Cool


Cooling control

File: Cool.doc

Last edition: 4 of March 2003

Author: Mikael Krantz

History: 96-02-13/MK First released version.

96-10-03/MK Updated to Menta 1.20

97-09-02/MK Updated to Menta 3.0

98-03-09/MK Unit corrected.

98-12-30/MK New filename

2003-03-04/MK Updated to Menta 4.0

Description

Cooling battery controller is activated when the "Normal control" flag is true. In other cases, the controller are minimised.

Inputs

(Real) SP supply temperature, C.

(Real) Supply temperature, C.

(Binary) Normal control

Outputs

(Real) Cooling control signal, %.

Parameters

(Real) CoolingPBand 25 C

(Real) CoolITime 4 minutes

(Real) CoolingTravelTime 180 seconds

Public signals

(Real) CoolingPBand

(Real) CoolITime

(Real) Cooling