Cooling control
File: Cool.doc
Last edition: 4 of March 2003
Author: Mikael Krantz
History: 96-02-13/MK First released version.
96-10-03/MK Updated to Menta 1.20
97-09-02/MK Updated to Menta 3.0
98-03-09/MK Unit corrected.
98-12-30/MK New filename
2003-03-04/MK Updated to Menta 4.0
Description
Cooling battery controller is activated when the "Normal control" flag is true. In other cases, the controller are minimised.
Inputs
(Real) SP supply temperature, C.
(Real) Supply temperature, C.
(Binary) Normal control
Outputs
(Real) Cooling control signal, %.
Parameters
(Real) CoolingPBand 25 C
(Real) CoolITime 4 minutes
(Real) CoolingTravelTime 180 seconds
Public signals
(Real) CoolingPBand
(Real) CoolITime
(Real) Cooling