background image

Protection
and control

VIP300

Technical manual

<< Back

background image

technical manual VIP300

2

contents

1. presentation of the VIP300............................................................... 3
2. use and settings ............................................................................... 4
3. choice of sensors and operating ranges .......................................... 9
4. connection scheme .......................................................................... 10
5. assembly .......................................................................................... 11
6. IDMT tripping curves ........................................................................ 13
7. technical characteristics ................................................................... 17
8. testing of the VIP300 and use of the VAP6 ...................................... 20

background image

technical manual VIP300

3

1. presentation of the VIP300

VIP300

Mitop

- simplified wiring scheme -

10Is

t>

I>>

t>>

- phase or earth fault curves -

1,2Is

I

t

self-powered protective relay

n

The VIP300 relay is designed for

use in distribution networks. It may be
used as MV/LV transformer
protection, protection at the incoming
point of industrial installations, and
also as branch feeder protection.

n

The VIP300 provides protection

against phase-to-phase faults and
earth faults. The choice of tripping
curves and the multiple settings allow
it to be used in a wide variety of
discrimination plans.
The VIP300 is a self-powered relay,
energized by the current sensors; it
does not require any auxiliary source.
It actuates a Mitop release.

phase protection

The phase protection has two
separately adjustable settings:

n

the low setting may be chosen with

definite time or IDMT. The IDMT
curves are in compliance with the IEC
255-3 standard. They are of the
standard inverse, very inverse and
extremely inverse types.
The low setting may also be used
with the RI curve.

n

the high setting is of the definite

time type.

earth protection

The earth fault protection operates by
residual current measurement: it uses
the sum of the sensor secondary
currents.
Like phase protection, earth
protection has two separately
adjustable settings.

LL and LH models

There are two models of the VIP300:
VIP300LL and VIP300LH, They differ
with respect to :

n

operating range.

Refer to the chapter entitled "choice
of sensors and operating ranges".

n

the VIP300LH has a table for

setting "equivalent time multiplier"
conversion on the front.

sensors

In order for the specified
performances to be obtained, the
VIP300 relay must be used with the
following current transformers:

n

CRa and CRb sensors:

(for RM6s 1998 and later).

n

CSa and CSb sensors of the SFset

circuit breaker. The CSa and CSb
sensors have the same number of
secondary turns as the CRa and CRb
sensors respectively.

n

200/1 and 800/1 sensors of the

Ringmaster:

description

n

The VIP300 relay is mounted in a

polycarbonate injected casing which
protects it against dripping water and
dusty environments.
The front is protected by a
transparent cover fitted with a sealing
joint. The cover may be lead-sealed
to prohibit access to the settings.

n

Rotating selector switches are

used for setting. The phase setting
current and earth fault setting current
are set in amperes. This means that
the scale on the front must be
adapted to suit the sensor used. This
is done by positioning a "setting scale
label" on the relay at the time of
assembly.

n

Connections are made on the back

using fast-on clips.

indication

Two indicators indicate the origin of
tripping (phase or earth). They stay in
position after a break in the relay
power supply.
Two LEDs (phase and earth) indicate
that the low setting has been overrun
and that the time delay is running.

background image

technical manual VIP300

4

2. use and settings

front view

I>>

(sec)

0.03

0.05

0.1

0.2

0,4

0,6

0,9

1.5

(x Ios)

t>>

t>

(sec)

0.1

0.05

0.6

0.15 0.2

0.3

0.4

0.07

x 1

x 10

I>

overcurrent

phase

curve selection

curve selection

Is

I>

Ios

Io>

to

>

(sec)

to

>>

VIP300LL range: x 1

sensors:

earth fault

Io>

reset

trip

trip

minimum operating
phase current

:

10A

(A)

10

12

15

18

21 24 28

32

36

40

45

50

30

35

40

16

1

2

4

8 12

20

25

6

(A)

DT only

(x Is)

3

1

1.2

1.8

2.4

2.7

2.1

1.5

DT only

(x Ios)

DT

SI

VI EI

RI

off

(x Is)

3

4

6

9

12

15

20

off

x 1

x 10

VIP 300

1.2Is

10Is

t>

I>>

t>>

EI, VI, SI

I>

RI

DT

Is

Io>>

DT

SI

VI EI

RI

off

3

1

1.2

1.8

2.4

2.7

2.1

1.5

3

4

6

9

12

15

20

off

0.03

0.05

0.1

0.2

0,4

0,6

0,9

1.5

(sec)

0.07

0.05

0.1

0.15 0.2

0.3

0.4

0.6

VAP6 test plug

1

2

3

4

5

6

7 8

9

10

b

a

c

11

12

13

14 15 16

17

18

19

20

e

d

CRa 51007003F0

- front panel -

f

phase protection

earth protection

other functions

1. phase setting zone
2. setting overrun indicator
3. phase trip indicator
4. phase setting current Is
5. choice of low setting curve type
6. low setting I>
7. low setting time delay t>
8. multiplying factor (low setting)
9. high setting I>>
10. high setting time delay t>>

11. earth setting zone
12. setting overrun indicator
13. earth trip indicator
14. earth setting current Ios
15. choice of low setting curve type
16. low setting Io>
17. low setting time delay to>
18. multiplying factor (low setting)
19. high setting Io>>
20. high setting time delay to>>

a. setting scale label
b. sensor and range information
c. indicator reset
d. minimum operating current
e. VAP6 test plug
f. VIP300LL: tripping curves
VIP300LH: table for « equivalent
time multiplier » conversion.

background image

technical manual VIP300

5

2. use and settings (cont’d)

tripping curves

1,2 Is

10 Is

t>>

t>

I>>

SI, VI, EI, RI

low setting

4

10

9

5

8

7

Is

fig 1: phase setting : IDMT low threshold

1,2 Is

I>

t>>

t>

I>>

fig 2: phase setting: definite time low threshold

DT

low setting

5

6

9

10

4

8

7

Is

settings

phase protection setting

The numbers indicated on the curves
opposite are those of the phase
protection setting switches (refer to
the diagram of the front view).

Set:

n

setting current Is (4)

n

type of low setting I> curve (5)

IDMT: RI, SI, VI, EI
definite time: DT

n

low setting I> (6)

This setting is only active if the low
setting curve chosen is of the definite
time DT type (fig 2). For the other
choices, SI, VI, EI, RI (fig 1), the
selector switch is disabled.

n

low setting time delay t> (7) and (8)

n

high setting I>> (9)

n

high setting time delay t>> (10)

earth protection setting

The principle is the same as for
phase protection.

Set:

n

setting current Ios (14)

n

type of low setting Io> curve (15)

IDMT: RI, SI, VI, EI
definite time: DT

n

low setting Io> (16)

This setting is only active if the low
setting curve chosen is of the definite
time DT type. For the other choices,
SI, VI, EI, RI, the selector switch is
disabled.

n

low setting time delay to> (17) and

(18)

n

high setting Io>> (19)

n

high setting time delay to>> (20)

operation

The high and low settings operate
separately. The tripping order results
from the "logical OR" between the
two settings.

background image

technical manual VIP300

6

2. use and settings (cont’d)

phase protection

1. phase protection setting
zone

All the information concerning phase
protection is grouped together in the
dark zone of the upper half of the
front face.

2. setting overrun indicator

When the red indicator blinks, it
means that the phase protection low
setting time delay is running. When
this is the case, if the current does
not decrease, the relay will trip.

n

for IDMT curves (SI, VI, EI), the

LED lights up when the current is
greater than 1.2 times the setting
current Is.

n

for the IDMT curve (RI), it lights up

when the current is greater than the
Is setting.

n

for the definite time curve DT, it

lights up when the low setting is
overrun.

F

also refer to "indicator reset

button".

3. trip indicator

It is normally black and turns yellow
to indicate that the phase protection
has given a tripping order. It stays in
the same status, even when the relay
is no longer energized.

4. choice of setting current Is

The setting current setting range
depends on the sensor and range
used: the selector switch scale
should be adapted to suit the sensor
and range using the setting scale
label.

F

also refer to "choice of sensors

and operating ranges" chapter.

5. choice of type of low setting
curve

DT: definite time
SI: inverse time
VI: very inverse time
EI: extremely inverse time
RI: specific curve
off: low setting is disabled.

6. choice of low setting I>

The setting is a multiple of the setting
current. It is only active for definite
time settings (selector switch 5 set to
DT).
If the tripping curve is selected with
IDMT (selector switch 5 set to RI, SI,
VI, EI), the selector switch has no
effect.

7. setting of low setting time
delay t>.

n

If the tripping curve is of the

definite time (DT) type, the selector
switch sets the low setting time delay.

n

If the curve is of the IDMT type (RI,

SI, VI, EI), the value displayed is the
tripping time for a phase current
equal to 10 times the setting current.

8. low setting time delay
multiplying factor.

In the x10 position, the time delay
displayed on selector switch 7 is
multiplied by 10.

9. setting of high setting I>>.

The high setting is chosen as a
multiple of the setting current.
In the "off" position, the high setting is
disabled.

10. setting of high setting time
delay t>>.

The time delay is set directly in
seconds.

background image

technical manual VIP300

7

2. use and settings (cont’d)

earth protection

The setting principle is the same as
for phase protection.

11. earth protection setting
zone

The earth protection settings are
grouped together in the dark zone of
the lower half of the front face.

12. setting overrun indicator

When this indicator blinks, it means
that the earth protection low setting
time delay is running. When this is
the case, if the current does not
decrease, the relay will trip.

n

for IDMT curves (SI, VI, EI), the

LED lights up when the current is
greater than 1.2 times the setting
current Ios.

n

for the IDMT curve (RI), it lights up

when the current is greater than the
Ios setting.

n

for the definite time curve DT, it

lights up when the low setting is
overrun.

F

for the cases above, the LED only

lights up when a phase current is
greater than the minimum operating
current.

F

also refer to "indicator reset

button".

13. trip indicator

It is normally black and turns yellow
to indicate that the phase protection
has given a tripping order. It stays in
the same status, even when the relay
is no longer energized.

14. choice of setting current Ios

This is the maximum residual current
that can flow in the network without
the protection being triggered.
The Ios current setting range
depends on the sensor and range
used: the selector switch scale
should be adapted to suit the sensor
and range using the setting scale
label.

F

also refer to "choice of sensors

and operating ranges" chapter.

15. choice of type of low setting
curve

DT: definite time
SI: inverse time
VI: very inverse time
EI: extremely inverse time
RI: specific curve
off: low setting is disabled.

16. choice of low setting Io>

The setting is a multiple of the setting
current. It is only active for definite
time settings (selector switch 15 set
to DT).
If the tripping curve is selected with
IDMT (selector switch 15 set to RI, SI,
VI, EI), the selector switch has no
effect.

17. setting of low setting time
delay to>.

n

If the tripping curve is of the

definite time (DT) type, the selector
switch sets the low setting time delay

n

If the curve is of the IDMT type (RI,

SI, VI, EI), the value displayed is the
tripping time for an earth current
equal to 10 times the setting current.

18. low setting time delay
multiplying factor.

In the x10 position, the time delay
displayed on selector switch 17 is
multiplied by 10.

9. setting of high setting Io>>.

The high setting is chosen as a
multiple of the setting current Ios.
In the "off" position, the high setting is
disabled.

10. setting of high setting time
delay t>>.

The time delay is set directly in
seconds.

background image

technical manual VIP300

8

2. use and settings (cont’d)

other functions

CRb 51007004F0
VIP300LL range: x 1

Is

Ios

(A)

6.2

12.5

25

37

50 75

187

218

156

100

125

250

62

75

94

112

131 150 175

200

225

250

281

312

(A)

recto

minimum operating
phase current : 62A

CRb 51007004F0
VIP300LL range: x 4

Is

Ios

(A)

25

50

100

200 300 400

150

875

1000

750

625

500

250

300

375

450

525 600 700

800

900

1000

1125

1250

(A)

verso

minimum operating

phase current:250A

- setting scale label -

sensors:

sensors:

- how to install the setting scale label -

a. setting scale label

n

it should be mounted on the

VIP300 when it is assembled on the
circuit breaker. The label indicates
the scales for the phase setting
current and earth protection setting
current. It is inserted, from the top,
behind the transparent part of the
front face.

n

each VIP300 comes with a set of

labels. Install the label that matches:
- the type of sensor used
- the VIP300 model
- the range used

n

each setting scale label matches a

sensor and is printed on both sides
for each of the 2 ranges. The label
may therefore be turned around if the
VIP300 range is changed during the
service life of the installation.

F

also refer to "assembly" chapter.

b. sensor and range indication

The text is printed on the setting
scale label.
When the label is installed in the slot,
the text is hidden by an opaque zone.
It is not visible to the user.

c. indicator reset button

The button is accessible when the
transparent cover is closed. When
the button is pressed, 2 actions are
triggered:

n

it resets (black position) the 2

phase and earth trip indicators. When
the relay is no longer energized, it is
still possible to reset the indicators for
about 48 hours. After that time, they
may be reset after the VAP6 is
plugged in.

n

it triggers the lighting up of the 2

red LEDs (about 3 sec). This
indicates that:
- the relay is energized. The indicator
lights up when the current is greater
than the minimum operating current.
- relay self-testing results are OK.
If one of the two conditions is not
met, the indicators do not light up.
This function may be used to carry
out a basic relay operation test.

d. minimum operating current

The minimum operating current is the
phase current required for the relay to
be energized and operational. It is
printed on each setting scale label.
The value given on the setting scale
label is the single-phase rms
minimum operating current.
The minimum operating current is
always the lowest setting current
setting.

F

note regarding minimum

operating current:
The VIP300 does not operate below
the minimum operating current level.
As a result, if the earth protections
are set below the minimum operating
current, they will only take effect
when there is phase current greater
than or equal to the minimum
operating current.

e. VAP6 test plug

The test plug is exclusively designed
for connection of the VAP6 which is
used for fast, simplified relay testing.
The operation may be carried out
while the relay is operating since the
VAP6 and VIP300 provide the
possibility of testing with inhibition of
circuit breaker tripping.

F

also refer to the "testing of the

VIP300 and use of the VAP6"
chapter.

- testing of the VIP300 using the VAP6 -

background image

technical manual VIP300

9

3. choice of sensors and operating ranges

selection principle

Choose the sensor to be used and
the VIP300 connection range in
accordance with the desired
operating range. Refer to the charts
below.

sensors

The VIP300 should be used with the
specified sensors. The relay/sensor
assembly must be used together in
order to comply with the
characteristics, in particular:
- operation across the range
- response time
- accuracy
- short-circuit current behaviour
It is compulsory for the 3 sensors to
be of the same type.

sensors specified for VIP300LL:

- CRa 200/1 51007003F0 (1)
- CRb 1250/1 51007004F0 (1)

sensors specified for
VIP300LH:

- Ringmaster 200/1 4509996A0
- Ringmaster 800/1 4509169A0

(1): for RM6 model 98 and higher.

range

The VIP300 relay contains input
transformers that have an
intermediary tap on the primary
winding. Each tap corresponds to a
rating with a different operating range.

VIP300LL model ranges:
- X1
- X4
VIP300LH model ranges:
- X2
- X4

VIP300LL model operating ranges

CRa

CRb

10

20K

100

1k

10k

20

30

60

200

300

600

2k

3k

6k

4k

50

40

62,5

312

6,25K

25K

250

1,25K

range x1

range x4

range x4

range x1

10

200

1k

Amps

VIP300LH model operating ranges

Ringmaster 200/1

Ringmaster 800/1

10

20K

100

1k

10k

20

30

60

200

300

600

2k

3k

6k

4k

40

80

400

8K

16K

160

800

range x2

range x4

range x4

range x2

200

100

20

2k

Amps

operating current Is setting range

selective operating range

For a given operating range, the
bottom of the setting current range
represents the relay minimum
operating current.

background image

technical manual VIP300

10

4. connection scheme

wiring to x1 (or x2) range

VIP300LL

S1

S2

S1

S2

S1

S2

x 4

x 4

x 4

x 4

P1

P2

P1

P2

P1

P2

1

2

3

3

4

5

6

7

8

9

1

2

(VIP300LH)

x 1

(x2)

x 1

(x2)

x 1

(x2)

x 1

(x2)

L3

L2

L1

Io

MITOP

+

-

15

16

10

11

12

13

14

0 V

wiring to x4 range

VIP300LL

S1

S2

S1

S2

S1

S2

x 4

x 4

x 4

x 4

P1

P2

P1

P2

P1

P2

1

2

3

3

4

5

6

7

8

9

1

2

(VIP300LH)

x 1

(x2)

x 1

(x2)

x 1

(x2)

x 1

(x2)

L3

L2

L1

Io

MITOP

+

-

15

16

10

11

12

13

14

0 V

The connection is made on the back
of the VIP300

connection using fast-on clips
The standard way to connect the
VIP300 is by means of 6.35 mm fast-
on clips.

background image

technical manual VIP300

11

5. assembly

cut-out

161 0.5mm

130 0.5mm

- drilling of cut-out -

The VIP300 is flush-mounted in a
rectangular cut-out made in a metal
plate 3 mm thick at the most.

assembly

E

V

N

P

n

insert the VIP300 in the cut-out and

correctly position the 2 lower pins (E)
of the casing on the edge of the
metal plate cut-out.

n

tighten the screws (V) on the 2

mounting lugs accessible via the front
face after having opened the
transparent cover.

n

after tightening, make sure that the

latch (N) of each lock (visible on the
rear face) is in the vertical position,
pressing against the support plate.

F

the latch may be put into the

vertical position by loosening each of
the screws (V) before tightening
them.

n

the hole (P) may be used to lead-

seal the relay after the setting scale
label is installed and the settings are
made.

installation of the setting scale label

M

n

slide the setting scale label into

position behind the transparent part
of the front face.

F

refer to the section entitled

"choice of the setting scale label".

n

make sure that the information

given at the top of the label (M)
matches:
the sensor used (sensor)
the VIP300 model
the range used (range)
This information is hidden when the
label is in position.

n

make sure that it is pushed right to

the bottom of the slot.

n

to remove the label, use the hole in

the top, if necessary with the help of
the tip of a pencil or a screwdriver.

background image

technical manual VIP300

12

5. assembly (cont’d)

choice of the setting scale label

for VIP 300 LL with CRa sensors

for VIP 300 LL with CRb sensors

Is

Ios

minimum operating

phase current : 10A

10

12

15

18

21 24 28

32

36

40

45

50

(A)

30

35

40

16

1

2

4

8

12

20

25

6

(A)

VIP300LL range: x 1

sensors:
CRa 51007003F0

recto

sensor:

VIP300LL range: x 4

Is

Ios

4

8

16

24

32 48 64

80

160

140

120

100

(A)

72

84 96 112

128

144

160

180

200

40

48

60

(A)

minimum operating
phase current :40A

verso

CRa 51007003F0

x 1 range x 4 range

Is

Ios

(A)

6.3

12.5

25

37

50 75

187

218

156

100

125

250

63

75

94

112

131 150 175

200

225

250

281

312

(A)

recto

minimum operating
phase current : 63A

Is

Ios

25

50

100

200

300 400

150

875

1000

750

625

500

(A)

250

300

375

450

525 600 700

800

900

1000

1125

1250

(A)

verso

minimum operating

phase current:250A

sensor:

VIP300LL range: x 1

CRb 51007004F0

sensor:

VIP300LL range: x 4

CRb 51007004F0

x 1 range x 4 range

for VIP 300 LH with 200/1 RMR sensors

for VIP 300 LH with 800/1 RMR sensors

Is

Ios

4

8

16

24

32 48 64

80

160

140

120

100

(A)

72

84 96 112

128

144

160

180

200

40

48

60

(A)

minimum operating
phase current : 40A

verso

sensor:

VIP300LH range: x 4

200/1: 4509996A0

Is

Ios

2

4

8

12

16 24 32

40

80 70

60

50

(A)

36

42 48 56

64

72

80

90

100

20

24

30

(A)

minimum operating
phase current : 20A

recto

sensor:

VIP300LH range: x 2

200/1: 4509996A0

x 2 range x 4 range

Is

Ios

(A)

8

16

32

48

64 96

240

280

200

128

160

320

80

96

120

144

168 192 224

256

288

320

360

400

(A)

minimum operating
phase current : 80A

sensor:

VIP300LH range: x 2

800/1 4509169A0

Is

Ios

16

32

64

128

192 256

96

560

640

480

400

320

(A)

160

192

240

288

336

384

448

512

576

640

720

800

(A)

minimum operating

phase current:160A

sensor:

VIP300LH range: x 4

800/1 4509169A0

verso

recto

x 2 range x 4 range

background image

technical manual VIP300

13

6. IDMT tripping curves

n

the curves in this chapter indicate

the IDMT low setting tripping times for
the 16 time delay t> (or to>) settings.

n

the phase protection and earth

protection curves are the same.

n

the numbers given on the right of

the curves represent the position of
the time delay t> (or to>) selector
switch.
(if the multiplying factor x1 / x10 is in
the x10 position, multiply the times
indicated by 10).

SI curve

SI

I/Is

t (s

)

0.01

0.1

1

10

100

1

10

100

0,05

0,07

0,1

0,15

0,2

0,3

0,4

0,6

1,2 Is

background image

technical manual VIP300

14

6. tripping curves (cont’d)

VI curve

VI

I/Is

t (s

)

0.01

0.1

1

10

100

1

10

100

0,05

0,07

0,1

0,15

0,2

0,3

0,4

0,6

1,2 Is

background image

technical manual VIP300

15

6. tripping curves (cont’d)

EI curve

EI

I/Is

t (s

)

0.01

0.1

1

10

100

1000

1

10

100

0,05

0,07

0,1

0,15

0,2

0,3

0,4

0,6

1,2 Is

background image

technical manual VIP300

16

6. tripping curves (cont’d)

RI curve

RI

I/Is

t (s

)

0.01

0.1

1

10

1

10

100

0,05

0,07

0,1

0,15

0,2

0,3

0,4

0,6

background image

technical manual VIP300

17

7. technical characteristics

phase protection

accuracy

see notes

low setting I>

±

5% or 0/+2A

1

low setting time delay t>

definite time
IDMT

±

2% or

±

20 ms

class 5 according to IEC 60255-3 or
0/+20ms

2, 8
2, 8

high setting I>>

±

5%

high setting time delay t>>

±

2% or

±

20 ms

2

% of pick-up

95%

storage time

20 ms

earth protection

accuracy

see notes

low setting Io>

±

5% or 0/+2A

3, 4, 5

low setting time delay to>

definite time
IDMT

±

2% or

±

20 ms

class 5 according to IEC 60255-3 or
0/+25ms

2, 8
2, 5, 8

high setting Io>>

±

5%

high setting time delay to>>

±

2% or

±

20 ms

2, 8

% of pick-up

95%

storage time

20 ms

general characteristics

value

steady thermal resistance

240 A
1500 A
240 A
960 A

with CRa sensor
with CRb sensor
with RMR 200/1 sensor
with RMR 800/1 sensor

1 sec thermal resistance

25 kA/1s
25 kA/1s
20 kA/1s

with CRa, CRb, RMR800/1
sensors
with RMR200/1 sensor on
range x2
with RMR200/1 sensor on
range x4

operating frequency

50 Hz

±

10%, 60 Hz

±

10%

operating temperature

-25° C to +70° C

storage temperature

-40°C to +85°C

weight

1.7 kg

minimum operating current

range

value

see notes

VIP300LL + CRa sensor

x1

10A

7

x4

40A

VIP300LL + CRb sensor

x1

62A

x4

250A

VIP300LH + RMR 200/1 sensor

x1

20A

x2

40A

VIP300LH + RMR 800/1 sensor

x1

80A

x2

160A

climatic resistance

standard

severity

low temperature operation

IEC 60068-2-1

-25°C, 16h

low temperature storage

IEC 60068-2-1

-40°C, 96h

high temperature operation

IEC 60068-2-2

+70°C, 16h

high temperature storage

IEC 60068-2-2

+85°C, 96h

fast changes in temperature

IEC 60068-2-14

-25°C to +70°C, 5 cycles

operation in damp heat

IEC 60068-2-3

56 days, 93% RH

salt spray

IEC 60068-2-52

severity 1

mechanical resistance

standard

severity

vibrations

IEC 60255-21-1

class 2

shocks and jolts

IEC 60255-21-2

class 2

earthquakes

IEC 60255-21-3

class 2

enclosure protection index

EN 60529

IP54, (cover closed)

fire resistance

IEC 60695-2-1

650°C

background image

technical manual VIP300

18

7. technical characteristics (cont’d)

electrical resistance

standard

severity

sensor input isolation

IEC 60255-5

2 kV rms, 50 Hz, 1 mn

1.2/50 µs impulse voltage

IEC 60255-5

5 kV, note 6

1 MHz dampened oscillating wave

IEC 60255-22-1

2,5 kV cm, note 6
1 kV dm

rapid transient bursts

IEC 60255-22-4

4 kV cm and dm, 5 kHz burst, note 6

1.2/50(8-20 µs) hybrid wave

IEC 61000-4-5

2 kV, 42 ohms, note 6

electrostatic discharge

IEC 60255-22-2

8 kV in air, 6 kV on contact

HF electromagnetic field

IEC 60255-22-3

30V/m not modulated, 27 to 1000 MHz

EN 50082-2

10 V/m mod. ampl., 80 to 1000 MHz

EN 50082-2

10 V/m mod.impuls., 900 MHz

notes

1. Value given for three-phase
VIP300 power supply.
For single-phase operation, the
accuracy range is

±

10% or 0/+4A.

For the low setting, this does not
generally represent a real operating
situation. However, it may occur
during injection testing carried out
with single-phase.
The error is mainly due to the non-
linearity of the sensors and VIP300
input transformers with weak current,
the inaccuracy being accentuated
when the relay is only supplied by
one phase.

2. The accuracy is indicated for a
fault that occurs when the VIP300 is
already supplied by the current let
through by the circuit breaker. The
accuracy is indicated for sinusoidal
current. In the event of closing while
a fault is present, the tripping time
may be extended by:

+30 ms at 1.5 Is
+20 ms from 2 Is to 10 Is
+10 ms above 10 Is

3. Generally speaking, the accuracy
ranges of earth protection times and
settings are indicated for when the
VIP300 is supplied by current that is
greater than or equal to the minimum
operating current. The measurement
of a setting for earth protection with
single-phase supply is therefore not
significant if the setting is lower than
the minimum operating current.

4. Value given for three-phase
VIP300 supply. For single-phase
testing, the accuracy is

±

10% or

0/+4A. For the low setting, this may
occur when the earth protection is
tested with single-phase supply, and
no supply by the other phases.

5. In the following specific conditions:

- VIP300LL
- with CRa sensor
- wiring to x1 range
- if Ios < 8A
- if phase current < 20A

the setting and time delay
characteristics are:

- low settings:

±

10% 0/+4A

- class not specified

6. Not applicable to test plug

7. Accuracy

±

10% or

±

1.5A.

The value indicates the guaranteed
minimum operating current for single-
phase operation. With three-phase
oepration, it may be less than the
value indicated.

8. The tripping times indicated do not
include the mitop response time. Its
tripping time depends on its
mechanical load (for no load, its
tripping time is less than 5 ms)

background image

technical manual VIP300

19

7. technical characteristics (cont’d)

dimensions

159

179

139

22

raccordemen

90

127

6

background image

technical manual VIP300

20

8. testing of the VIP300 and use of the VAP6

presentation of the VAP6

battery test

phase overcurrent

on

test in progress

trip

earth fault

VAP 6

trip

inhibition

+

-

external mitop

VIP30
VIP35
VIP300
VIP50
VIP37

mitop

circuit breaker

earth fault

phase

overcurrent

trip

trip

test

VIP11,11R
VIP12R
VIP13
VIP17
VIP200,201

circuit breaker

phase

overcurrent

test

mitop

external

mitop

inhibition

- VAP6 front panel -

The VAP6 is a portable unit that is
connected to the VIP300 to carry out
simplified testing.
The test can be carried out in the
following two cases:
- the VIP300 is already supplied by
the sensors.
- the VIP300 is not supplied. In this
case, the VAP6 batteries supply
power to the relay.

The test consists of:
- starting up the VIP300 central unit
self-testing sequence.
- injecting a stimulus to simulate a
phase fault.
- injecting a stimulus to simulate an
earth fault.
- checking tripping.

F

refer to the description of the test

in the section entitled "test sequence"

F

the VAP6 is supplied by batteries.

Therefore the parts of the VIP300
that run on AC current are not
checked using this method (input and
supply circuits).

push-buttons

n

battery test: if the batteries are

OK, the "on" indicator lights up while
the button is pushed.

n

phase overcurrent: it sends the

phase protection test stimulus. The
stimulus is equivalent to 20 times the
setting current Is.

n

earth fault: it sends the earth

protection test stimulus. The stimulus
is equivalent to 20 times the earth
setting current Ios.

n

trip inhibition: press the "trip

inhibition" button if the VIP300 test
should be carried out without tripping
of the circuit breaker. Circuit breaker
tripping is inhibited while the ’trip
inhibition" button is pressed, even if
the tripping order results from a real
fault.

indicators

n

on: indicates that the batteries are

operating. Also lights up when the
battery test is carried out by pressing
"battery test".

n

test in progress: confirms sending

of the test stimulus to the VIP300.

n

trip: it is used to test other relays in

the VIP range. It is not to be
considered for the VIP300 test. (it
lights up for a transient period when
the VIP300 sends a tripping order;
whether or not the circuit breaker is
inhibited).

"external mitop" output

It may be used to connect an
auxiliary mitop designed, for instance,
to stop a stop watch during operating
tests. The mitop is triggered at the
same time as the circuit breaker
mitop. It is not inhibited by pressing
the "trip inhibition" button.

batteries

n

the batteries are normally

deactivated and are automatically
activated when the VAP6 is
connected to the VIP300.
They are activated in the following
cases:
- pressing the "battery test" button.
- direct connection to a VIP3X or
VIP5X relay.
- connection to the adapter cord
designed for testing of the VIP1X or
VIP2X relays.

n

to install or change the batteries,

open the unit by removing the 4
screws on the bottom of the unit. Be
sure to use the correct polarities.

technical characteristics

supply:

3 x 9V 6LR61

batteries
weight:

0.45 kg

dimensions: 93x157x45

background image

technical manual VIP300

21

8. testing of the VIP300 and use of the VAP6 (cont’d)

VAP6 test sequence

The test may be carried out with or
without current in the sensors. During
the test operations, all the VIP300
settings are effective; the relay
should perform in accordance with
the settings. During the test, the relay
remains operational and will give a
tripping order in the event of a fault,
unless the "trip inhibition" button is
pressed.

n

connect the VAP6 to the "VAP6

test plug". The VAP6 batteries are
activated and the "on" indicator lights
up.

n

press the VIP300 "reset" button.

- if the 2 "trip" indicators were yellow,
they become black.
- the 2 red I> and Io> indicators of the
VIP300 light up for about 3s to
indicate that the central unit has
correctly performed self-testing.

n

press the "trip inhibition" button if

the test should be carried out without
tripping of the circuit breaker.

F

be sure to continue pressing the

"trip inhibition" button throughout the
time it takes to send the stimulus.

n

press the "phase overcurrent"

button to send the phase protection
test stimulus.
- continue pressing the button
throughout the duration of the
stimulus. The stimulus represents
about 20 times the setting current Is.
- the VAP6 "test in progress" indicator
lights up to confirm the sending of the
stimulus to the VIP300 relay.
- the red "I>" indicator of the VIP300
blinks during the time delay period.
- then the VIP300 phase "trip"
indicator turns yellow.
- the circuit breaker trips if it is not
inhibited.

F

if the "phase overcurrent" button is

held down after tripping, the VIP300
starts the time delay/tripping cycle
again; this is normal operation.
In that case:
- the VAP6 red "trip" indicator lights
up for a transient period each time
there is a trip.
- depending on the time delay setting,
the VIP300 red "I>" indicator may be
off or blink rapidly and/or in an
irregular manner.

n

press "earth fault" to test operation

of the earth protection. The stimulus
injected is equal to 20 times the
setting current Ios. Use the same
procedure as for the phase protection
test.

n

disconnect the VAP6.

In order to save batteries, do not
leave the VAP6 connected to the
relay unnecessarily.

background image

technical manual VIP300

22

Notes

background image

technical manual VIP300

23

Notes

background image

technical manual VIP300

24

Schneider Electric SA

Postal address
F-38050 Grenoble cedex 9
Tél : +33 (0)4 76 57 60 60
Télex : merger 320842F
http://www.schneider-electric.com
Rcs Nanterre B 954 503 439

Rcs Nanterre B 954 503 439

As standards, specifications and designs change
from time to time, please ask for information
given in this publication

Publishing: Schneider Electric SA
Design, production: Schneider Electric SA
Printing:

This document has been
printed on ecological paper

PCRED399008EN

ART. 20499

04 / 1999


Document Outline


Wyszukiwarka

Podobne podstrony:
06 INSTRUCTION MANUAL FUEL OIL FILTER 12153 3188 E
06 MANUAL TRANSAXLE (C153)(1)
06 MANUAL TRANSAXLE (C153)(1)
Chartek QC Manual 30 Jan 06
Interchar 212 Application Manual 7 june 06
06 MANUAL TRANSAXLE (C153)(1)
MT st w 06
Kosci, kregoslup 28[1][1][1] 10 06 dla studentow
06 Kwestia potencjalności Aid 6191 ppt
06 Podstawy syntezy polimerówid 6357 ppt
06
06 Psych zaburz z somatoformiczne i dysocjacyjne
GbpUsd analysis for July 06 Part 1
Probl inter i kard 06'03
06 K6Z4

więcej podobnych podstron