OPT


Optimise supply control

File: opt.doc

Last edition: 2003-03-11

Author: Mikael Krantz

History: 96-10-15/MK First released version.

97-08-19/MK Updated to Menta 3.0

2003-03-11/MK Updated to Menta 4.0

Description

Optimise for supply control. During optimising, the "MorningBoost" setpoint is added to the outdoor temperature compensated setpoint for the supply control. During day time, the outdoor temperature compensated setpoint is used for the supply control. During night time, the outdoor temperature compensated setpoint is used for the supply control.

Inputs

(Real) Outdoor temperature, °C

Outputs

(Real) Calculated SP for the supply, °C

Parameters

(TSCH) DayTime

(Real) NightSetback 3 °C

(Real) MorningBoost 6 °C

(Real) LowOutdoorTemp -10 °C

(Real) HighSupplyTemp 55 °C

(Real) MediumOutdoorTemp 0 °C

(Real) MediumSupplyTemp 50 °C

(Real) HighOutdoorTemp 15 °C

(Real) LowSupplyTemp 30 °C

Public signals

(TSCH) DayTime

(Real) NightSetback

(Real) MorningBoost

(Real) LowOutdoorTemp

(Real) HighSupplyTemp

(Real) MediumOutdoorTemp

(Real) MediumSupplyTemp

(Real) HighOutdoorTemp

(Real) LowSupplyTemp

(Real) SupplySP



Wyszukiwarka

Podobne podstrony:
4 Gen prom opt źródła naturalne
808D OPT Part3 pol POL pl PL
opt 2, uek, MOPG
analityka światło i met opt 2012 2013
dobor opt asort
Opt rodaka
platan sig opt mic instr2
Geologia 2008 4 opt elektr okreslanie skladu granulom gruntow
Pomoc kc opt
Pomoc kc opt
9 JIT i OPT Mech
opt czarnybór
Aby na wsi OPT OK (1)
808D OPT Part1 Operation 1212 pol pl PL
dost. oporządzenia i umund. śr. opt. i łączn. do działania, PP i K
Access 3 Opt Vocab Practice 6
mik opt pop, Biologia 2010, Rok I, Semestr I, Fizyka

więcej podobnych podstron